Loading...
HomeMy WebLinkAbout3508 Rocky Stream Dr - Disclosures/Blower Door Test - 10/09/2014BUILDING LEAKAGE TEST Customer: Joinery Bldg Group Technician: Justin Heldenbrand Project Number: EnergyLogic (33741) Building Address: 3508 Rocky Stream Dr Fort Collins, CO 80528 Test Results 1. Airflow at 50 Pascals: 1122 CFM50 (+/- 2.7 %) (50 Pa = 0.2 w.c.) 1.28 ACH50 2. Leakage Area: 61.7 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 84.7 (+/ 58.8 %) Exponent (n) = 0.661 ( +/- 0.145 ) Correlation Coefficient = 0.97658 4. Test Settings: Test Standard: RESNET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 65.4 CFM 0.07 ACH 10.9 CFM per person 2. Estimated Design Infiltration Rate: Winter: 123.1 CFM Summer: 77.2 CFM 0.14 ACH 0.09 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 89.8 CFM Base Rate: 89.8 CFM Infiltration Credit: <0.0 CFM> BUILDING LEAKAGE TEST Pag2 o�f 4 Date of Test: 10/09/14 Test File: 3508 Rocky Stream Dr -Multi Point T t4 i e Building Information Volume 52575 Surface Area 10082 Floor Area 4485 Height 20 # of Bedrooms 5 # of Occupants 6 Year of Construction 2014 Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Location Climateinformation Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 275 6 03/20/08 BUILDING LEAKAGE TEST Page 3 of.4,, Date of Test: 10/09/14 Test File: 3508 Rocky Stream Dr -Multi Point Tectite a Depressurization Test: Environmental Data Indoor Temperature (OF) Outdoor Temperature (*F) Altitude (ft) 58.0 59.0 5003.0 Data Points Nominal Baseline Adjusted Fan Building Pressure Building Pressure Pressure (Pa) (Pa) (Pa) Nominal Adjusted Flow Flow Fan (cfm) (cfm) % Error Configuration -5.3 n/a n/a -73.5 -69.2 55.8 1351 1383 -0.6 Ring A -69.2 -64.9 54.0 1329 1360 2.0 Ring A -69.2 -64.9 49.9 1279 1309 -1.8 Ring A -61.9 -57.6 42.5 1183 1211 -1.7 Ring A -58.7 -54.4 41.7 1172 1199 1.0 Ring A -56.2 -51.8 41.3 1167 1194 3.9 Ring A -55.2 -50.9 36.5 1099 1124 -0.9 Ring A -49.9 -45.5 30.9 1012 1035 -1.8 Ring A -3.3 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi -Point Test - Test Parameters None * correlation coefficient outside of normally accepted limits. * n value and/or correlation coefficient limits are not officially part of the RESNET Multi -Point Test Standard. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 10/09/14 Test File: 3508 Rocky Stream Dr -Multi Point Tectite Comments Connection to: Mechanicals -50pa Garage -47.1 pa