5046 Fossil Blvd - Special Inspections/Field Verification - 02/22/2015
B & B Balancing, Inc. CERTIFIED AIR TEST, ADJUST AND BALANCE REPORT FEBRUARY 22, 2015 Project: REDTAIL PONDS FISH Address: 1715 West Mountain Avenue Fort Collins, CO 80521 General Contractor: Fransen Pittman General Contractors Mechanical Contractor: Mountain Aire Mechanical, LLC Mechanical Engineer: Christopher Menges Engineering, Inc. Prepared By: B & B Balancing, Inc. 1531 Tweed Street Colorado Springs, CO 80909 (719) 632-4898 - Phone (719) 633-8074 - Fax NEBB Certification # 3255 LARRY Q:6AR71.EY CERTIFICATION 3255 UP.301J76 j B &B Ba arcing, Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECTM SYSTEM/UNIT. EF-1-104 AREA: Unit -.Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 59 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/2212015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-104 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-105 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test,Data Motor Volts 1 119 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 65 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data .' Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-105 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 3 of 66 Exhaust Fans B & B Baclancin.�r, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-106 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test 'Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 68 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-106 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-107 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data, Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 66 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-107 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 4 of 66 Exhaust Fans - B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-108 AREA: Unit Data _ Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 64 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 22, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data. Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-108 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-109 AREA: UnitData Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 57 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-109 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 5of66 Exhaust Fans ff &B Balanem Inc Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT.• EF-1-110 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 71 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data . Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-110 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-111 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number Q138013C Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 64 CFM SP Out Actual, in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Eric Bowhay Test Date: February 20, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase, 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-111 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 6 of66 Exhaust Fans -11 & B Ba lancir g Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-112 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 55 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. WC Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 20, 2015 Motor Data, Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model. Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-112 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-201 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 64 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor, Data ; Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor.Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model f Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-201 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 7of66 Exhaust Fans B& B Balancing, Inc Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-202 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 50 CFM Total CFM Actual 55 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 u Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-202 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-203 AREA: Unif Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 62 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-203 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 8 of 66 Exhaust Fans B, & B Balancer g► Ina. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-204 AREA: Unit Data Fan Manufacturer Reverse 0 Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 63 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-204 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-205 AREA: ,Unit Data Fan Manufacturer Reverse O Mate Fan Model Number QBBOBC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 50 CFM Total CFM Actual 70 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor`Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes i EF-1-205 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 9 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-206 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 79 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-206 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-207 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 76 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-207 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 10 of66 Exhaust Fans Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-9-208 AREA: Unit Data' Fan Manufacturer Reverse O Matic Fan Model Number QBBOBC Fan Serial Number Test Data Motor Volts 1 120 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 74 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data. Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-208 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF--1-209 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data' Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 72 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 `Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data , Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in, * Notes EF-1-209 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 11 of 66 Exhaust Fans B, & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEWUNIT: EF-1-210 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 50 CFM Total CFM Actual 71 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP in Actuat in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-210 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-211 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 79 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data . Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-211 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 12 of 66 Exhaust Fans Certification PROJECT: REDTAIL PONDS PSH 1715 WEST MOUNTAIN AVENUE FORT COLLINS, CO 80521 THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED THROUGHOUT THE REPORT. SUBMITTED & CERTIFIED BY: NEBB TAB FIRM: B & B BALANCING, INC. li+Ray.o,anRTLEY 1531 TWEED STREET `Ear_i�cA►aH' COLORADO SPRINGS, CO 80909L-EV.3bl/16 (719) 632-4898 - PHONE 719) 633-8074 - FAX dronla,` TAB SUPERVISOR: LARRY G. BARTLEY REG. NO.3255 SIGNATURE: DATE: FEBRUARY 22, 2015 B & B Balancing jnca Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT., EF-1-212 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.2 Amps Total CFM Design 50 CFM Total CFM Actual 76 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data , Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-212 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-213 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts MotorAmps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 80 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-213 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 13 of 66 Exhaust Fans B & B .Balancn:g, Inca Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-214 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 71 CFM SP Out Actual in, we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-214 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-215 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 71 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-215 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 14 of 66 Exhaust Fans B,.. , B Bae ancing Inc.. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-216 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number - TestiData Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 68 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-216 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-301 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 72 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 - Motor Data - Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-301 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 15of66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-302 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 80 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data, Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-302 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-303 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number OB80BC Fan Serial Number a Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 72 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-303 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 16 of 66 Exhaust Fans & B41ancingO Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-304 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 79 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP in Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2016 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data. Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-304 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-305 AREA: i Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 68 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual In. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in: Sheave Center Line in. * Notes EF-1-305 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 17of66 Exhaust Fans B B Balancing, Inc Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-306 AREA: Unit Data Fan Manufacturer Reverse 0 Matic Fan Model Number QB80BC Fan Serial Number Testbata Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 82 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data' Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-306 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-307 AREA: UnitData . Fan Manufacturer Reverse 0 Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 78 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-307 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 18 of 66 Exhaust Fans B & B Bala.n.cing jnc . Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-308 AREA: Unit Data ' Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number :Test'Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 78 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data: Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-308 22-Feb-15 Eric Bowhay Direct.Drive, no SSC SYSTEM/UNIT: EF-1-309 AREA: Unit Data _ Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 60 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated, Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-309 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 19 of66 Exhaust Fans 1g & B Balancing, g, Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-310 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 76 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave"Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-310 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-311 AREA: Unit Data, Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps. Total CFM Design 50 CFM Total CFM Actual 71 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor °Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-311 22-Feb-15 Eric Bowhay Direct Drive, no SSG B & B Balancing, Inc. Page 20 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT. EF-1-312 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number `Test Data Motor Volts 1 124 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 46 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-312 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-313 AREA: Unit" Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 56 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-313 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 21 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-314 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 77 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-314 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT. EF-1-315 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data ' Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 63 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-315 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 22 of 66 Exhaust Fans AMPS Amperes AHU Air Handling Unit BAS Building Automation System BUT British Thermal Unit CFM Cubic Feet per Minutes CHWP Chilled Water Pump CHWR Chilled Water Return CHWS Chilled Water Supply CV Constant Volume DAT Discharge Air Temperature DB Dry Bulb or Dead Band DP Differential Pressure EF Exhaust Fan ERV Energy Recovery Ventilator EXIST. (E) Existing F Fahrenheit FCU Fan Coil Unit FD Fire Damper FLA Full Load Amps FPM Feet per Minute GPM Gallons per Minute HOA Hand Off Auto HRV Heat Recovery Ventilator HWP Hot Water Pump HWR Hot Water Return HWS Hot Water Suppler FIX Heat Exchanger HZ Hertz B & B Balancing, Abbreviations Inc. in. WC Inches of Water Column LAT Leaving Air Temperature MA Mixed Air MAT Mixed Air Temperature MAU Make-up Air Unit OA Outside Air OAT Outside Air Temperature PD Pressure Drop PH Phase PTAC Portable Terminal Air Conditioner RAT Return Air Temperature RF Return Fan RH Relative Humidity RPM Revolutions per Minute RTU Roof Top Unit SA Supply Air SAT Supply Air Temperature SD Smoke Damper SP Static Pressure or Set Point SSc Variable Speed Controller VAV Variable Air Volume VFD Variable Frequency Drive VSD Variable Speed Drive VVT Variable Volume/Temperature W Watt WB Wet Bulb ZD Zone Damper Prepared By: B & B Balancing, Inc. 1531 Tweed Street Colorado Springs, CO 80909 (719) 632-4898 - Phone (719) 633-8074 - Fax IN LARRY 0. DAFM.EY CERTIFICATION 3255 e . PP.'3Y31„fi , B & B Balancing,, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-316 AREA: Unit Data Fan Manufacturer Reverse 0 Matic Fan Model Number QB80BC Fan Serial Number Test'Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 80 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-316 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-401 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 124 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 63 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 'Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1401 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 23 of 66 Exhaust Fans R & B Balancing, Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-402 AREA: Unit Data . Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 71 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data , '. Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-402 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-403 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Made[ Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 58 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor ,Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-403 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 24 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-404 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data _. Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 72 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-404 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-405 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 65 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 'Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1405 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 25 of 66 Exhaust Fans f & B B glancing, If.c. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-406 AREA: Unit Datar Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data . Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 63 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-406 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-407 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 78 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual In. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-407 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 26 of66 Exhaust Fans B & B Balancing, Inc. Fan unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-408 AREA: Unit,Data " Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 67 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we MotorAmps2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-408 22-Feb-15 Eric Bowhay Direct Drive, no SSG SYSTEM/UNIT: EF-1-409 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 68 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-409 22-Feb-15 Eric Bowhay Direct Drive, no SSG B & B Balancing, Inc. Page 27of 66 Exhaust Fans &_B .Bar anctng, Inc Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-410 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test`Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 71 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor'Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1410 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-411 AREA: Unit Data = Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 47 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 MotorData Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size In. Sheave Center Line in. * Notes EF-1-411 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancr'ng, Inc. Page 28 of 66 Exhaust Fans ff & B Balancing, Inc . Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-412 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80SC Fan Serial Number TeSi Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 65 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data ; Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Centerline in. * Notes I EF-1-412 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-1-413 AREA: Unit Data: Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data - Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 67 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3: Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-413 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 29 of66 Exhaust Fans BI & B Balancing, Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT. EF-1-414 AREA: Unit ;Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 62 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-414 22-Feb-15 Eric Bowhay Direct Ddve, no SSC SYSTEM/UNIT: EF-1-415 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 67 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1415 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 30 of66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-1-416 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 65 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-1-416 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-101 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts MotorAmps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 112 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-101 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 31 of 66 Exhaust Fans B &B Baiancin:g, -Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-102 AREA: :. Unit Delta . Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 120 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 113 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data. Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data ` Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-102 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-103 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 112 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-103 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 32 of66 Exhaust Fans B & B Balancing, Inc. Certified Test, Adjust and Balance Report February 22, 2015 Project: Redtail Ponds PSH Address: 1715 West Mountain Avenue Fort Collins, CO 80521 Instruments Used: Alnor EBT-721 Capture Hood w/Digital Manometer, Velocity Matrix, Airfoil, and Humidity & Temperature Probes Serial # 90635001; Certification Date: 2/16/2014 Fluke 337 Digital Clamp Meter Serial # 83707731; Certification Date: 2/18/2014 Omega HHT13 Pocket Laser Photo Digital Tachometer Serial # 1822060; Certification Date: 2/18/2014 Prepared By: B & B Balancing, Inc. 1531 Tweed Street Colorado Springs, CO 80909-2844 (719) 632-4898 - Phone (719) 633-8074 - Fax B & B Balancing, Ina. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT M SYSTEM/UNIT: EF-2-104 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 133 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-104 22-Feb-15 Eric Bowhay Direct Drive, no SSG SYSTEM/UNIT: EF-2-105 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-105 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 33 of66 Exhaust Fans B'- & B :Baldwing.9. Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft Collins, CO PROJECT #: SYSTEM/UNIT: EF-2.106 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 105 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we MotorAmps2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor 'Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-106 22-Feb•15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-107 AREA: Unit Data: , - Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 120 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-107 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 34 of 66 Exhaust Fans R & B Balancil g, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-108 AREA: Unit Data Fan Manufacturer Reverse 0 Matic Fan Model Number CF170ES Fan Serial Number Test'Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 115 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data . Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line In. "' Notes. EF-2-108 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-109 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 126'CFM SP Out Actual In. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. ' Notes I EF-2-109 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & 8 Balancing, Inc. Page 35of66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-110 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 114 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Lary Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data. Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-110 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-111 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 121 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor -Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor 'Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. " Notes I EF-2-111 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 36 of66 Exhaust Fans B & B Balancing, Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-112 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test,Data •, Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 128 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/2212015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 20, 2015 Motorbata Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-112 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-201 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data ` Motor Volts 1 121 Volts MotorAmps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 100 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Eric Bowhay Test Date: February 22, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-201 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 37of66 Exhaust Fans B, & B Balancing, Inc:. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-202 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test"Data Motor Volts 1 120 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 124 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Lary Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor ,Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-202 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-203 AREA: Unit Data, • -, Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 104 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-203 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 38 of 66 Exhaust Fans B & B Balancing, Inc, - Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT. EF-2-204 AREA: Unit Data . Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 104 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-204 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-205 AREA: UnitData Fan Manufacturer Reverse 0 Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.5 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data . Motor Sheave Make Motor Sheave Made[ Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line In. * Notes EF-2-205 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 39 of66 Exhaust Fans B. & Bad ancingr, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-206 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 128 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Lary Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-206 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-207 AREA: Unit Data _ Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data. . Motor Volts 1 120 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 109 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 MotorData' .. Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line In. * Notes EF-2-207 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 40 of66 Exhaust Fans K & B Balancirtg, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-208 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 113 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in, we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-208 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-209 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 110 CFM Total CFM Actual 122 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Eric Bowhay Test Date: February 20, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data' Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-209 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 41 of 66 Exhaust Fans B & B B,a�Iane ngr, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-210 AREA: Unit'Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number ;.:. Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM, Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data, Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-210 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-211 AREA: - Unit Data, Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number "Test Data Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 121 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave,Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-211 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 42 of66 Exhaust Fans B & B .Bala ncing- Inc's Roof Top Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: MUA-01 AREA: Unit Data Unit Manufacturer Captive Aire Unit Model Number A2-IBT-400-200-200-G15 Unit Serial Number 1886903 Unit Discharge Vertical /Down Unit Filter Quantity 6 Unit Filter Size 16x20x2 Test Delta' Total CFM Design 3500 CFM Total CFM Actual 3697 CFM Outside Air CFM Design 3500 CFM Outside Air CFM Actual 3697 CFM Return Air CFM Design CFM Return Air CFM Actual CFM MUA-01 / Supply Fan Fan RPM Design 1152 RPM Fan RPM Actual 1163 RPM Motor Volts 1 206 Volts Motor Amps 1 9.4 Amps Motor Amps 2 9.7 Amps Motor Amps 3 10.0 Amps MUA-01 Supply Outlet Summary DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 17, 2015 Motor Data MUA-01 I Supply Fan Motor Manufacturer Westinghouse Motor Frame 18014 Motor HP 3.7 HP Motor RPM 1750 RPM Motor Rated Volts 230 Volts Motor Phase 3 Motor FL Amps 13.6 Amps Motor Service Factor 1.15 Sheave Data MUA-01 I Supply Fan Motor Sheave Make PRP Motor Sheave Model 2VP42xl 1/8 Fan Sheave Make PRP Fan Sheave Model 2BK59Hx1 Number of Belts 2 Belt Size BX47 Sheave Center Line 17 3/4 in. Test Pressures Fan SP In Actual 0.76 in. we External SP In Actual 0.01 in. we External SP Out Actual 0.19 in. we Total SP 0.95 in. we Filter Pressure Drop 0.14 in. wc. Cooling Coil Pressure Drop in. wc. ' System /`Unit Outlet Type ' Size LxW / D % Prelim Deviation % Final Deviation Design Reading Prelim Reading Final Reading ° Outlet-01 SD-3 59 100 875 513 879 Outlet-02 SD-3 105 101 875 917 884 Outlet-03 SD-3 130 102 875 1135 892 Outlet-04 SD-3 129 119 1 875 1125 1042 Totals.:,;, - 105 0 -. 106 %q ' , 3,500 3,690 3 697 * Notes B & B Balancing, Inc. Page 1 of RootRon Units B &B :Batlancing, Inc, Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-212 AREA: .Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CH70ES Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 121 CFM SP Out Actual in. we Fan. RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data, Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-212 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-213 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data „ Motor Volts 1 123 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 112 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data , Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data . Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-213 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 43 of 66 Exhaust Fans B &B Ba anctng� Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-214 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor.Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data " Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-214 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-215 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test, Data Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 139 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps MotorAmps3 Amps Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-215 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 44 of 66 Exhaust Fans B &' B .a lancing, Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-216 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 108 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data, Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-216 22-Feb•15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT; EF-2-301 AREA: Unit Data , Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-301 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 45of66 Exhaust Fans .B, & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-302 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 127 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-3 22 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-303 AREA: Unit Data . Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 109 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we MotorAmps2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data , Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-303 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 46of66 Exhaust Fans B & B Balancing, Inc Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-304 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 118 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-304 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-305 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 105 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor' Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-305 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 47of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH DATE: 2/22/2015 LOCATION: Ft. Collins, CO CONTACT: Larry Bartley PROJECT #: SYSTEM/UNIT: EF-2-306 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 124 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-306 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-307 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 116 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-307 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 48 of66 Exhaust Fans B &B Balancing, Inc., Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-308 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design. 110 CFM Total CFM Actual 112 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. " Notes EF-2-308 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-309 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data ' Motor Volts 1 122 Volts MotorAmps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 115 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. ' Notes I EF-2-309 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing,, Inc. Page 49 of66 Exhaust Fans R &: B Balancing Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT M SYSTEM/UNIT: EF-2-310 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number TeSt'Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make - Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-310 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-311 AREA: ., Unit Data, . Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data - Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 100 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data, Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-311 22-Feb-15 Eric Bowhay Direct Drive, no SSC 8 & B Balancing, Inc. Page 50 of 66 Exhaust Fans B.,& B alancrg, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-312 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data .. Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 110 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor `Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line In. * Notes I EF-2-312 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-313 AREA: Unit Data, Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test' Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 110 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data, Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data• ; Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-313 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 51 of 66 Exhaust Fans 410 B & B Ba► I"noing, I , 0 Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-314 AREA: r Unit,Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 120 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-314 22-Feb-I5 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-315 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 108 CFM SP Out Actual In. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 'Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-315 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 52 of 66 Exhaust Fans B & B Balancing; Inc: Roof Top Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: RTU-01 AREA: Unit Data Unit Manufacturer TRANE Unit Model Number YSC072F3EMA02ZV Unit Serial Number 143711171L Unit Discharge Vertical !Down Unit Filter Quantity 4 Unit Filter Size 16x25x2 Test Data Total CFM Design 2205 CFM Total CFM Actual 2342 CFM Outside Air CFM Design 200 CFM Outside Air CFM Actual 213 CFM Return Air CFM Design 2005 CFM Return Air CFM Actual 2129 CFM RTU-01 / Supply Fan Fan RPM Design 994 RPM Fan RPM Actual 986 RPM Motor Volts 1 212 Volts Motor Amps 1 3.1 Amps Motor Amps 2 3.3 Amps Motor Amps 3 3.0 Amps RTU-01 Supply Out/et Summary DATE: 2/2212015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 22, 2015 Motor Data RTU-01 1 Supply Fan Motor Manufacturer Marathon Motor Frame 56 Motor HP 1 HP Motor RPM 1725 RPM Motor Rated Volts 200 Volts Motor Phase 3 Motor FL Amps 4.0 Amps Motor Service Factor 1.15 Sheave Data' RTU-01 1 Supply Fan Motor Sheave Make Browning Motor Sheave Model 1 VL34x5/8 Fan Sheave Make Browning Fan Sheave Model AK66x1 Number of Belts 1 Belt Size AX32 Sheave Center Line 9 1/4 in. Test Pressures Fan SP In Actual 0.52 in. we External SP In Actual 0.18 in. we External SP Out Actual 0.21 in. we Total SP 0.73 in. we Filter Pressure Drop w/Clg. Coil in. wc. Cooling Coll Pressure Drop0.24 in. wc. System !'Unit Outlet Type Size.LxW / D %.Prelim ' Deviation % Final Deviation. Design Reading Prelim Reading Final Reading , Outlet-01 SDA 10" 177 108 225 398 243 Outlet-02 SDA 10" 105 108 345 361 374 Outlet-03 SD-1 10" 82 109 330 269 361 Outlet-04 SDA 10" 90 109 330 297 359 Outet-05 SDA 10" 112 109 235 263 255 Outlet-06 SDA 6" 150 108 60 90 65 Outlet-07 SDA 8" 106 109 175 186 190 Outlet-08 SD-1 10" 74 94 375 276 353 Outlet-09 SD-1 1 8" 83 109 130 108 142 Tofais : - '' .. - 102' % 106 %o 2,205 2,248 2342 * Notes I - B & B Balancing, Inc Page 2 of Rootfton Units B & B Balancing, Ine Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-316 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test°Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 114 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-316 22-Feb-15 Eric Bowhay Direct Drive, no SSG SYSTEWUNIT. EF-2-401 AREA: Unit Data . Fan Manufacturer Reverse 0 Matic Fan Model Number CF170ES Fan Serial Number Test Data, Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 109 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data - Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-401 22-Feb-15 Eric Bowhay Direct Drive, no SSG B & B Balancing, Inc. Page 53 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-402 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 112 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data , Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2402 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-403 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 101 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual- RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-403 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 54 of 66 Exhaust Fans B & B .BaIanc.' IIn ►, Inc, Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-404 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 124 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 120 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line In. * Notes EF-2-404 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-405 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 124 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 119 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-405 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 55 of 66 Exhaust Fans B & B Balancing, Inc: Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-406 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF17CES Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we MotorAmps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-406 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-407 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 101 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-407 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 56 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-408 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 123 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 100 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2408 22-Feb-15 Eric Bowhay Direct Drive, no SSG SYSTEM/UNIT: EF-2-409 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test,Data Motor Volts 1 123 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 104 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM , SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-409 22-Feb-15 Eric Bowhay Direct Drive, no SSG B & B Balancing, Inc. Page 57of 66 ExhauslFans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-410 AREA: Unit.Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 106 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-410 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-411 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 124 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 119 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-411 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 58of66 Exhaust Fans B & B BaIancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-412 AREA: Unit Data Fan Manufacturer Reverse O Mabc Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 105 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-2-412 22-Feb-15 Eric Bowhay Direct Drive, no SSG SYSTEM/UNIT: EF-2-413 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps Total CFM Design 110 CFM Total CFM Actual 103 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-413 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 59 of 66 Exhaust Fans B &B BaIancin.g, Inc. Fan unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-414 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 102 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/2212015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-414 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-2-415 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 108 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: ConnorAnley Test Date: February 17, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2415 22-Feb-15 Eric Bowhay Direct Drive, no SSC B & B Balancing, Inc. Page 60 of 66 Exhaust Fans B & B Ballanct Ir g, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-2-416 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number CF170ES Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 110 CFM Total CFM Actual 107 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.7 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes I EF-2-416 22-Feb-15 Eric Bowhay Direct Drive, no SSC SYSTEM/UNIT: EF-3-01 AREA: Unit Data Fan Manufacturer Twin City Fan Fan Model Number T200 Fan Serial Number 41H21H Test Data Motor Volts 1 121 Volts Motor Amps 1 0.8 Amps Total CFM Design 94 CFM Total CFM Actual 208 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps * Notes Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 1.8 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. B & B Balancing, Inc. Page 61 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-3-02 AREA: Unit Data Fan Manufacturer Twin City Fan Fan Model Number T200 Fan Serial Number 41H21H Test Data Motor Volts 1 121 Volts Motor Amps 1 0.9 Amps Total CFM Design 94 CFM Total CFM Actual 104 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps * Notes SYSTEM/UNIT: EF-3-03 AREA: Unit Data Fan Manufacturer Twin City Fan Fan Model Number T200 Fan Serial Number 41 H21 H Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 94 CFM Total CFM Actual 104 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps * Notes DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: ConnorAnley Test Date: February 18, 2015 Motor Data „ Motor Rated Volts 120 Volts Motor FL Amps 1.8 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 1.8 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Made[ Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. B & B Balancing, Inc. Page 62 of 66 Exhaust Fans R & B BaIancing, Inc:. Roof Top Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT. RTU-02 AREA: Unit Data Unit Manufacturer TRANE Unit Model Number YSC072F3EMA02ZV Unit Serial Number 143711161L Unit Discharge Vertical /Down Unit Filter Quantity 4 Unit Filter Size 16x25x2 Test;Dat'a Total CFM Design 2600 CFM Total CFM Actual 2617 CFM Outside Air CFM Design 500 CFM Outside Air CFM Actual 521 CFM Return Air CFM Design 2100 CFM Return Air CFM Actual 2096 CFM RTU-02 / Supply Fan Fan RPM Design 1040 RPM Fan RPM Actual 1046 RPM Motor Volts 1 212 Volts Motor Amps 1 3.6 Amps Motor Amps 2 3.5 Amps Motor Amps 3 3.6 Amps RTU-02 Supply Outlet Summary DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 22, 2015 Motorbata RTU-021 Supply Fan Motor Manufacturer Marathon Motor Frame 56 Motor HP 1 HP Motor RPM 1725 RPM Motor Rated Volts 200 Volts Motor Phase 3 Motor FL Amps 4.0 Amps Motor Service Factor 1.15 Sheave Data RTU-02 I Suooly Fan Motor Sheave Make Browning Motor Sheave Model 1VL44x518 Fan Sheave Make Browning Fan Sheave Model AK56x1 Number of Belts 1 Belt Size AX32 Sheave Center Line 9 114 in. Test Pressures, Fan SP In Actual 0.72 in. External SP In Actual 0.32 in. we External SP Out Actual 0.29 in. we Total SP 1.01 In. we Filter Pressure Drop w/Clg. coil in, wc. Cooling Coll Pressure Drop0.29 in. wc. System /Unit' Outlet Type Size LxW l 'D %,Prelim Deviation 0/6Final' Deviation Design, Reading ' Prelim Reading Final - Reading `..' Outlet-01 34 97 190 65 185 Outlet-02 100 98 285 284 279 Outlet-03 101 96 280 283 269 Outlet-04 139 105 275 381 290 Outlet-05 105 104 155 163 161 Outlet-06 137 109 220 301 240 Outlet-07 18 103 220 40 227 Outlet-08 10 108 215 22 233 Outlet-09 92 104 160 147 167 Outlet-10 0 90 300 0 270 Outlet-11 59 99 300 176 296 Totals : • . ` 72 % 101 % 2,600 1,862 2,617 * Notes B & B Balancing, Inc. Page 3 of Rootfton Units B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-5-132 AREA: Unit Data Fan Manufacturer Twin City Fan Fan Model Number DSI-080AE Fan Serial Number H14-000000128365 Test Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 250 CFM Total CFM Actual 271 CFM SP Out Actual 0.08 in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual 0.20 in. we Motor Amps 2 Amps Motor Amps 3 Amps EF-5-132 Exhaust Inlet Summary DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 22, 2015 Motor Data Motor Rated Volts 115 Volts Motor FL Amps 3.9 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. System / Unit Outlet Type Size LxW I D % Prelim Deviation % Final Deviation Design Reading Prelim Reading, Final Reading Inlet-01 EG-2 124 109 100 124 109 Inlet-02 EG-2 196 110 50 98 55 Inlet-03 EG-2 113 107 100 113 107 Totals : 134 % 108 6% 250 335 271 * Notes B & B Balancing, Inc. Page 63 of 66 Exhaust Fans B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT. EF-5-204 AREA: Unit Data Fan Manufacturer Twin City Fan Fan Model Number DSI-080AE Fan Serial Number H14-000000128364 Test Data Motor Volts 1 122 Volts Motor Amps 1 0.4 Amps Total CFM Design 250 CFM Total CFM Actual 271 CFM SP Out Actual 0.07 in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual 0.18 in. we Motor Amps 2 Amps Motor Amps 3 Amps EF-5-204 Exhaust Inlet Summary DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 18, 2015 Motor Data Motor Rated Volts 115 Volts Motor FL Amps 3.9 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data , Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. System /Unit Outlet Type Size LxW / D -% Prelim Deviation %Final Deviation Design Reading, Prelim Reading Final Reading^ Inlet-01 EG-2 121 107 100 121 107 Inlet-02 EG-2 232 108 50 116 54 inlet-03 EG-2 123 110 100 123 110 Totals: 144 % 108 % 250 360, 271 * Notes B & B Balancing, Inc. Page 64 of 66 Exhaust Fans B & B Balancing, Inc . Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-5-304 AREA: " Unit Data Fan Manufacturer Twin City Fan Fan Model Number DSI-080AE Fan Serial Number H14-000000128362 Test Data Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps Total CFM Design 250 CFM Total CFM Actual 267 CFM SP Out Actual 0.08 in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual 0.20 in. we Motor Amps 2 Amps Motor Amps 3 Amps EF-5-304 Exhaust Inlet Summary DATE: 2/2212015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 18, 2015 Motor Data Motor Rated Volts 115 Volts Motor FL Amps 3.9 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. System / Unit Outlet Type Size LxW / D "/o Prelim Deviation % Final Deviation Design - Reading Prelim Reading ', Final Reading. Inlet-01 EG-2 100 103 100 100 103 Inlet-02 EG-2 240 110 50 120 55 Inlet-03 EG-2 120 109 100 120 109 Totals _ - t 136 % 107 %. 250 340 267 * Notes B & B Balancing, Inc. Page 65of66 Exhaust Fans B & B alanci g, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-5-404 AREA: Unit Data Fan Manufacturer Twin City Fan Fan Model Number DSI-080AE Fan Serial Number H14-000000128363 Test Data Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps Total CFM Design 250 CFM Total CFM Actual 266 CFM SP Out Actual 0.07 in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual 0.18 in. we Motor Amps 2 Amps Motor Amps 3 Amps EF-5-404 Exhaust Inlet Summary DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Eric Bowhay Test Date: February 18, 2015 Motor Data Motor Rated Volts 115 Volts Motor FL Amps 3.9 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. System l Unit Outlet Type Size LxW ! D % Prelim Deviation % Final Deviation Design Reading Prelim Reading Final Reading Inlet-01 EG-2 80 110 100 80 110 Iniet-02 EG-2 260 106 50 130 53 Inlet-03 EG-2 163 103 100 163 103 Totals : - 149 % 106 % 250 373 266' * Notes B & B Balancing, Inc. Page 66 of66 Exhaust Fans kW REGISTER GRILLE DIFFUSER SCHEDULE I v ' ��omom•macira0mmos� I13a�0��IDIDIe�O1I0m®oom ��IDI��IDIOI�®0®®OQnm � m�0m0�C7©a��®mO �mmm�vuovYa®ol�� Ila 1 mac] iw ew sld.Xm wa[en XXYm]I elm, mxma a]a Iwm eeu vela lam¢ F(Y1-I nac] wlol YVWIm w Lea amn umrzE emmXni Xm]n ILVXmc xulvX lanes w m E¢ Ymav YIM nenx wnec]E momnR. ® MAKE-UP AIR UNIT SCHEDULE WVl3L1Yk4 XI. MY 9P0.i a 1LN IE; pq R iM V11W dm yrt 1p RLlale Ylm wVD1 L1 d61R IW 6Y ESY. 91I L6! 16 W M WR IW-I � 4-®�Ytrmmil] W !SM a5 [G I n 10 IJw Ill IW ] 1 1. M Um 9WL M1142 t MLEdI9AlID1.TQ P]® MO wl 1FFl4X [WuwL wmlvl nu2t mn wy'w uu�I Ie:ut w r yy5I9E W] pp[ i.WtpM1 Ea[WF6 pLLUF NL ROSRO WIIaIS. WPX4 w xfl9 m MMR QYIIR161mi OPa[ IAYRAFS .1i ]] 1 M NIIR4 R/SMI6 9wL H RMJIO:.R wIFIeNI lmf!- 3h%OA. %Q ima[£ fAR 0.II" XC IlWap Y4191d GLEE -s-I]" mMi�n106 U1161w 6a5NLCT SRmI w[ OMpL lM[enIFPtWL �NN¢zM wm �M fm'WAm[�Oa1 ]m3b, NEX 0.q PACKAGED GAS/ELECTRIC ROOFTOP UNIT SCHEDULE (RTU) - R-410A WMi.RJFW 14 [W SFW SOIO X MF M3 M6V PN [M[i 1&I iPNA 9MiM YX eL M m11P PJ W! 0.4 REw H 4PCM'-0X MC71YA qG 4V1O91 OERIWL M] FW LM Vlx WE XNk1 Y]m w Imft m. M1M ® MP IBI M ]EN R IBS NIY SFM OY ES➢. W @P Ip4 h1P IF1P M Nlq III YW 14. M q.R A M W]R mR rsmxE a Il.x - x Im m I X xa me LIm u >m n [i x Im I ul am n I ]e xm i u m] na w - i-e mY_x nYc rsReE a lu x Ixe m Imo m me ].Im an ]w n E m wi I ul am ] I ]a tm I u 3v] na w yStd 6Y wILVm R WLI46 6 m/HI 6y [. tlM/[EI M8, m RG i, wlpf Y SP IkIR my oAX fa] uYal mam e}1aX Lc]E cm msE]rs eew [ov m asp oae smlEnu DmEw Itu trni wv ae XLMA3 Wn. Mw wo ]u ,wwa v,gls v mX 4srYx Own m m nll¢ .. Xmvow m w PACKAGED TERMINAL AIR -CONDITIONER UNIT SCHEDULE YNWYARII MW RA 9X IFM Q4➢ maaa 1911 .awe 4RilM N] WR IAIR LRi Igl6 YM w YFF1 F NS Wlx R Im IOIM SPS QY ESV. 6Y NP6 Xw WF mW. wml la.t _ m Ho Iu t xm - E >ml Ial m f31F1 WYN TWISF 1 L9 Ilm iw ISe O3 ]W E TAI ]l] ]0 i �m�ii � onXmX w¢mansue Wmm.lw-wma Re mmms m,mwa m.l]w[c m. ® ELECTRIC HEATER SCHEDULE Y\VIF]mI1P 11H x]tile 3➢Rp 'AME WIS Y5 w-I w-x awN mwsw WYwI We]avx r emaEw aaE eM Im ero m-l-m m-I.m Imo lxv Le a ew. d-] MIv, B]Im1 WWE YR ISW YN m-I-W 141 If S w aY.« wlm-w ulr IEud a eM ]v m-I-eo aow Ile > L mNC LLLMm WYA9 9wl Mf MN ixw. f.LtlYl M-M. i-0R 1PUC m. iPP4U6'W Rm LLq WIPE m ]t Wfi ]t KKi XXl ImwNa IIXwlmrlr, mRXa I.A], w Ix aMi m1Xr. 1 iXwv em vR IlmxXn ra1wl]r. mmx aaxu*. w rYL uMmE WXTaS. ® GAS RADIANT HEATER SCHEDULE IRNX In mM]CEItR MV.IML I[AI[Ie IpCIX XYIM IVJP ILLR M EV. R. Y]m w 1[IXL W N+lf MEIVI M. M IB'a muWu c.mex amc] wlew m ae n SIWA:IILL @IIE6 fItlLY,E w M'P iRAWxfi SMR-pi w gl6T SF91 IAlp1 XWlgiw 51[6 KM......... � onwWlam m. rrexeER 1llX ry wame. oErerexsmmavaals nwlvwsE]smN ul�i4.!•�)•ti��s1•s!•���11•�R��P�1• m+pus)♦etl�s'1•�!•�'>•S!•��>•!i!•�i�l�Wu1 e�� V eeeeo� __�•—p mil• �� ___ ]Q^� nn.�e0e0 s'�f)sEfv".1f!•t�t.!•e.!•Sl�s;!•eQ�si1• 1J'� pCHflIS YHmmliNGES, M®11AMANN Jt\ENGWEEPoNG, INC./t\ YeW YalfawCNEN^we �d/REevEss�areaure " IlmRlewmXWevae[m.Xm MIm CCnmiwiw - fM[3mIY]�93mIBFw1[wl3mmw - ee^ws.ym,I i FCHA FOGT COLLINS REDTDIL PONDS PSH MILT CCLLINS HOUSING AUTHORITY 1115WEui1iWMm AVE m fO0.iCUl]LIS.CO.i09]1 pH011E91ae16ID10 iAYB]eiIINH SIlIDI TIVA ARCHITECT: STUDIO COW IMA ,,p S1PFET DENVERCDBNII xW6: ]ONR-015e fAF]ON1181'A IANDSLAPE IRLXNECi: AZUK GROUND M WX2IS faXfC[11NS,m®SL RIOIv:e]aertwn m6] NA 9aLD10H =MESL9TE20 [OWCOIIIX9,m N5L rlm�weaeeEx fMYIFIIXxII smucn]Nw KL&A NI FARIIX SiPEFT 10XFL.V0,m165O MWN:X]6M3C1 f]S•pBNI.31G] YECHAWCAL/P Mn MOUNTATNMRE auafaANUHXTS¢LT amX[]LLaoaAmew rx fm;Ase Mmlem=e9x lucmC - WAYNES ELECTRIC aL1mwav � PPra WNW PXm@]m+5 7m [AIC•]0]fl%8Ri IWD,TL'[NI118Bt 1.11i01 T' ct/11/IE DRLY.N SY: MA CP11/NUV OIECI6LBY: CPV ]uraovEoar: CPN ENEEIT3RE: HECHAVICIL SCH--DU=S M1.2 fig- FCHA FORT COLLINS REDTAIL PONDS PSH FORTCOLUNS HOUSING AUTHORITY 1TISMSTIMNT VAME fLMlcmlm9,mevn mora:vrNie.vTo iMR816nIA11 SRIDI TIVA ARCHITEcr: STUDIO COMILEWA mmm.srmET mxvm,mmin wmm::msMmalm fAtm1Ai91m LANDSCAPE MICHIIECT: AZURGROUND TroMM mam msoul PH0129m ffmll OVO: rvA wmST()vvI= tS roaran]mS,mmue rmYS:ammeme iAv:5f6}mEsm slNucnxu KMA 00137AM37I4:ET ernnma mmm Tnwe:nosvum fA ITH17M MEOiMwcu/ U"M MOUNTAINAIRE o�NMw�a uoe� wm�:mxmasm iucrosemaml EtccTraca: . WAYNES ELECTRIC umm�raww�emtu PNUtS: mT691lm1 fMlm]i4iVl! Pf481WY PTM&m NU1®FR CMWNEY: MPPRCVFDBY: 9RE rt E I.LIiCI:T' am/up Py CPII flR f2Cfl uEC�ICK %Mn M2.1 rCHRISTCPHEFHJEXGESAI�+�1B�Pv��iN3RA /iOR-ti FCHA FORT COLLINS REDTAIL PONDS PSN FORT COU.NS HOUSING AUTHORITY f115M3TYDYRAYAVEMIE foRlChwISC0.N51f PN0.@OM16P10 fALBl6IIldfil C=109)TIVA ANCHNECT: STUDIOCCMPEEUVA MMSTREEr DENVErt.WIOII RIvre:Nla w FAT:Ni Wl VNDSCME MCHITECi: AZURGROUND PDDmlifR FORTCCi1M9,MNmi PIm1aA PWIw v am - TVA vlma:anaaoovF FAIMNHiMi smucrvxM. IC&A NIEM MICIPEFI wreuo,camm Hv.:amNTam FYCf16N>3N] YEGIMACAL/PWYWNR MOUNTAIN AIRE aNsrwNAixmaET IEHY P1 : Mo PMDNE:NidQiRO PAI:]WdNd9il EIEDmM. WAYNES ELECTRIC Faawrt commf fl NH Pm Nut muNam NEVSM IawFnrNnmFx I,17/12 DRIP CPU/m1• DRU'NDy; CPN/CPR PR 440.QVFD BT. APPIto BI CPN S �A9Dt SFCONN F.CCfl IIEC{MICAL PNN M2.2 I C C C CE co C C C c, r, r, n n r.n r� rn rn rfn rta my ZMALna um Haste rats � ® Pd fII r A - vlm� - MECHANICAL KEYED NOTES m vura:mM ]IlMMaxsw MDMwmma ®W.VEIP M WLt IIW M1V IOIMIFP W9i M Wf QIF� ooM . Mn] vmum no Two r m rK Davc F . IF.6 M 1II 11W1 QE IIW. IV M M:P91 iM OJLf 9ffi _ m �PinaS MBP tvn nmia w1. rnu ma UI I -- P S 1P XT fD °A v v v vv eeCHHIST ,R MENGI GINEFAING, BfC. t/� wal�w /1E STUDIO CO.MPLEINA INC COPYRIGHT O'1 013 /try-1 FCHA FORT COLLINS REDTAIL PONDS PSN FORT COLLINS HOUSING AUTHCRHY ITISMMSTMWMTAVERDE PPmccuws.cD.emn P�na:Fam iM:SiBTi14BT1 STMI TIVA ArscxnEcr. smnloca++n�mn mMEN"Rm mml �4MM PM:.t MUZ IMI)SCME M WTECT: AZUR GROUND MWX210 HRrtmuxs,Lnmm Pnal�nwnal] am - WA m.rmLuxs,cneBvf Plol.:n.ansys EM:9i6LSM'O KMA WVUAIAMMV w-VVa]aM PAenPaCFuM MEOIM'IcXL/P"&m MOUNTAIN ARE uuaxMMSATxm¢:tT Dwre+,camAmlafu Prwa:Mwalw iAL W86t3in EfccmcAi WAYNES ELECTRIC flMwao caumrRDAPn F:1RrLpPTPx,mMu Pnmre:fwawaan FAaMasLan PEYSRtt giCIECIMD m 1S1PGI:l' DAM DIWN W. CPMIMVR O D!CRDBY: CPR MP0.pYEDBT. CPU BRELTI RE MRD F-COR MECi lch P I RBEETMMMR M2.3 1 f.9 3.1 d n i 8 9 10 12 13 y � T N N cm G G F FLIREI E E 0 G B A b J 38 1 ��)/� yCHgISTOPHEq MENGESp /FA /�/, j tENGMEERING INO./�\ T6G'�I- (//� ES/0 wwuwco,w,m.vW... NO, . ,r,e,f ......s..ue Nw ml� Pn Rte1�A}m 18� Sl S ILIDIO CONITLETIVA. INC (AITRK;H1 02013 o-- ww m Ras vv Im mcN vet vmwcv rws J -- - ro °w' uwr UNIT VNR UNR UNn UNIT S B�I qq q A p STAR - .i y aPEN Sfl-11NG y� UNIT I UNIT UNn UNIT 1 UNIT f UNIT AREA ` ® ® q ® A q A I vue I UNIT A © MECHANICAL KEYED NOTES O uvKnon vvw n/a'rwartp wNmw artvm � — ®Y PV /A DLt MY KR WA1fD YY9P MY WI Dlm6 -- — �a rl�s¢aewvsO'.w �vl�mv am G) •v � max amKs mvx xrvr nwza nu, nPT.a wv VI � U UNq A A 1 .ve. P 5' 1P iT Yl W FCHA FORT COLLINS e:lry REDTAIL PONDS PSN FCIiT cewNs Ht`1151NG AIfITiOgf1Y IIISWESTtlWMAWAYENIIE wRrcowxs,w.NMI Plml¢:erwlFDlo /— PAx:smd%al% STUD TIVA ARaVGECi: SEUOIO COA1PLCTNA ]%OIN1131REET pEMYER. CO W311 vxaa;lewnms fAt]O3AhYb LM'DSCAPE gRLXNECI; nzuRCRcuuu wsoRim PDRrmlims,calom PxDIaE:vnanwa A isDlnmvm swAREeurExoo PDMcroums,ta.eduf PMOiE:Ql6II5W93 f4116111ESd S1XUC111Rµ: KL.W 41 FA9IdIHRI1REi 1awpWweom PIYIEYrOEPF]VI PAR: %OEQ,M1 u[aANkALRwuarva MOUNTAIN AIR IS H116. NWAMRIHQRIFEi OFNL^cP fLWMW eGill PIP]ME']W-0R479e iM3W434pi1 EIECTPoCAI WA1NE5 ELECTRIC. if%M'MDCWNT'RDADn FDM LUPIDX.GIMQ% PRDr@:]%d6iN1 PAQim<uden REYSRYt PRD.¢CTN11A®ER 1.1•1i01:1' 0.iiE DPAWNBY: LPN/MNV DNECYIDDI: CPV ARRDYEDBY: CHI 6REEI}nLE: =OUi-i PSDfl MEf iMICN RNV 6MEETMINBFh M2.4 1.9 3.1 8 ]ol T 8 10 11 12 13 H H G G FHK F m[X4 fu. row FCHA FORT LOLLING REDTAIL PONDS PSH FORT COLLINS HOUSING AUTHORITY nlsxssxartrtwarNUE FONTCOWN9.w.8W11 vle]�:neaea]v iA%:PN]]1dx}1 �/QQ—M.x // rlvnl i STUDIO COMPLEPVA ]oafalmsrNQLr GEmEywimn rxwE: Wuna]n inY:]vunaen UNUSGYFKWRR: azur ground PoBQ%xtn FNn COLLB19,t6]OW vIWnE:naenaen Onu JVA zlanrowxswrassmlE:as Fovrcowne,w. Was vxanE:naxvWW fucvn.vxW] nvlNa]vu: KL&A xx1 EA3r11XSTNFEi Rmns:nsxar.xem FMevna®.uW Mfl:H1NIGL➢LIIMBINfi. MOUNTAIN AIRE xle]e.NwxQlxsrl¢sr Ggivm,w]auwemn FMnE:lW89.19W f0.l ]4]aNant FIFR¢IGL wAv11e's ELECTRIC 2101wu9wuxn9own Fa¢rLunon,wmml FIRM: W]assnn iu Wuswxn f1EVFIWF RtGlE4T NJAGER I\liGl:l' G¢Pe GQnv.Ner: cvu/uxx GHFCNw Bi: CPII MPROYEJBY: CPII 6NEEfnIIE esar L=w.L I+EC-IMICAI MN 6NEETWNBFA M2.5 B & B Balancing, Inc. Fan Unit PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: SYSTEM/UNIT: EF-04 AREA: Unit Data Fan Manufacturer Twin City Fan Fan Model Number T100 Fan Serial Number 41H12H Test Data Motor Volts 1 119 Volts Motor Amps 1 0.4 Amps Total CFM Design 155 CFM Total CFM Actual 117 CFM SP Out Actual in. we Fan RPM Design RPM j N Fan RPM Actual RPM ! SP In Actual in. we r Motor Amps 2 Amps Motor Amps 3 Amps' * Notes DATE: 2/22/2015 CONTACT: Larry Bartley Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 1.1 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. EF-04 18-Feb-15 ConnorAnley Verified back draft damper was free. Design flow not met, fan rated for 100 CFM. Bathroom still maintains negative pressure. SYSTEM/UNIT: EF-1-101 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 70 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Eric Bowhay Test Date: February 20, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-101 22-Feb-15 Eric Bowhay Direct Drive, no SSG B & B Balancing, Inc. Page I of66 Exhaust Fans ENUA GMTYPICN. 741RUNIT MEC VMICPL RANG ENLARGED TYPICAL MR UNIT MECNAN CPI. RAN O MAKEUP AIR DU CI WORK EIEVANONO w..Ea J jyCNRI3TOPHENMENGES ®C(�fiF�®�/`♦\ENGINEFAING, WG� A (/ Iwwxmc�n,x E..quo-R stoow smmodxwb.e�m..m FCHA PORT COLLINS REDTAIL PONDS PSH FORT COLUNS HOUSING AUTHORITY ntsYhRrx=fi"AEwIE FORT WI1MACe.EWt I+Imns::vmall:so ////' FAL1x0atEm1 SIlIDI TIVA STUDIO COMPLETIVA NMRDMIRDEET RENVEA,COWtI T E:a nMSI PRLaHR WIOEGYEA ,ON ci xr qround PDDCRRIR FWCOU24 ANSR Im VM74 en one JVA aaln>�cowl+ii�s, ca�i Pxm�:Ra.mmEs EACN4i]E69a snucruw KL&A v wm cam PIKRERm MIZI EA)DO 410 MECHANIGLRUMmNL: MOUNTAIN AIRE TMs.KAlAYA1HSIWEf RFNYHRCM1CPAW9Ma vwla:asamwm P.1LkHEDM1 EIECERIGL wAyne's ELECTRIC amwuREKMRITI=v POIR WPIRN.rmM N :mxnrat PALIaeEECOR PReIECENuIIDOt EXUMA- wtE DPAMN" CCAITt I= CPM/xNN m EGKI3I Y: CPN ARRCYFOBY: CPII mffETTnIE: BN RCED LECFAWCAL PW S AID E.EAAECNS M2.6 PROJECT: Red Tail Ponds PSH LOCATION: Ft. Collins, CO PROJECT #: DATE: 2/22/2015 CONTACT: Larry Bartley SYSTEM/UNIT: EF-1-102 AREA: Uhit 'Data, Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts MotorAmps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 66 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Connor Anley Test Date: February 18, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-102 22-Feb-15 Eric Bowhay Direct Drive, no SSG SYSTEM/UNIT: EF-1-103 AREA: Unit Data Fan Manufacturer Reverse O Matic Fan Model Number QB80BC Fan Serial Number Test Data Motor Volts 1 121 Volts Motor Amps 1 0.3 Amps Total CFM Design 50 CFM Total CFM Actual 66 CFM SP Out Actual in. we Fan RPM Design RPM Fan RPM Actual RPM SP In Actual in. we Motor Amps 2 Amps Motor Amps 3 Amps Tested By: Eric Bowhay Test Date: February 20, 2015 Motor Data Motor Rated Volts 120 Volts Motor FL Amps 0.35 Amps Motor Phase 1 Motor RPM RPM Motor HP HP Motor Manufacturer Motor Frame Motor Service Factor Sheave Data Motor Sheave Make Motor Sheave Model Fan Sheave Make Fan Sheave Model Number of Belts Belt Size in. Sheave Center Line in. * Notes EF-1-103 22-Feb-15 Eric Bowhay Direct Drive, no SSG B & B Balancing, Inc. Page 2 of 66 Exhaust Fans