Loading...
HomeMy WebLinkAbout5827 Big Canyon Dr - Disclosures/Blower Door Test - 12/23/2014BUILDING LEAKAGE TEST Date of Test: 12/23/2014 Customer: Ryand Homes Test File: 5827 Big Canyon Dr Multi Point Tectite Technician: Brad Smith - EnergyLogic Project Number: 34313 Building Address: 5827 Big Canyon Dr Fort Collins, CO 80528 Test Results 1. Airflow at 50 Pascals: 2197 CFM50 (+/- 4.7 %) (50 Pa = 0.2 w.c.) 2.90 ACH50 2. Leakage Area: 120.8 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 331.0 (+/- 88.4 %) Exponent (n) = 0.484 ( +/- 0.218 ) Correlation Coefficient = 0.91159 4. Test Settings: Test Standard: RES NET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 144.7 CFM 0.19 ACH 28.9 CFM per person 2. Estimated Design Infiltration Rate: Winter: 240.9 CFM Summer: 151.2 CFM 0.32ACH 0.20ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 85.7 CFM Base Rate: 85.7 CFM BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 12/23/2014 Test File: 5827 Big Canyon Dr Multi Point Tectite Building Information Location Climate Information Volume 45501 Surface Area 9707 Floor Area 4817 Height 30 # of Bedrooms 4 # of Occupants 5 Year of Construction 2014 Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 13013-7 6/17/2014 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 12/23/2014 Test File: 5827 Big Canyon Dr Multi Point Tectite Depressurization Test: Environmental Data Indoor Temperature (A°F) Outdoor Temperature (A°F) Altitude (ft) 67.0 36.0 1 5003.0 Data Points Nominal Baseline Adjusted Fan Building Pressure Building Pressure Pressure (Pa) (Pa) (Pa) Nominal Adjusted Flow Flow Fan (cfm) (cfm) % Error Configuration -10.4 n/a n/a -77.6 -72.2 32.7 2776 2693 2.6 Open -72.0 -66.6 30.4 2681 2600 3.1 Open -71.2 -65.8 27.1 2533 2456 -2.1 Open -66.0 -60.6 26.2 2492 2416 0.2 Open -60.6 -55.2 168.5 2315 2245 -2.5 Ring A -52.8 -47.4 170.4 2328 2258 5.4 Ring A -60.3 -54.9 153.4 2212 2145 -6.7 Ring A -48.6 -43.2 140.8 2121 2057 0.5 Ring A -0.4 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi -Point Test - Test Parameters None * n value outside of normally accepted limits. * correlation coefficient outside of normally accepted limits. * n value and/or correlation coefficient limits are not officially part of the RESNET Multi -Point Test Standard. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 12/23/2014 Test File: 5827 Big Canyon Dr Multi Point Tectite Comments Connection to: Garage: -47.3 Mechanicals: -50 Pa