HomeMy WebLinkAbout5021 Brookfield Dr - Disclosures/Blower Door Test - 09/05/2014 (8)Z Date of Test: 9/5/2014 Customer: Landmark Homes Windsor, CO 80550 Test Results 1. Airflow at 50 Pascals: (60 Pa = 0.2 w.c.) 2. Leakage Area: 3. Building Leakage Curve: BUILDING LEAKAGE TEST GS Services 2000 S. College Ave Fort Collins, Co 80525 Test File: Landmark Homes 5021 Brookfield Unit F -BD Technician: Paul Higman Project Number: Building Address: 5021 Brookfield Unit F Fort Collins, CO 80528 848 CFM50 (+/- 1.2 %) 3.48 ACH50 46.6 in2 LBL ELA @ 4 Pa Flow Coefficient (C) = 28.3 (+/- 9.1 %) Exponent (n) = 0.869 ( +/- 0.025 ) Correlation Coefficient = 0.99947 4. Test Settings: Test Standard: RESNET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 40.2 CFM 0.16 ACH 2. Estimated Design Infiltration Rate: Winter: 56.8 CFM Summer: 41.7 CFM 0.23 ACH 0.17 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: A' 'v -`5 GS'SerAces BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 9/5/2014 Test File: Landmark Homes 5021 Brookfield Unit F -BD Building Information Volume 14607 Surface Area Floor Area 1623 Height 10 # of Bedrooms 2 # of Occupants Year of Construction 2014 Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 GS Ses BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 9/5/2014 Test File: Landmark Homes 5021 Brookfield Unit F -BD Depressurization Test: Environmental Data Indoor Temperature (A°F) Outdoor Temperature (A°F) Altitude (ft) 72.0 84.0 5000.0 Data Points - Data Entered Manually Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration -1.5 n/a n/a -60.1 -58.8 222.9 -55.1 -53.8 188.2 -50.2 -48.9 158.2 -45.1 -43.8 132.8 -40.3 -39.0 103.7 -35.0 -33.7 82.7 -29.4 -28.1 409.2 -25.4 -24.1 297.0 -19.8 -18.5 201.1 -1.1 n/a n/a Time Averaging Period: 10 None 884 983 0.7 Ring B 813 904 0.0 Ring B 746 829 -0.3 Ring B 684 760 0.6 Ring B 605 672 -1.5 Ring B 541 601 -0.0 Ring B 468 520 1.3 Ring C 397 441 -1.9 Ring C 325 361 1.1 Ring C Deviations from Standard RESNET Multi -Point Test - Test Parameters GS BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 9/5/2014 Test File: Landmark Homes 5021 Brookfield Unit F -BD Comments House WRT Gargae = -47.1 pa