Loading...
HomeMy WebLinkAbout2221 Milton Ln - Disclosures/Mechanical - 06/26/2014City of Fort Collins Residential Mechanical Systems Performance Report This form i a record of testing targets and results, with Pass/Fail outcomes. For information on measurement tools and testing techniques, see the "Residenti I New Construction Mechanical Systems Testing Guide." The guide and this form may be periodically updated; check the Building Services wgb site for the current version. This for �nS must be completed and signed by an "Approved Agency," and submitted to Building Services as a requirement for receiving a C.O. Color key Measured value :forget; to compare w th Pass Fm(; Cautwre Other t 1mrt„ targetorlimit. data �_ ,` ADCF = Air Density Correction Factor, based on tool, ADCF altitude (5000% air temperature through tool Volumetric flow (CFM 5000) = ADCF x Indicated flow (CFM) P�ddress A ) Date of "Residential Mechanical Systems 'Builder J �. y{, Design Submittal" +'C information referenced HVAC contractor i! by testing technicians As-bu It changes vs mech deign submittal Testing dal (s) to _lzl -017 SAW Bath exhaust Testing tech (initials) Flo bw box _ Pitot tube duct traverse Air terr ADCF % too Passive flow hood — Other (note below) through tool (F)L�—� Measured Airflow Design (II Exhaust PickupMinimum Airflow Requirement Indicated Volumetric � Location Airflow (CFM (CFM 5000') Flow Flow I Pass Fail Snnmt + Type of Operation (CFM) (CFM 5000') _ So Intermittent; ' 20 Gontirfudus , ElL g,+ —50lntermittent ._20Commuousm a ❑' Dit Y 50,fntermrttent_20Continuous ❑ 30 Intermittent '_ 20 Continuous _ ❑ [" 50:Interm!ttent, T 20 Continuous' ❑ , �;°„ Testing notes Kitchen xhaust WA - hood does not vent to outside ®— Testing tech (initials)= Oven all -Gas 5EEctncl Minimum airflow requirement (CFM 5000) + operation -I_ 100 Intermittent ._ 25 Continuous :.'Measured airflow '= Flow tool --1 —* Flow box Passive flow hood Powered flow hood — Pitot tube traverse Flow nd — g Tool location —Interior grille — Exhaust duct Air temp through ADCF —Other (note below) (Ex a or terrine on not OK) tool (� Indicat i flow CFM Volumetric flow CFM 5000' ❑ Pass Fail => Testing,, notes Residential Mechanical Design Submittal V20140101 Page 1 Systems, other than substructural floor exhaust Testing tech (initials) 's Cod e- Design ventilation CFM •• inimum ventilation airflow s✓J CFM 5000' CFM 5000 ased on CFA and # of BR) 7 7� airflow austonly System —Supply-only Target l ��++ ventilation airflow range .._ t0, LL tO 3'• �i''' .r' CFM 5000' Typo —Balanced ' (code -minimum]; (120vo of dEsign 9awg:. • Measured Airflow AlrTemp Indicated Volumetric Measurement Method Tool Location Through ADCF Flow Flow I Pass Fail Tool (F) (CFM) (CFM 5000') Total N/A Passive -flow hood -#�? exhaust airflov1 _1:f FJow box _ Pitot tube traverse collar Other —Flow _ (note below) Total VV — N/A — Passive flow hood r, supply — Flow box _ Pilot tube traverse ❑ ❑ -� airflo���v,,,Y117117 — Flow collar _ Other (note below) When supply airflow is circulated by air handler fan, fan speed for measurement Heating Cooling Continuous fan d!Balan d airflow in balanced systems Average supply of measured CFM +exhaust flowsC�5000, Target flow range - rt .;: ' tO CFM El Pass Fail (average +/-15%) • ::r 5000' testingl note Substructural floor exhaust _V""—no sub -structural floor exhaust system Testing tech (initials) ° '• Desig exhaust airflow (based on�CFM 500D' Target airflow limits a� -i ' approved design) (design }/-15%)°> to �;:, CFM 5000 , "- •.;Measu d airflow Flow tool -� Flowbox Pilot tube traverse Tool Air temp Passive flowhood _ _Flow collar location through(�❑ ADCF Powered flow hood _ Other (note below) tool Indiq d flow CFM Volumetric flow CFM 5000' ❑ Pass Fail Testis note; i� "5' @:° Q � e 5r � � � • � 0 �,Ayk�� 4 � �'"4 s�ni�ak�,��y.,,d49i'� :�""��' �'a{'a �4�� % �j�r�'Y � E p^ � A�;```� *�We'� '' �'f ductwork ' �"fa-twork outside conditioned space Testing notes (ind muWpte sys) - Duct leaage — Testing tech (initials): - data sot rce Energy rater (name, —: company, testing date): House nncludf efloor area include full basement) sf Air temp through tool (F) ADCF Maximum Allowed Duct Leakage Measured Duct Leakage Test Parameter and Conditions Normalized Absolute (CFM25 5000' / 100 so (CFM25 5000) Indicated Volumetric (CFM25 (CFM25 5000') System #'I Passl Fail System #2 I Passl Fail Leakage ('ype I Timing Air Handler Total leafage Rough -in Excluded 4 , "'. El Total lea age Rough -in Included 6 �• ❑ ,�-_ ❑ Total leaf age Complete Included 12 +; ❑ ❑^" 11 'r❑ ,� ea ge outdot Complete Included $. "• - Residential leechanical Design Submittal V20140101 Page 2 . For multiple systems, attach one page per system System I #1�1 Which parts of house does it serve? Installed equipment (Be clear about which AC components are installed at time of testing) Testing tech Cinitials) II Furnace or Boller AC or Heat Pump Condenser AC or Heat Pump Coll Manufacturer I ps F Ilk t r basic pleated Other. Thickness r/ MERV High-effic pleated (oplional) Basic fiberglass Electrostatic Fill ri bran� Type I ❑ Static pressures Testing tech (initials) Setup ... Speed: [ocaban Heating Cooling Cont. fan SP4 for NSOP, TF,911P) Higl -stage for multi -stage equipment Blower ;peed tap: AP Coil Humidifier damper. N/A (SP3,SN) Open (Heating) Closed (Cooling) Allegis t SP3 Zo�ers open TX, �VIA a dampers open ZI spi 1:M W AP Total ESP AP Filter , (SP I'T4 1 ,2),7 (SPI - SF 1 9 SP2 Cooling: Des!! Measure Flow plate Mee adju! Testin( note; Heating: Man OEM: Measured air flow through indoor coil no AC installed Testing tech (iniffals) i cooling airflorw (high stage) Target airflowlimits CFM 50OU .. . : CFM 5000' ...... I airflow rid [:� Air lemp[❑ ize through tool (F) ADCF NSOP[❑ TFSop[ Flow Resistance Correction Factor ured airflow, no rnent/correction=CFM Indicated alrflow CFM Measured Volumetric airflow, CFM El Pass JCF, AF x FRCF Indicated AFxADCF 5000, Fell ; manifold pressure (high stage) pressure IWC Target manifold P @,5000- limits (spec +/- 5%) I -,to -17 , E� I Heating: temperature rise OEM temperature rise limits (high stage)� F Measured temps (F)- Supply airF/;z Return air[K] Testing tech (initials) IWC Measured bfFass pressure IWC UFal iz= Testing tech (initials) TempCaution, within 1 OF ri[7F Pass' Fai se 6l r low of top of range Residential Mechanical Design Submittzil V20140101 Page 3 Testing approach and targets Testing tech (initials) ;�,�❑N/A:I No complete AC system $tt"ouse completed November-April(installing contractorresponsiblefortestinginwaan weather) _::; ❑ TXV: Subcooling + SH check ❑Non-TXV: Superheat ❑ OEM -specific: Approach ❑ Other OEM -specific (documentation required) z sue,. Temperatures Condenser Non-TXV: Return Target , Target �r Target g `: (F}: entering air temp airwet-bulb temp superheat- r'(- subcooling , approach Dischr a Condenser Liquid Actual ❑ TXV Pass: Actual SC within +/- pressure❑ saturation T❑F line ❑F subcooling❑F 3 F of target SC,:2 F min (ioSl) (5000'chart) temp (CandT-fici r) TXV FalI Suction Evaporator Suction Actual ❑ Non-TXV Pass: Actual SH ' pre0 , saturation T F line F superheat F Wthin +/- 5 F of target SH ( SI) (5000'chart) ❑ temp❑ (sus liar-evap r) Non-TXV Fail TXV ecks: Pass: Field -installed TXV installed in accordance with OEM instructions Caution: Actual SH outside mfgr range Approach Liquids line F Actual approach F ���1❑tt Approach Pass: Actual approach Wthin +/- 1 F of target approach line (Llq line T-condenser EAT) Approach Fail Register air flows Allegisters are cut through finish materials and moving air 912ass b t'❑ Fail (Remainder of register air flow section, under development, not yet being enforced) Pressur balance Testing tech (initials Testing tech (initials) Room Room -to -Core Measured (match names on plans, include Pressure Drop Pressure Pass Fail basement if there is a door) Target Range (Pa) Drop (Pa) to r� 73 to +3;' -&to+3 ❑ Q l j , 3'to:+3� • ❑ ❑ -3 to +3 ❑ ❑�^ x F3 to>+3 ❑ ❑ § -3'to +3 ❑ r❑'F Residential P'Aechanical Design Submittal V20140101 Page 4 n safety testing NIA — no natural -draft combustion appliances Types table must be completed for every home) types Testing tech. (initials). Fumacq Appliance #1 Combustion T pe NIA ❑ Draft -hood Natural -draft ❑ Induced -draft Natural -draft ❑ Power- vent ❑ Direct- vent ❑ Powered sealed - combustion Electric ❑ Fumac #2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Boiler r1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Boiler #2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Water l eater #1 ❑ ❑ ❑ ❑ ❑ ❑ Water f eater #2 El El❑ ❑ El El El #1 ❑ ❑ ❑ ❑ ❑ ❑ ElFreplace#2 ❑ ❑ ❑ ❑ El❑ ❑ Other. ( ❑ El ❑ ❑ ❑ ❑ ❑ 4` .,House Ou CAZ pi BPI Mee OK ., BPI i `'z Mea: -s" Pass Draft pi BPI Mee! Pass +CO con BPI Meae Pass Cautl Tesflnc note: depressurization performance #of bath fans on Vented range hood on Clothes dryer on Air handler on fans on: temperature = F limit (Pa wrt outside) 'ed net CAZ depressurization (Pa wrtoutside) ,s negative) I Caution (more negative) ximum limit (seconds ad spillage duration (seconds duration not exceeding limit E] JOK :,.❑- Caution JOK .1 Caution .-❑ JOK []^11 Caution 6 A: ❑ Pass ,'❑ Fail ❑ Pass jQ 1 Fall ElPass a Fail It (Pa wrt CAZ) 'ad (Pa wrt CAZ) pressure more negative than limit Oration in undiluted flue gas ximum limit (ppm) ad CO (ppm) CO level not exceeding limit = CO level 25 to 100 ppm IPass � Fail _ ❑ Pass I�� Fail E] 1pass [--�Qtj Fail 'r : 100 100 10Q ❑ +n Pass i ❑'„ Fail El Pass ❑ Fail El. Pass '.❑",` Caution ❑�; Caution r ❑.; Caution Residential t echanical Design Submittal V20140101 Page 5 hniciari #1 performing inspection and testing documented on this report (Approved Agency) certify That the tests referenced above, in sections bearing my initials, were performed in accordance with protocols specified by the ;ity ofort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge, Name (print Title Compam ure and Dab sOr.V `Ft`c :hnicla #2 performing inspection and testing documented on this report (Approved Agency) I certify Ihat the tests referenced above, in sections bearing my initials, were performed in accordance with protocols specified by the City of rt Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. Na HVAC Contra is certi I tat 'N fY 7m systems Name (print cs... Titb Compan) tr }, Signs t re and Date t: ctor (City oPFart Collins license holder) I have reviewed this report and that the test results are an accurate representation of the performance of the installed mechanical Dwayne Shawver Owner IMS Heating & Air, Inc. Digitally signed ., n.. Sh �/��`,p` ;Shawver 1 1 V V V G Date: �'-- `2014:06;26 r r, 17 1 13:25:16-06'00' Residential Mechanical Design Submittal V20140101 Page 6