CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
DATE
1/31/14
PROJECT
Colorado State University
Engines & Energy Conservation Laboratory
430 N. College Avenue
Ft. Collins, CO
ARCHITECT
Neenan Archistruction
2607 Midpointe Drive
Ft. Collins, CO
ENGINEER
AE Associates, Inc.
5587 W. 18th Street
Greeley, CO
CONTRACTOR
Air Comfort, Inc. Lind's Plumbing & Heating, Inc.
150 Rome Court 1414 Blue Spruce Drive, Unit A
Ft. Collins, CO Ft. Collins, CO
r
Lawrence H. Finn & Associates,Inc. B
2s89
Air Handling Unit
PROJECT: CSIJ Engines & Energy Conversion Laboratory
LOCATION: Fort Collins, CO
SYSTEM/UNIT: AHU-01 / V2-02
AREA:
Uriit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
53
Box Inlet Size
5 In.
K Factor -1
1.495
* Notes
SYSTEM/UNIT: AHU-01 / V2-03
AREA:
Unit Data _ -
Manufacturer
Titus
Model Number
DESV
VAV Address
54
Box Inlet Size
6 In.
K Factor -1
2.054
* Notes
DATE: 1 /31/2014
CONTACT: Emerson Moore
Tested By: Keith Finn
Test Date: January 22, 2014
Term Bok Test Data
Max Des. CFM
300 CFM
Max Act. CFM
303 CFM
Min Des. CFM
255 CFM
Min Act. CFM
255 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
410 CFM
Max Act. CFM
412 CFM
Min Des. CFM
350 CFM
Min Act. CFM
350 CFM
SYSTEM/UNIT: AHU-01 / V2-04 Tested By: Keith Finn
AREA: Test Date: January 22, 2014
Unit Data'.
Manufacturer
Titusa
Model Number
DESV
VAV Address '
56
Box Inlet Size
5 In.
K Factor-1
1.379
* Notes
Term Box.Tesf Data
Max Des. CFM
226 CFM
Max Act. CFM
219 CFM
Min Des. CFM.
195 CFM
Min Act. CFM
197 CFM
SYSTEM/UNIT: AHU-01 /V2-05 Tested By: Keith Finn
AREA: Test Date: January 22, 2014
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
56
Box Inlet Size
4 In.
K Factor -1
1.587
* Notes
Term Box Test'Data
Max Des. CFM
120 CFM
Max Act. CFM
123 CFM .
Min Des. CFM
120 CFM
Min Act. CFM
123 CFM
L.H. Finn and Associates
Panes A of 79
Lawrence H. Finn Associates, Inc. P1� `9
if k
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory
LOCATION: Fort Collins, CO
SYSTEM/UNIT: AHU-01 / V2-06
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
57
Box Inlet Size
5 In.
K Factor -1
1.500
* Notes
SYSTEM/UNIT: AHU-01 / V2-07
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
58
Box Inlet Size
5 In.
K Factor -1
1.866
* Notes
SYSTEM/UNIT: AHU-01 / 1/2-08
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
59
Box Inlet Size
4 In.
K Factor -1
1.172
* Notes
SYSTEM/UNIT: AHU-01 / V3-01
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
31
Box Inlet Size
5 In.
K Factor -1
1.557
* Notes
DATE: 1 /31 /2014
CONTACT: Emerson Moore
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
300 CFM
Max Act. CFM
295 CFM
Min Des. CFM
255 CFM
Min Act. CFM
246 CFM
Tested By: Emerson Moore
Test Date: January 23, 2014
Term Box Test Data
Max Des. CFM'
300 CFM
Max Act. CFM
303 CFM
Min Des. CFM
255 CFM
Min Act. CFM
255 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
120 CFM
Max Act. CFM
123 CFM
Min Des. CFM
120 CFM
Min Act. CFM
123 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
225 CFM
Max Act. CFM
224 CFM
Min Des. CFM
195 CFM
Min Act. CFM
206 CFM
L.H. Finn and Associates
Panes in of 79
t""'r
Lawrence H. Finn & Associates, Inc. NAEs
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014
LOCATION: Fort Collins, CO CONTACT: Emerson Moore
SYSTEM/UNIT: AHU-01 / V3-02
AREA:
Unit. Data
Manufacturer
Titus
Model Number
DESV
VAV Address
32
Box Inlet Size
5 In.
K Factor-1
1.504
* Notes
SYSTEM/UNIT: AHU-01 / V3-03
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
33
Box Inlet Size
5 In.
K Factor -1
1.496
* Notes
SYSTEM/UNIT: AHU-01 /V3-04
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
34
Box Inlet Size
4 In.
K Factor -1
1.078
* Notes
SYSTEM/UNIT: AHU-01 /V3-05
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
35
Box Inlet Size
4 In.
K Factor-1
1.066
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
300 CFM
Max Act. CFM
289 CFM
Min Des. CFM
255 CFM
Min Act. CFM
258 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
300 CFM
Max Act. CFM
303 CFM
Min Des. CFM
255 CFM
Min Act. CFM
257 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
200 CFM
Max Act. CFM
195 CFM
Min Des. CFM
170 CFM
Min Act. CFM
174 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
200 CFM
Max Act. CFM
198 CFM
Min Des. CFM
170 CFM
Min Act. CFM
174 CFM
* Notes
L. H. Finn and Associates
Panes 1 1 of 79
Lawrence H. Finn & Associates, Inc. N E
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014
LOCATION: Fort Collins, CO CONTACT: Emerson Moore
SYSTEM/UNIT: AHU-01 / V3-06
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
36
Box Inlet Size
5 In.
K Factor -1
1.496
* Notes
SYSTEM/UNIT: AHU-01 / V3-07
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
37
Box Inlet Size
5 In.
K Factor-1
1.501
* Notes
SYSTEM/UNIT: AHU-01 /V4-01
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
38
Box Inlet Size
4 In.
K Factor -1
1.037
* Notes
SYSTEM/UNIT: AHU-01 / V4-02
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
39
Box Inlet Size
5 In.
K Factor -1
1.887
* Notes
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
270 CFM
Max Act. CFM
271 CFM
Min Des. CFM
270 CFM
Min Act. CFM
271 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
300 CFM
Max Act. CFM
294 CFM
Min Des. CFM
255 CFM
Min Act. CFM
252 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
150 CFM
Max Act. CFM
148 CFM
Min Des. CFM
130 CFM
Min Act. CFM
133 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
300 CFM
Max Act. CFM
298 CFM
Min Des. CFM
255 CFM
Min Act. CFM
259 CFM
L.H. Finn and Associates
=:__, �--- Panes 19 of 79
r
Lawrence H. Finn & Associates, Inc. P.!
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014
LOCATION: Fort Collins, CO CONTACT: Emerson Moore
SYSTEM/UNIT: AHU-01 / V4-03
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
40
Box Inlet Size
5 In.
K Factor -1
1.490
* Notes
SYSTEM/UNIT: AHU-01 / V4-04
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
41
Box Inlet Size
4 In.
K Factor -1
1.413
* Notes
SYSTEM/UNIT: AHU-01 / V4-05
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
42
Box Inlet Size
4 In.
K Factor-1
1.83
* Notes
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
300 CFM
Max Act. CFM
300 CFM
Min Des. CFM
255 CFM
Min Act. CFM
248 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
150 CFM
Max Act. CFM
151 CFM
Min Des. CFM
130 CFM
Min Act. CFM
129 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test Data
Max Des. CFM
150 CFM
Max Act. CFM
147 CFM
Min Des. CFM
130 CFM
Min Act. CFM
132 CFM
L.H. Finn and Associates
=:...., �--- Panes 1 � of 79
9 .wM }
Lawrence H. Finn & Associates, Inc. N , e �
2389
Fan Unit
PROJECT: CSU Engines & Energy Conversion Laboratory
LOCATION: Fort Collins, CO
SYSTEM/UNIT: EF-03
AREA: Roof
Unit Data
Fan Manufacturer
Twin City Fan
Fan Model Number
BCRD-160D
Fan Serial Number
G13-000000095270
Fan Type
Backward Incline
Fan Class
1
Fan Arrangement
SWSI
Fan Discharge
Downblast
Starter Data
Installed Thermal
Internal
Test Data
Total CFM Design
1885 CFM
Total CFM Actual
1889 CFM
Fan RPM Actual
1176 RPM
Motor Volts 1
210 Volts
Motor Amps 1
3.8 Amps
SP In Actual
-0.46 in. we
SP Out Actual
0.0 in. we
Total SP Actual
0.46 in. we
EF-03 Exhaust Inlet Summary
DATE: 1 /31 /2014
CONTACT: Emerson Moore
Tested By: Emerson Moore
Test Date: January 30, 2014
Motor Data
Motor Manufacturer
SMC
Motor Frame
56C
Motor HP
1/2 HP
Motor RPM
1750 RPM
Motor Rated Volts
115/208-230 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
8.2/4.1 Amps
Motor Service Factor
1.15
Nominal Efficiency
61 %
Power Factor
65
Sheave Data
Motor Sheave Make
Browning
Motor Sheave Model
Adjustable
Motor Sheave Diam.
3 3/4 in.
Motor Operating Diameter 3 112
Motor Sheave Bore
5/8 in.
Fan Sheave Make
Browning
Fan Sheave Model
AK 54
Fan Sheave Diam.
5 1/4 in.
Fan Sheave Bore
3/4 in.
Number of Belts
1
Belt Size
4L 280 in.
Sheave Center Line
5 1/4 in.
System f Unit
Area Served
Outlet
Type
Size LxW ! D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum%a
Final
Prelim
Deviation
% Final
Deviation
Inlet -A
Crawl Space
ER
435
425
423
98
97
Inlet-B
121
E
12x12
300
242
311
81
104
Inlet-C
122
E
12x12
300
246
305
82
102
Inlet-D
114
E
6x6
75
62
73
83
97
Inlet-E
See Print
E
8x8
110
117
109
106
99
Inlet-F
117
E
6x6
50
59
49
118
98
Inlet-G
116
E
6x6
50
58
52
116
104
Inlet-H
112
E
6x6
115
0
116
0
101
Inlet -I
232
E
10x10
225
350
222
156
99
Inlet-J
See Print
E
10x10
225
350
229
156
102
Totals:
-
-
-
1,885
1,909
1,889
101 %
100 %
* Notes
L.H. Finn and Associates
Panes 17 of 79
Lawrence H. Finn & Associates, Inc. NE{
2389
Fan Unit
PROJECT: CSU Engines & Energy Conversion Laboratory
LOCATION: Fort Collins, CO
SYSTEM/UNIT: EF-04
AREA: 322
Unit Data
Fan Manufacturer
Twin City Fan
Fan Model Number
T400L
Fan Type
Forward Curve
Fan Size
6" ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Horizontal
Starter Data
Installed Thermal
Internal
Test Data
Total CFM Design
300 CFM
Total CFM Actual
287 CFM
Fan RPM Actual
Direct Drive RPM
Motor Volts 1
121 Volts
Motor Amps 1
1.1 Amps
SP In Actual
-0.09 in. we
SP Out Actual
0.21 in. we
Total SP Actual
0.30 in. we
EF-04 Exhaust Inlet Summary
DATE: 1 /31 /2014
CONTACT: Emerson Moore
Tested By: Joe Castanon
Test Date: January 24, 2014
Motor Data
Motor Manufacturer Broan
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 1.4 Amps
Sheave Data
Motor Sheave Make Direct Drive
System /Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet -A
321
E
8x8
150
151
144
101
96
Inlet-13
322
E
8x8
150
130
143
87
95
Totals :
300
281
287
94 %
96 %
* Notes I EF-04 24-Jan-14 Joe Castanon Unit contains 1 motor and 2 blowers.
L.H. Finn and Associates
Pane 1 R of 79
r'
Lawrence H. Finn & Associates, Inc. !�� �'
2389
Fan Unit
PROJECT: CSU Engines & Energy Conversion Laboratory
LOCATION: Fort Collins, CO
SYSTEM/UNIT: EF-05
AREA: 401
Unit Data
Fan Manufacturer
Twin City Fan
Fan Model Number T500L
Fan Type
Forward Curve
Fan Size
6" ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Horizontal
Starter Data
Installed Thermal
Internal
Test Data
Total CFM Design
500 CFM
Total CFM Actual
477 CFM
Fan RPM Actual
Direct Drive RPM
Motor Volts 1
122 Volts
Motor Amps 1
1.8 Amps
SP In Actual
-0.09 in. we
SP Out Actual
0.25 in. we
Total SP Design
0.50 in. we
Total SP Actual
0.34 in. we
EF-05 Exhaust Inlet Summary
DATE: 1 /31 /2014
CONTACT: Emerson Moore
Tested By: Joe Castanon
Test Date: January 24, 2014
Motor Data
Motor Manufacturer Broan
Motor Rated Volts 120 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 2.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet -A
402
E
8x8
150
146
146
97
97
Inlet-B
401
E
8x8
150
142
142
95
95
Inlet-C
Under Floor
200
189
189
95
95
Totals :
-
-
500
477
477
95 %
95 %
* Notes
EF-05 24-Jan-14 Joe Castanon Inlet-C for future connection. Balanced to design of
200 CFM as per note on page M1.24A.
EF-05 24-Jan-14 Joe Castanon Unit contains 1 motor and 2 blowers.
L.H. Finn and Associates
_. Panes I of 79
PRESSURIZATION TEST DATA
SUMMARY
PROJECT INFORMATION
Normalized Leakage Rate (cfm/ft2 @75Pa)
0.1713
Test Date
January 11, 2014
Normalized Leakage Rate _low (cfm/ft2 @75Pa)
0.1693
Client
Neenan
Normalized Leakage Rate_high (cfm/ft2 @75Pa)
0.1733
Project
CSU - EECL
PIE Project #
C0111586.00
Envelope Area (W)
82,648
Location
Fort Collins, CO
Equivalent Leakage Area, EgLA (ft2) @ 0.3 1nWG
10.8
Fan #
14,15,16
DATA ANALYSIS
PRECISION & BIAS
ENVIRONMENTAL VALUES
nP U.b334
Avg n - x 3.9b9b
Density_in
Ln C 6.8872
Avg (Ingo) - y 9.4015
Density_out (lb/ft3)
0.0665
C 979.7
S2x 0.0493
Density ref (lb/ft3)
0.0752
CP 919.1
Sx 0.2219
Dyn.
Viscosity, u, press (lb/ft/h)
0.0434
P_ref (Pa) 75
S2y 0.0200
Dyn. Viscosity,
u, depress (lb/ft/h)
0.0420
AI_Pref (inWg) 0.3
Sy 0.1413
Dyn.
Viscosity, u_o, ref (lb/ft/h)
0.0439
Q @ 75Pa 14157.2
Sxy 0.0312
Temp out (OF)
38.0
Q@4Pa 2211.5
np 0.6334
-initial
Temp out _final (OF)
39.0
InC 6.8872
Temp out_avg (OF)
38.5
95% Confidence Limits
C 979.67
Temp in -initial (OF)
61.0
Qo @ 75Pa_low 13995.2
Sn 0.0135
Temp in -final (OF)
61.0
Qo @ 75Pa_high 14321.2
S_InC 0.0538
Temp in_avg (OF)
61.0
Confidence Interval 0.0020
T(95%,N) 2.0739
Temp ref (OF)
68.0
1_I11C 0.1116
Elevation (ft)
4,982
Avg. Baseline Pressures (Pa):
I_n 0.0281
Elevation _ref (ft)
0
Station X 3.38
Pa (x) 75
Wind Speed (mph)
0
Sy(x) 0.0056
Wind Direction
n/a
FAN STATION DESCRIPTION
ly(x) U.U115
Station Number # of fans
INTERIOR AP CHECK (Pa) - EXTERIOR/INTERIOR CONTROL STATION
1 3
Pressure Tap
AP (aD 50 Pa
CS - 4th East
0.4
EXTERIOR TAP LOCATION
C3 - 3rd Last
0.2
#1 West Elevation
CS - 2nd East
0.1
CS - 1st East
0.1
4th East - 1 st East
0.0
Pie Consulting & Engineering Page 1 of 8
PRESSURIZATION TEST DATA
idex
P tar et
MEASURED
P (Pal
PLOT VALUES
Q CFM P corr
LN(PLOT
Q corr Ln P corr
14534 4.27
VALUES)
Ln Q corr BASELINE
1
80
74.9
4265 71.5
9.58 3.8
2
80
74.9
4260 71.5
14517 4.27
9.58 3.9
3
80
74.8
4260 71.4
14517 4.27
9.58 3.9
4
75
69.8
4110 66.4
14006 4.20
9.55 4.0
5
75
69.8
4115 66.4
14023 4.20
9.55 4.0
6
75
69.8
4115 66.4
14023 4.20
9.55 3.9
to
b5.0
397U 61.b
13529 4.12
9.51 3.6
8
70
65.1
3970 61.7
13529 4.12
9.51 3.4
9
70
65.1
3970 61.7
13529 4.12
9.51 3.3
10
65
60.0
3745 56.6
12762 4.04
9.45 3.6
11
65
60.1
3745 56.7
12762 4.04
9.45 3.9
12
65
60.0
3745 56.6
12762 4.04
9.45 3.7
13
60
55.5
3500 52.1
11927 3.95
9.39 3.1
14
60
55.4
3500 52.0
11927 3.95
9.39 3.3
15
60
55.4
3495 52.0
11910 3.95
9.39 3.3
16
55
50.4
3230 47.0
11007 3.85
9.31 3.1
17
55
50.4
3230 47.0
11007 3.85
9.31 2.8
18
55
50.4
3235 47.0
11024 3.85
9.31 2.8
19
.50
45.0
3000 41.6
10223 3.73
9.23 2.8
20
50
45.1
3000 41.7
10223 3.73
9.23 3.0
21
50
45.1
3000 41.7
10223 3.73
9.23 3.0
22
45
40.0
2870 36.6
9780 3.60
9.19 3.0
23
45
40.0
2870 36.6
9780 3.60
9.19 3.0
24
45
39.9
2870 36.5
9780 3.60
9.19 3.0
Pie Consulting & Engineering Page 2 of 8
9.65
9.60
9.55
9.50
9.45
LL
U
9.40
ry
0 9.35
U-
c
9.30
9.25
9.20
9.15
9.10
3.50
PRESSURIZATION DATA
y = 0.6334x + 6.8872
R2 = 0.9901
n
3.60 3.70 3.80 3.90 4.00
Ln Pressure (Pa)
Page 3 of 8
E
4.10 4.20 4.30 4.40
Lawrence H. Finn & Associates, Inc.
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory
LOCATION: Fort Collins, CO
SYSTEM/UNIT: AHU-01
AREA:
Unit Data
Unit Manufacturer
Annex Air
Unit Model Number
MAU-E-07-D-D-H-WMP24
Unit Serial Number
2092-01-0813
AHU-01 / Supply Fan
Fan Type
Air Foil
Fan Size
29" OD
Fan Class
1
Fan Arrangement
SWSI
Fan Discharge
Plenum
AHU-01 / SF Final Filter Bank
Filter Manufacturer
AAF
Filter Type
Bag
Filter Quantity
3/3
Filter Size
12x24xl2/24x24xl2
AHU-01 / SF Pre -Filter Bank
Filter Manufacturer
AAF
Filter Type
Pleated
Filter Quantity
3/3
Filter Size
12x24x2/24x24x2
Starter Data
AHU-01 / Supply Fan
Installed Thermal
VFD
Test Data
Total CFM Design
8977 CFM
Total CFM Actual
9651 CFM
OA CFM Design
8977 CFM
OA CFM Actual
9651 CFM
RA CFM Design
0 CFM
RA CFM Actual
0 CFM
AHU-01 / Supply Fan
Fan RPM Actual
1731 RPM
Motor Volts 1
448 Volts
Motor Volts 2
448 Volts
Motor Volts 3
448 Volts
Motor Amps 1
12.5 Amps
Motor Amps 2
12.5 Amps
Motor Amps 3
12.5 Amps
VFD Speed
58.4 HZ
* Notes
DATE: 1 /31 /2014
CONTACT: Emerson Moore
Tested By: Emerson Moore
Test Date: January 30, 2014
Motor Data
AHU-01 / Supply Fan
Motor Manufacturer
Baldor
Motor Frame
254T
Motor HP
15 HP
Motor RPM
1765 RPM
Motor Rated Volts
208-2301460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
37.4-35.4117.7 Amps
Motor Service Factor
1.15
Nominal Efficiency
93 %
Power Factor
86
Sheave Data
AHU-01 / Supply Fan
Motor Sheave Make
Direct Drive
Test Pressures
Pre -Filter SP In
-0.3 in. we
Pre -Filter SP Out
ANA in. we
Heat. Coil SP In
ANA in. we
Heat. Coil SP Out
-2.04 in. we
Cool. Coil SP In
-2.04 in. we
Cool. Coil SP Out
-2.45 in. we
Fan SP In
-2.45 in. we
Fan SP Out
1.61 in. we
OA Damper Pos
100 %
RA Damper Pos
N/A %
Actual E.S.P.
1.91 in. we
AHU-01 30-Jan-14 Emerson Moore CFM was recorded with all boxes on full cooling.
Unit total design CFM based on VAV summation.
AHU-01 30-Jan-14 Emerson Moore Static Pressure Set Point = 1.12 in. w.c.
L.H. Finn andAssociales
Panes 4 of 79
i r
Lawrence H. Finn & Associates, Inc. aBB
2359
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014
LOCATION: Fort Collins, CO CONTACT: Emerson Moore
SYSTEM/UNIT: AHU-01 /V1-01
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
45
Box Inlet Size
6 In.
K Factor -1
1.862
AHU-01/V1-01 Supply Outlet Summary
Tested By: Emerson Moore
Test Date: January 30, 2014
Term Box Test Data
Max Des. CFM
440 CFM
Max Act. CFM
436 CFM
Min Des. CFM
375 CFM
Min Act. CFM
370 CFM
Heat Des. CFM
375 CFM
Heat Act. CFM
370 CFM
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
108
H
8" Round
88
65
86
74
98
Outlet-02
108
H
8" Round
88
76
90
86
102
Outlet-03
108
H
8" Round
88
45
85
51
97
Outlet-04
108
H
8" Round
88
135
88
153
100
Outlet-05
108
H
8" Round
88
137
87
156
99
Totals
1 440
1 458
1 436
1 104 %
99
* Notes
SYSTEM/UNIT: AHU-01 /V1-02
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
46
Box Inlet Size
6 In.
K Factor -1
2.077
AHU-01 /V1-02 Supply Outlet Summary
Tested By: Joe Castanon
Test Date: January 24, 2014
Term Box Test Data
Max Des. CFM
440 CFM
Max Act. CFM
444 CFM
Min Des. CFM
375 CFM
Min Act. CFM
379 CFM
Heat Des. CFM
375 CFM
Heat Act. CFM
379 CFM
System 1 Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
%° Final
Deviation
Outlet-01
108
H
8" Round
88
71
85
81
97
Outlet-02
108
H
8" Round
88
77
91
88
103
Outlet-03
108
H
8" Round
88
76
89
86
101
Outlet-04
108
H
8" Round
88
61
93
69
106
Outlet-05
108
H
8" Round
88
105
86
119
98
Totals :
440
1 390
1 444
1 89 %
T01
* Notes
L.H. Finn and Associates
Pnnn...r, of 79
Lawrence H. Finn & Associates, Inc. KF,BB
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014
LOCATION: Fort Collins, CO CONTACT: Emerson Moore
SYSTEM/UNIT: AHU-01 /V1-03
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
47
Box Inlet Size
5 In.
K Factor -1
1.838
AHU-01 /V1-03 Supply Outlet Summary
Tested By: Joe Castanon
Test Date: January 27, 2014
Term Box Test Data
Max Des. CFM
320 CFM
Max Act. CFM
324 CFM
Min Des. CFM
275 CFM
Min Act. CFM
273 CFM
Heat Des. CFM
275 CFM
Heat Act. CFM
273 CFM
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
109
F
8x6
160
170
165
106
103
Outlet-02
109
F
8x6
160
161
159
101
99
Totals :
320
331
324
103 %
101 %
* Notes
SYSTEM/UNIT: AHU-01 /V1-04
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
48
Box Inlet Size
7 In.
K Factor -1
1.981
AHU-01 / V1-04 Supply Outlet Summary
Tested By: Joe Castanon
Test Date: January 24, 2014
Term Box Test Data
Max Des. CFM
615 CFM
Max Act. CFM
603 CFM
Min Des. CFM
525 CFM
Min Act. CFM
547 CFM
Heat Des. CFM
525 CFM
Heat Act. CFM
547 CFM
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
112
H
8" Round
90
50
90
56
100
Outlet-02
112
H
8" Round
90
83
88
92
98
Outlet-03
112
H
8" Round
90
79
86
88
96
Outlet-04
112
H
8" Round
90
91
90
101
100
Outlet-05
109
H
8" Round
85
159
82
187
96
Outlet-06
109
H
8" Round
85
131
82
154
96
Outlet-07
109
H
8" Round
85
58
85
68
100
Totals :
615.
651
603
106 %
98 %
* Notes
L.H. Finn and Associates
�:...., �....,,.. Panes F of 79
Lawrence H. Finn & Associates, Inc.BB
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014
LOCATION: Fort Collins, CO CONTACT: Emerson Moore
SYSTEM/UNIT: AHU-01 /V1-05
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
49
Box Inlet Size
8 In.
K Factor -1
1.610
AHU-01 /V1-05 Supply Outlet Summary
Tested By: Emerson Moore
Test Date: January 30, 2014
Term Box Test Data
Max Des. CFM
880 CFM
Max Act. CFM
853 CFM
Min Des. CFM
750 CFM
Min Act. CFM
744 CFM
Heat Des. CFM
750 CFM
Heat Act. CFM
744 CFM
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
123
H
8" Round
75
44
72
59
96
Outlet-02
123
H
8" Round
75
34
71
45
95
Outlet-03
125
M
48x2 Slot
100
149
97
149
97
Outlet-04
125
M
48x2 Slot
100
134
96
134
96
Outlet-05
125
M
48x2 Slot
100
125
95
125
95
Outlet-06
124
H
8" Round
60
46
62
77
103
Outlet-07
125
M
24x2 Slot
60
54
63
90
105
Outlet-08
125
M
24x2 Slot
60
57
58
95
97
Outlet-09
125
M
242 Slot
60
91
57
152
95
Outlet-10
125
M
242 Slot
60
52
57
87
95
Outlet-11
125
M
242 Slot
60
46
58
77
97
Outlet-12
101
H
8" Round
70
54
67
77
96
Totals :
880:
886
853
101 %
97 %
* Notes AHU-01 / V1-05 24-Jan-14 Josh Behrendsen VAV set to match outlet summation.
L.H. Finn and Associates
Panes 7 of 79
Lawrence H.. Finn & Associates, Inc. r1E,BV
2389
Air Handling Unit
PROJECT: CSU Engines & Energy Conversion Laboratory DATE: 1/31/2014
LOCATION: Fort Collins, CO CONTACT: Emerson Moore
SYSTEM/UNIT: AHU-01 /V1-06
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
Box Inlet Size
9 In.
K Factor -1
1.668
AHU-01 /V1-06 Supply Outlet Summary
Tested By: Joe Castanon
Test Date: January 24, 2014
Term Box Test Data
Max Des. CFM
1002 CFM
Max Act. CFM
998 CFM
Min Des. CFM
1002 CFM
Min Act. CFM
998 CFM
Heat Des. CFM
1002 CFM
Heat Act. CFM
998 CFM
System / Unit
Area Served
Outlet
Type
Size LxW I D
AK
Factof
Maximum
Design
Prelim
Reading
Maximum
final
% Prelim
Deviation .
% Final
Deviation
Outlet-01
104
M
48x2 Slot
167
164
171
98
102
Outlet-02
104
M
48x2 Slot
167
159
165
95
99
Outlet-03
104
M
48x2 Slot
167
93
166
56
99
Outlet-04
104
M
48x2 Slot
1
167
234
167
140
100
Outlet-05
104
M
48x2 Slot
1
1 167
1 219
1 166
1 131
99
Outlet-06
104
M
48x2 Slot
1
167
220
1 163
1 132
98
Totals :
1,002
1,089
998
109 %,
100. %
* Notes AHU-01 / V1-06 24-Jan-14 Josh Behrendsen VAV set to match outlet summation.
SYSTEM/UNIT: AHU-01 /V1-07
AREA:
Unit Data
Manufacturer
Titus
Model Number
DESV
VAV Address
51
Box Inlet Size
6 In.
K Factor -1
2.436
* Notes
SYSTEM/UNIT: AHU-01 / V2-01
AREA:
Unit Data a
Manufacturer
Titus
Model Number
DESV
VAV Address
52
Box Inlet Size
5 In.
K Factor -1
1.400
Tested By: Emerson Moore
Test Date: January 30, 2014
Term Box Test Data
Max Des. CFM
435 CFM
Max Act. CFM
431 CFM
Min Des. CFM
435 CFM
Min Act. CFM
431 CFM
Heat Des. CFM
435 CFM
Heat Act. CFM
431 CFM
Tested By: Keith Finn
Test Date: January 22, 2014
Term Box Test'Data_'
Max Des. CFM
225 CFM
Max Act. CFM
229 CFM
Min Des. CFM
145 CFM
Min Act. CFM
151 CFM
* Notes
L.H. Finn and Associates
Panes R of 79