Loading...
HomeMy WebLinkAbout430 N College Ave - Special Inspections/Field Verification - 01/31/2014 (2)Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 — Eaton, CO 80615 ® Phone (970) 454-5351— Fax (970) 454-5391 2389 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 1/31/14 PROJECT Colorado State University Engines & Energy Conservation Laboratory 430 N. College Avenue Ft. Collins, CO ARCHITECT Neenan Archistruction 2607 Midpointe Drive Ft. Collins, CO ENGINEER AE Associates, Inc. 5587 W. 18th Street Greeley, CO CONTRACTOR Air Comfort, Inc. Lind's Plumbing & Heating, Inc. 150 Rome Court 1414 Blue Spruce Drive, Unit A Ft. Collins, CO Ft. Collins, CO r Lawrence H. Finn & Associates,Inc. B 2s89 Air Handling Unit PROJECT: CSIJ Engines & Energy Conversion Laboratory LOCATION: Fort Collins, CO SYSTEM/UNIT: AHU-01 / V2-02 AREA: Uriit Data Manufacturer Titus Model Number DESV VAV Address 53 Box Inlet Size 5 In. K Factor -1 1.495 * Notes SYSTEM/UNIT: AHU-01 / V2-03 AREA: Unit Data _ - Manufacturer Titus Model Number DESV VAV Address 54 Box Inlet Size 6 In. K Factor -1 2.054 * Notes DATE: 1 /31/2014 CONTACT: Emerson Moore Tested By: Keith Finn Test Date: January 22, 2014 Term Bok Test Data Max Des. CFM 300 CFM Max Act. CFM 303 CFM Min Des. CFM 255 CFM Min Act. CFM 255 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 410 CFM Max Act. CFM 412 CFM Min Des. CFM 350 CFM Min Act. CFM 350 CFM SYSTEM/UNIT: AHU-01 / V2-04 Tested By: Keith Finn AREA: Test Date: January 22, 2014 Unit Data'. Manufacturer Titusa Model Number DESV VAV Address ' 56 Box Inlet Size 5 In. K Factor-1 1.379 * Notes Term Box.Tesf Data Max Des. CFM 226 CFM Max Act. CFM 219 CFM Min Des. CFM. 195 CFM Min Act. CFM 197 CFM SYSTEM/UNIT: AHU-01 /V2-05 Tested By: Keith Finn AREA: Test Date: January 22, 2014 Unit Data Manufacturer Titus Model Number DESV VAV Address 56 Box Inlet Size 4 In. K Factor -1 1.587 * Notes Term Box Test'Data Max Des. CFM 120 CFM Max Act. CFM 123 CFM . Min Des. CFM 120 CFM Min Act. CFM 123 CFM L.H. Finn and Associates Panes A of 79 Lawrence H. Finn Associates, Inc. P1� `9 if k 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory LOCATION: Fort Collins, CO SYSTEM/UNIT: AHU-01 / V2-06 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 57 Box Inlet Size 5 In. K Factor -1 1.500 * Notes SYSTEM/UNIT: AHU-01 / V2-07 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 58 Box Inlet Size 5 In. K Factor -1 1.866 * Notes SYSTEM/UNIT: AHU-01 / 1/2-08 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 59 Box Inlet Size 4 In. K Factor -1 1.172 * Notes SYSTEM/UNIT: AHU-01 / V3-01 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 31 Box Inlet Size 5 In. K Factor -1 1.557 * Notes DATE: 1 /31 /2014 CONTACT: Emerson Moore Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 300 CFM Max Act. CFM 295 CFM Min Des. CFM 255 CFM Min Act. CFM 246 CFM Tested By: Emerson Moore Test Date: January 23, 2014 Term Box Test Data Max Des. CFM' 300 CFM Max Act. CFM 303 CFM Min Des. CFM 255 CFM Min Act. CFM 255 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 120 CFM Max Act. CFM 123 CFM Min Des. CFM 120 CFM Min Act. CFM 123 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 225 CFM Max Act. CFM 224 CFM Min Des. CFM 195 CFM Min Act. CFM 206 CFM L.H. Finn and Associates Panes in of 79 t""'r Lawrence H. Finn & Associates, Inc. NAEs 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014 LOCATION: Fort Collins, CO CONTACT: Emerson Moore SYSTEM/UNIT: AHU-01 / V3-02 AREA: Unit. Data Manufacturer Titus Model Number DESV VAV Address 32 Box Inlet Size 5 In. K Factor-1 1.504 * Notes SYSTEM/UNIT: AHU-01 / V3-03 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 33 Box Inlet Size 5 In. K Factor -1 1.496 * Notes SYSTEM/UNIT: AHU-01 /V3-04 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 34 Box Inlet Size 4 In. K Factor -1 1.078 * Notes SYSTEM/UNIT: AHU-01 /V3-05 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 35 Box Inlet Size 4 In. K Factor-1 1.066 Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 300 CFM Max Act. CFM 289 CFM Min Des. CFM 255 CFM Min Act. CFM 258 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 300 CFM Max Act. CFM 303 CFM Min Des. CFM 255 CFM Min Act. CFM 257 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 200 CFM Max Act. CFM 195 CFM Min Des. CFM 170 CFM Min Act. CFM 174 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 200 CFM Max Act. CFM 198 CFM Min Des. CFM 170 CFM Min Act. CFM 174 CFM * Notes L. H. Finn and Associates Panes 1 1 of 79 Lawrence H. Finn & Associates, Inc. N E 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014 LOCATION: Fort Collins, CO CONTACT: Emerson Moore SYSTEM/UNIT: AHU-01 / V3-06 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 36 Box Inlet Size 5 In. K Factor -1 1.496 * Notes SYSTEM/UNIT: AHU-01 / V3-07 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 37 Box Inlet Size 5 In. K Factor-1 1.501 * Notes SYSTEM/UNIT: AHU-01 /V4-01 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 38 Box Inlet Size 4 In. K Factor -1 1.037 * Notes SYSTEM/UNIT: AHU-01 / V4-02 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 39 Box Inlet Size 5 In. K Factor -1 1.887 * Notes Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 270 CFM Max Act. CFM 271 CFM Min Des. CFM 270 CFM Min Act. CFM 271 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 300 CFM Max Act. CFM 294 CFM Min Des. CFM 255 CFM Min Act. CFM 252 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 150 CFM Max Act. CFM 148 CFM Min Des. CFM 130 CFM Min Act. CFM 133 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 300 CFM Max Act. CFM 298 CFM Min Des. CFM 255 CFM Min Act. CFM 259 CFM L.H. Finn and Associates =:__, �--- Panes 19 of 79 r Lawrence H. Finn & Associates, Inc. P.! 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014 LOCATION: Fort Collins, CO CONTACT: Emerson Moore SYSTEM/UNIT: AHU-01 / V4-03 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 40 Box Inlet Size 5 In. K Factor -1 1.490 * Notes SYSTEM/UNIT: AHU-01 / V4-04 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 41 Box Inlet Size 4 In. K Factor -1 1.413 * Notes SYSTEM/UNIT: AHU-01 / V4-05 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 42 Box Inlet Size 4 In. K Factor-1 1.83 * Notes Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 300 CFM Max Act. CFM 300 CFM Min Des. CFM 255 CFM Min Act. CFM 248 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 150 CFM Max Act. CFM 151 CFM Min Des. CFM 130 CFM Min Act. CFM 129 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test Data Max Des. CFM 150 CFM Max Act. CFM 147 CFM Min Des. CFM 130 CFM Min Act. CFM 132 CFM L.H. Finn and Associates =:...., �--- Panes 1 � of 79 9 .wM } Lawrence H. Finn & Associates, Inc. N , e � 2389 Fan Unit PROJECT: CSU Engines & Energy Conversion Laboratory LOCATION: Fort Collins, CO SYSTEM/UNIT: EF-03 AREA: Roof Unit Data Fan Manufacturer Twin City Fan Fan Model Number BCRD-160D Fan Serial Number G13-000000095270 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Downblast Starter Data Installed Thermal Internal Test Data Total CFM Design 1885 CFM Total CFM Actual 1889 CFM Fan RPM Actual 1176 RPM Motor Volts 1 210 Volts Motor Amps 1 3.8 Amps SP In Actual -0.46 in. we SP Out Actual 0.0 in. we Total SP Actual 0.46 in. we EF-03 Exhaust Inlet Summary DATE: 1 /31 /2014 CONTACT: Emerson Moore Tested By: Emerson Moore Test Date: January 30, 2014 Motor Data Motor Manufacturer SMC Motor Frame 56C Motor HP 1/2 HP Motor RPM 1750 RPM Motor Rated Volts 115/208-230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 8.2/4.1 Amps Motor Service Factor 1.15 Nominal Efficiency 61 % Power Factor 65 Sheave Data Motor Sheave Make Browning Motor Sheave Model Adjustable Motor Sheave Diam. 3 3/4 in. Motor Operating Diameter 3 112 Motor Sheave Bore 5/8 in. Fan Sheave Make Browning Fan Sheave Model AK 54 Fan Sheave Diam. 5 1/4 in. Fan Sheave Bore 3/4 in. Number of Belts 1 Belt Size 4L 280 in. Sheave Center Line 5 1/4 in. System f Unit Area Served Outlet Type Size LxW ! D AK Factor Maximum Design Prelim Reading Maximum%a Final Prelim Deviation % Final Deviation Inlet -A Crawl Space ER 435 425 423 98 97 Inlet-B 121 E 12x12 300 242 311 81 104 Inlet-C 122 E 12x12 300 246 305 82 102 Inlet-D 114 E 6x6 75 62 73 83 97 Inlet-E See Print E 8x8 110 117 109 106 99 Inlet-F 117 E 6x6 50 59 49 118 98 Inlet-G 116 E 6x6 50 58 52 116 104 Inlet-H 112 E 6x6 115 0 116 0 101 Inlet -I 232 E 10x10 225 350 222 156 99 Inlet-J See Print E 10x10 225 350 229 156 102 Totals: - - - 1,885 1,909 1,889 101 % 100 % * Notes L.H. Finn and Associates Panes 17 of 79 Lawrence H. Finn & Associates, Inc. NE{ 2389 Fan Unit PROJECT: CSU Engines & Energy Conversion Laboratory LOCATION: Fort Collins, CO SYSTEM/UNIT: EF-04 AREA: 322 Unit Data Fan Manufacturer Twin City Fan Fan Model Number T400L Fan Type Forward Curve Fan Size 6" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 300 CFM Total CFM Actual 287 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 121 Volts Motor Amps 1 1.1 Amps SP In Actual -0.09 in. we SP Out Actual 0.21 in. we Total SP Actual 0.30 in. we EF-04 Exhaust Inlet Summary DATE: 1 /31 /2014 CONTACT: Emerson Moore Tested By: Joe Castanon Test Date: January 24, 2014 Motor Data Motor Manufacturer Broan Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.4 Amps Sheave Data Motor Sheave Make Direct Drive System /Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet -A 321 E 8x8 150 151 144 101 96 Inlet-13 322 E 8x8 150 130 143 87 95 Totals : 300 281 287 94 % 96 % * Notes I EF-04 24-Jan-14 Joe Castanon Unit contains 1 motor and 2 blowers. L.H. Finn and Associates Pane 1 R of 79 r' Lawrence H. Finn & Associates, Inc. !�� �' 2389 Fan Unit PROJECT: CSU Engines & Energy Conversion Laboratory LOCATION: Fort Collins, CO SYSTEM/UNIT: EF-05 AREA: 401 Unit Data Fan Manufacturer Twin City Fan Fan Model Number T500L Fan Type Forward Curve Fan Size 6" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 500 CFM Total CFM Actual 477 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 122 Volts Motor Amps 1 1.8 Amps SP In Actual -0.09 in. we SP Out Actual 0.25 in. we Total SP Design 0.50 in. we Total SP Actual 0.34 in. we EF-05 Exhaust Inlet Summary DATE: 1 /31 /2014 CONTACT: Emerson Moore Tested By: Joe Castanon Test Date: January 24, 2014 Motor Data Motor Manufacturer Broan Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 2.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet -A 402 E 8x8 150 146 146 97 97 Inlet-B 401 E 8x8 150 142 142 95 95 Inlet-C Under Floor 200 189 189 95 95 Totals : - - 500 477 477 95 % 95 % * Notes EF-05 24-Jan-14 Joe Castanon Inlet-C for future connection. Balanced to design of 200 CFM as per note on page M1.24A. EF-05 24-Jan-14 Joe Castanon Unit contains 1 motor and 2 blowers. L.H. Finn and Associates _. Panes I of 79 PRESSURIZATION TEST DATA SUMMARY PROJECT INFORMATION Normalized Leakage Rate (cfm/ft2 @75Pa) 0.1713 Test Date January 11, 2014 Normalized Leakage Rate _low (cfm/ft2 @75Pa) 0.1693 Client Neenan Normalized Leakage Rate_high (cfm/ft2 @75Pa) 0.1733 Project CSU - EECL PIE Project # C0111586.00 Envelope Area (W) 82,648 Location Fort Collins, CO Equivalent Leakage Area, EgLA (ft2) @ 0.3 1nWG 10.8 Fan # 14,15,16 DATA ANALYSIS PRECISION & BIAS ENVIRONMENTAL VALUES nP U.b334 Avg n - x 3.9b9b Density_in Ln C 6.8872 Avg (Ingo) - y 9.4015 Density_out (lb/ft3) 0.0665 C 979.7 S2x 0.0493 Density ref (lb/ft3) 0.0752 CP 919.1 Sx 0.2219 Dyn. Viscosity, u, press (lb/ft/h) 0.0434 P_ref (Pa) 75 S2y 0.0200 Dyn. Viscosity, u, depress (lb/ft/h) 0.0420 AI_Pref (inWg) 0.3 Sy 0.1413 Dyn. Viscosity, u_o, ref (lb/ft/h) 0.0439 Q @ 75Pa 14157.2 Sxy 0.0312 Temp out (OF) 38.0 Q@4Pa 2211.5 np 0.6334 -initial Temp out _final (OF) 39.0 InC 6.8872 Temp out_avg (OF) 38.5 95% Confidence Limits C 979.67 Temp in -initial (OF) 61.0 Qo @ 75Pa_low 13995.2 Sn 0.0135 Temp in -final (OF) 61.0 Qo @ 75Pa_high 14321.2 S_InC 0.0538 Temp in_avg (OF) 61.0 Confidence Interval 0.0020 T(95%,N) 2.0739 Temp ref (OF) 68.0 1_I11C 0.1116 Elevation (ft) 4,982 Avg. Baseline Pressures (Pa): I_n 0.0281 Elevation _ref (ft) 0 Station X 3.38 Pa (x) 75 Wind Speed (mph) 0 Sy(x) 0.0056 Wind Direction n/a FAN STATION DESCRIPTION ly(x) U.U115 Station Number # of fans INTERIOR AP CHECK (Pa) - EXTERIOR/INTERIOR CONTROL STATION 1 3 Pressure Tap AP (aD 50 Pa CS - 4th East 0.4 EXTERIOR TAP LOCATION C3 - 3rd Last 0.2 #1 West Elevation CS - 2nd East 0.1 CS - 1st East 0.1 4th East - 1 st East 0.0 Pie Consulting & Engineering Page 1 of 8 PRESSURIZATION TEST DATA idex P tar et MEASURED P (Pal PLOT VALUES Q CFM P corr LN(PLOT Q corr Ln P corr 14534 4.27 VALUES) Ln Q corr BASELINE 1 80 74.9 4265 71.5 9.58 3.8 2 80 74.9 4260 71.5 14517 4.27 9.58 3.9 3 80 74.8 4260 71.4 14517 4.27 9.58 3.9 4 75 69.8 4110 66.4 14006 4.20 9.55 4.0 5 75 69.8 4115 66.4 14023 4.20 9.55 4.0 6 75 69.8 4115 66.4 14023 4.20 9.55 3.9 to b5.0 397U 61.b 13529 4.12 9.51 3.6 8 70 65.1 3970 61.7 13529 4.12 9.51 3.4 9 70 65.1 3970 61.7 13529 4.12 9.51 3.3 10 65 60.0 3745 56.6 12762 4.04 9.45 3.6 11 65 60.1 3745 56.7 12762 4.04 9.45 3.9 12 65 60.0 3745 56.6 12762 4.04 9.45 3.7 13 60 55.5 3500 52.1 11927 3.95 9.39 3.1 14 60 55.4 3500 52.0 11927 3.95 9.39 3.3 15 60 55.4 3495 52.0 11910 3.95 9.39 3.3 16 55 50.4 3230 47.0 11007 3.85 9.31 3.1 17 55 50.4 3230 47.0 11007 3.85 9.31 2.8 18 55 50.4 3235 47.0 11024 3.85 9.31 2.8 19 .50 45.0 3000 41.6 10223 3.73 9.23 2.8 20 50 45.1 3000 41.7 10223 3.73 9.23 3.0 21 50 45.1 3000 41.7 10223 3.73 9.23 3.0 22 45 40.0 2870 36.6 9780 3.60 9.19 3.0 23 45 40.0 2870 36.6 9780 3.60 9.19 3.0 24 45 39.9 2870 36.5 9780 3.60 9.19 3.0 Pie Consulting & Engineering Page 2 of 8 9.65 9.60 9.55 9.50 9.45 LL U 9.40 ry 0 9.35 U- c 9.30 9.25 9.20 9.15 9.10 3.50 PRESSURIZATION DATA y = 0.6334x + 6.8872 R2 = 0.9901 n 3.60 3.70 3.80 3.90 4.00 Ln Pressure (Pa) Page 3 of 8 E 4.10 4.20 4.30 4.40 Lawrence H. Finn & Associates, Inc. 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory LOCATION: Fort Collins, CO SYSTEM/UNIT: AHU-01 AREA: Unit Data Unit Manufacturer Annex Air Unit Model Number MAU-E-07-D-D-H-WMP24 Unit Serial Number 2092-01-0813 AHU-01 / Supply Fan Fan Type Air Foil Fan Size 29" OD Fan Class 1 Fan Arrangement SWSI Fan Discharge Plenum AHU-01 / SF Final Filter Bank Filter Manufacturer AAF Filter Type Bag Filter Quantity 3/3 Filter Size 12x24xl2/24x24xl2 AHU-01 / SF Pre -Filter Bank Filter Manufacturer AAF Filter Type Pleated Filter Quantity 3/3 Filter Size 12x24x2/24x24x2 Starter Data AHU-01 / Supply Fan Installed Thermal VFD Test Data Total CFM Design 8977 CFM Total CFM Actual 9651 CFM OA CFM Design 8977 CFM OA CFM Actual 9651 CFM RA CFM Design 0 CFM RA CFM Actual 0 CFM AHU-01 / Supply Fan Fan RPM Actual 1731 RPM Motor Volts 1 448 Volts Motor Volts 2 448 Volts Motor Volts 3 448 Volts Motor Amps 1 12.5 Amps Motor Amps 2 12.5 Amps Motor Amps 3 12.5 Amps VFD Speed 58.4 HZ * Notes DATE: 1 /31 /2014 CONTACT: Emerson Moore Tested By: Emerson Moore Test Date: January 30, 2014 Motor Data AHU-01 / Supply Fan Motor Manufacturer Baldor Motor Frame 254T Motor HP 15 HP Motor RPM 1765 RPM Motor Rated Volts 208-2301460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 37.4-35.4117.7 Amps Motor Service Factor 1.15 Nominal Efficiency 93 % Power Factor 86 Sheave Data AHU-01 / Supply Fan Motor Sheave Make Direct Drive Test Pressures Pre -Filter SP In -0.3 in. we Pre -Filter SP Out ANA in. we Heat. Coil SP In ANA in. we Heat. Coil SP Out -2.04 in. we Cool. Coil SP In -2.04 in. we Cool. Coil SP Out -2.45 in. we Fan SP In -2.45 in. we Fan SP Out 1.61 in. we OA Damper Pos 100 % RA Damper Pos N/A % Actual E.S.P. 1.91 in. we AHU-01 30-Jan-14 Emerson Moore CFM was recorded with all boxes on full cooling. Unit total design CFM based on VAV summation. AHU-01 30-Jan-14 Emerson Moore Static Pressure Set Point = 1.12 in. w.c. L.H. Finn andAssociales Panes 4 of 79 i r Lawrence H. Finn & Associates, Inc. aBB 2359 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014 LOCATION: Fort Collins, CO CONTACT: Emerson Moore SYSTEM/UNIT: AHU-01 /V1-01 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 45 Box Inlet Size 6 In. K Factor -1 1.862 AHU-01/V1-01 Supply Outlet Summary Tested By: Emerson Moore Test Date: January 30, 2014 Term Box Test Data Max Des. CFM 440 CFM Max Act. CFM 436 CFM Min Des. CFM 375 CFM Min Act. CFM 370 CFM Heat Des. CFM 375 CFM Heat Act. CFM 370 CFM System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 108 H 8" Round 88 65 86 74 98 Outlet-02 108 H 8" Round 88 76 90 86 102 Outlet-03 108 H 8" Round 88 45 85 51 97 Outlet-04 108 H 8" Round 88 135 88 153 100 Outlet-05 108 H 8" Round 88 137 87 156 99 Totals 1 440 1 458 1 436 1 104 % 99 * Notes SYSTEM/UNIT: AHU-01 /V1-02 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 46 Box Inlet Size 6 In. K Factor -1 2.077 AHU-01 /V1-02 Supply Outlet Summary Tested By: Joe Castanon Test Date: January 24, 2014 Term Box Test Data Max Des. CFM 440 CFM Max Act. CFM 444 CFM Min Des. CFM 375 CFM Min Act. CFM 379 CFM Heat Des. CFM 375 CFM Heat Act. CFM 379 CFM System 1 Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation %° Final Deviation Outlet-01 108 H 8" Round 88 71 85 81 97 Outlet-02 108 H 8" Round 88 77 91 88 103 Outlet-03 108 H 8" Round 88 76 89 86 101 Outlet-04 108 H 8" Round 88 61 93 69 106 Outlet-05 108 H 8" Round 88 105 86 119 98 Totals : 440 1 390 1 444 1 89 % T01 * Notes L.H. Finn and Associates Pnnn...r, of 79 Lawrence H. Finn & Associates, Inc. KF,BB 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014 LOCATION: Fort Collins, CO CONTACT: Emerson Moore SYSTEM/UNIT: AHU-01 /V1-03 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 47 Box Inlet Size 5 In. K Factor -1 1.838 AHU-01 /V1-03 Supply Outlet Summary Tested By: Joe Castanon Test Date: January 27, 2014 Term Box Test Data Max Des. CFM 320 CFM Max Act. CFM 324 CFM Min Des. CFM 275 CFM Min Act. CFM 273 CFM Heat Des. CFM 275 CFM Heat Act. CFM 273 CFM System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 109 F 8x6 160 170 165 106 103 Outlet-02 109 F 8x6 160 161 159 101 99 Totals : 320 331 324 103 % 101 % * Notes SYSTEM/UNIT: AHU-01 /V1-04 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 48 Box Inlet Size 7 In. K Factor -1 1.981 AHU-01 / V1-04 Supply Outlet Summary Tested By: Joe Castanon Test Date: January 24, 2014 Term Box Test Data Max Des. CFM 615 CFM Max Act. CFM 603 CFM Min Des. CFM 525 CFM Min Act. CFM 547 CFM Heat Des. CFM 525 CFM Heat Act. CFM 547 CFM System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 112 H 8" Round 90 50 90 56 100 Outlet-02 112 H 8" Round 90 83 88 92 98 Outlet-03 112 H 8" Round 90 79 86 88 96 Outlet-04 112 H 8" Round 90 91 90 101 100 Outlet-05 109 H 8" Round 85 159 82 187 96 Outlet-06 109 H 8" Round 85 131 82 154 96 Outlet-07 109 H 8" Round 85 58 85 68 100 Totals : 615. 651 603 106 % 98 % * Notes L.H. Finn and Associates �:...., �....,,.. Panes F of 79 Lawrence H. Finn & Associates, Inc.BB 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014 LOCATION: Fort Collins, CO CONTACT: Emerson Moore SYSTEM/UNIT: AHU-01 /V1-05 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 49 Box Inlet Size 8 In. K Factor -1 1.610 AHU-01 /V1-05 Supply Outlet Summary Tested By: Emerson Moore Test Date: January 30, 2014 Term Box Test Data Max Des. CFM 880 CFM Max Act. CFM 853 CFM Min Des. CFM 750 CFM Min Act. CFM 744 CFM Heat Des. CFM 750 CFM Heat Act. CFM 744 CFM System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 123 H 8" Round 75 44 72 59 96 Outlet-02 123 H 8" Round 75 34 71 45 95 Outlet-03 125 M 48x2 Slot 100 149 97 149 97 Outlet-04 125 M 48x2 Slot 100 134 96 134 96 Outlet-05 125 M 48x2 Slot 100 125 95 125 95 Outlet-06 124 H 8" Round 60 46 62 77 103 Outlet-07 125 M 24x2 Slot 60 54 63 90 105 Outlet-08 125 M 24x2 Slot 60 57 58 95 97 Outlet-09 125 M 242 Slot 60 91 57 152 95 Outlet-10 125 M 242 Slot 60 52 57 87 95 Outlet-11 125 M 242 Slot 60 46 58 77 97 Outlet-12 101 H 8" Round 70 54 67 77 96 Totals : 880: 886 853 101 % 97 % * Notes AHU-01 / V1-05 24-Jan-14 Josh Behrendsen VAV set to match outlet summation. L.H. Finn and Associates Panes 7 of 79 Lawrence H.. Finn & Associates, Inc. r1E,BV 2389 Air Handling Unit PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014 LOCATION: Fort Collins, CO CONTACT: Emerson Moore SYSTEM/UNIT: AHU-01 /V1-06 AREA: Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 9 In. K Factor -1 1.668 AHU-01 /V1-06 Supply Outlet Summary Tested By: Joe Castanon Test Date: January 24, 2014 Term Box Test Data Max Des. CFM 1002 CFM Max Act. CFM 998 CFM Min Des. CFM 1002 CFM Min Act. CFM 998 CFM Heat Des. CFM 1002 CFM Heat Act. CFM 998 CFM System / Unit Area Served Outlet Type Size LxW I D AK Factof Maximum Design Prelim Reading Maximum final % Prelim Deviation . % Final Deviation Outlet-01 104 M 48x2 Slot 167 164 171 98 102 Outlet-02 104 M 48x2 Slot 167 159 165 95 99 Outlet-03 104 M 48x2 Slot 167 93 166 56 99 Outlet-04 104 M 48x2 Slot 1 167 234 167 140 100 Outlet-05 104 M 48x2 Slot 1 1 167 1 219 1 166 1 131 99 Outlet-06 104 M 48x2 Slot 1 167 220 1 163 1 132 98 Totals : 1,002 1,089 998 109 %, 100. % * Notes AHU-01 / V1-06 24-Jan-14 Josh Behrendsen VAV set to match outlet summation. SYSTEM/UNIT: AHU-01 /V1-07 AREA: Unit Data Manufacturer Titus Model Number DESV VAV Address 51 Box Inlet Size 6 In. K Factor -1 2.436 * Notes SYSTEM/UNIT: AHU-01 / V2-01 AREA: Unit Data a Manufacturer Titus Model Number DESV VAV Address 52 Box Inlet Size 5 In. K Factor -1 1.400 Tested By: Emerson Moore Test Date: January 30, 2014 Term Box Test Data Max Des. CFM 435 CFM Max Act. CFM 431 CFM Min Des. CFM 435 CFM Min Act. CFM 431 CFM Heat Des. CFM 435 CFM Heat Act. CFM 431 CFM Tested By: Keith Finn Test Date: January 22, 2014 Term Box Test'Data_' Max Des. CFM 225 CFM Max Act. CFM 229 CFM Min Des. CFM 145 CFM Min Act. CFM 151 CFM * Notes L.H. Finn and Associates Panes R of 79