HomeMy WebLinkAbout430 N College Ave - Special Inspections/Blower Door Test - 01/14/2014■
1119
CONSULTING Sc
ENGINEERING
January 14, 2014
CSURF C/O of Mr. Jeff Jensen
Jensen Consulting
37154 Dickerson Run
Windsor, Colorado 80550
Project Name: CSU Engines and Energy Conversion Lab (EECL) Jensen
Consulting/CSURF
Pie Project Number: C0111586.00 (010)
Location: Fort Collins, Colorado
Subject: Air Barrier Performance Testing Report
Dear Mr. Jensen:
Per our agreement for professional services, Pie Consulting & Engineering (Pie) has conducted
performance testing of the air barrier system for the CSU EECL located in Fort Collins,
Colorado. The purpose of this performance evaluation was to provide CSURF a building air
tightness performance value of the as -constructed air barrier.
This report provides The City of Fort Collins a Certification of Compliance, summary of the air
barrier test procedure, and results of our performance testing. The purpose of the performance
testing was to quantify the amount of air leakage occurring through the air barrier test
envelope.
The testing was performed on January 11, 2014 by Mr. Troy Rodvold of Pie.
Air Barrier Performance Testing Report CSU EECL Jensen Consulting/CSURF
CITY OF FORT COLLINS CERTIFICATE OF COMPLIANCE
Building Air Leakage Test Results
Pressurization
Metric
Requirement
Actual
Requirement Met/Not Met
n
0.45,< n < 0.8
.6334
Met
C
N/A
919.1
N/A
rz
rz> 0.98
.9901
Met
CFM75/sq ft
Actual < 0.25 CFM 75/sq ft
0.1713
Met
95% C.I. Upper
N/A
0.1733
N/A
95% C.I. Lower
N/A
0.1693
N/A
EgLA75
N/A
10.8
N/A
Depressurization
Metric
Requirement
Actual
Requirement Met/Not Met
n
0.45 < n < 0.8
0.6973
Met
C
N/A
548.1
N/A
r2
rz > 0.98
.9973
Met
CFM75/sq ft
Actual < 0.25 CFM 75/sq ft
0.1346
Met
95% C.I. Upper
N/A
0.1351
N/A
95% C.I. Lower
N/A
0.1341
N/A
EgLA75
N/A
8.5
N/A
Average
Metric
Requirement
Actual
Requirement Met/Not Met
CFM75/ sq ft
Actual < 0.25 CFM 75/sq ft
0.1529
Met
Pie Consulting & Engineering Page 2 of 9 Cot 11586.00 (010)
Air Barrier Performance Testing Report CSU — Engines and Energy Conversion Lab
1
The test boundary area was obtained from the Architect of
Record and was checked on -site for reasonableness.*
��- Initial
2
Set up was performed according to section 2 of the test form and
all deviations and their impact noted here.
\ 1Z Initial
3
Test equipment used was in compliance with respect to accuracy
and calibration date.
Initial
4
The test procedure used was in compliance except as noted here.
N/A
Initial
5
The calculations were done in strict accordance with ASTM
E779-10 except as noted in this Protocol.
_ Initial
6
Provide the value calculated in step 5.15 (or 5.11 or 5.4 if
applicable).
.15 CFM75/sq ft
7
Determine pass/fail status based on the average of
pressurization and depressurization.
Pass
8
All accuracies, pressure limits, data correlations, and confidence
intervals are within the bounds specified in steps 3, 4, and 5 and
all deviations are noted here.
`T�
Initial
9
Supporting documentation described in steps 1, 3, 6, and 7 is
attached to this test form, including all digital photographs of the
"T b
building and test procedure.-
Initial
est oundary area was not provided by the DOR, and was provided by pie's plan take -off calculations.
I hereby certify that the results above are in conformance with the City of Fort Collins Air
Leakage Test Protocol.
Testing agency name:
Pie Consulting & Engineering
Testing agency authorize representative signature:
1--� Z
Testing agency authorized representative printed name:
Troy Rodvold
Date: January 13, 2014
Pie Consulting & Engineering Page 3 of 9 CO111586.00
Air Barrier Performance Testing Report CSU EECL Jensen Consulting/CSURF
BACKGROUND
On March 22, 2011, the City of Fort Collins adopted Ordinance No. 031, 2011 amending Chapter
5, Article II, Division 2 of the Code of the City of Fort Collins for the purpose of amending the
2009 International Energy Conservation Code (Ordinance). This ordinance requires (among
other measures) that all new buildings, additions, and those undergoing major renovations
shall have an air leakage rate that does not exceed 0.25 CFM75/sq ft of the total building
envelope area when tested in accordance with the City of Fort Collins Air Leakage Test Protocol
for Non- Residential Building Enclosures (Protocol).
This Directive references ASTM E 779-03, Standard Test Method for Determining Air Leakage Rate
by Fan Pressurization, as well as ASTM E 1827, Standard Test Methods for Determining Airtightness
of Buildings Using an Orifice Blower Door.
EXECUTIVE SUMMARY
A. _ On January 11, 2014, Pie conducted the building performance testing of the CSU -
Engines and Energy Conversion Lab located in Fort Collins, Colorado to determine the
current air tightness value for the building. Testing was conducted in general
accordance with the City of Fort Collins Building Air Leakage Test Protocol, which
references ASTM E 779, using controlled pressurization and depressurization
techniques.
B. The building was tested with the air barrier test envelope in the "closed" condition,
where applicable; as listed in Table 1 of ASTM E 1827-96 (2002) Standard Test Methods for
Determining Air Tightness of Buildings Using an Orifice Blower Door. The normalized
results of the air tightness testing of the building are listed in Figure 1.
Upper Limit
Percent above Max
Air Leakage
Air Leakage
Allowable
(CFM/ftz at
(CFM/ft2 at 757
(0.25 CFM/ft2 at 75-Pa)
Description
75-Pa)
Pa) -
OR PASS
Pressurization
0.171
0.173
PASS
Depressurization
0.135
0.135
PASS
Average
0.153
0.154
PASS
Figure 1 - Air Tightness Testing Results
C. The building passed the City of Fort Collins air tightness requirement (0.25 CFM/ft2 at
75-Pa). As a result, diagnostic evaluation of the building air leakage was not required
and was not performed.
Pie Consulting & Engineering Page 4 of 9 Cot11586.00 (010)
Air Barrier Performance Testing Report CSU EECL Jensen Consulting/CSURF
B. Pie measured and recorded 48 data points during both pressurization and
depressurization testing. Linear regression analysis was conducted to accurately
determine the overall air tightness value of the building.
C. Data points were plotted and a clear, unambiguous correlation between the measured
pressure differentials and total system flows was established.
1. Linear regression and data analysis were conducted in accordance with ASTM
E779 to determine the air leakage coefficients, CP and Cd, at standard conditions
and the pressure exponents, np and na, for pressurization and depressurization
testing. The correlation between the log -linearized pressure differential and flow
rate was analyzed to determine the validity of the test data.
2. Based on the Protocol, a correlation (Rz) of 0.98 or greater is necessary for the
data collected during testing to be considered accurate and reproducible. After
the flow coefficient and exponent were calculated, the overall air leakage rate at
75-Pa, Q75, at standard conditions was calculated and divided by the total surface
area of the air barrier, which provided the building air -leakage value.
D. A 95-percent confidence interval (95% CI) is included in the test. The 95-percent Cl can
be interpreted to mean there is a 95-percent chance that the calculated results of the air
tightness testing are between the "high" and "low' measured values. A smaller
confidence interval indicates less variation in the measurements and therefore more
accurate the test data.
1. The Fort Collins Protocol requires the 95% CI not exceed 0.02 for mean values of
0.25 or less, which equates to approximately 8-percent. The data collected on this
building resulted in a relatively narrow confidence interval, which confirms a
strong relationship between pressure and flow. The subject building data meets
the Protocol requirements.
E. The pressurization air barrier test results are listed in Figure 2. Reference Attachment A
at the end of this report for the raw data, calculations, and precision and baseline.
Pressurization Air Leakage Coefficient, C
919.1
Pressurization exponent, np
0.6334
Q at 75-Pa (CFM)
14,157.2
Air Barrier Envelope Area W
82,648
Air Leakage CFM/ft2envelo a at 75-Pa
0.1713
95% Confidence Limits CFM/ftzenvelope at 75-Pa
0.1693 - 0.1733
Upper Limit Air Leakage (CFM/ ftz envelope at 75-Pa
0.1733
Correlation Value, Rz
0.9901
Equivalent Leakage Area, E LA ftz at 75-Pa
10.8
Measured air tightness above the Protocol requirement
of 0.25CFM/ftzenvelope % , or PASS
PASS
Figure 2 -Pressurization Air Tightness Test Results
Pie Consulting & Engineering Page 7 of 9 CO111586.00 (010)
Air Barrier Performance Testing Report CSU EECL Jensen Consulting/CSURF
F. The depressurization test results are listed in Figure 3. Reference Attachment A at the
end of this report for the raw data, calculations, and precision and baseline.
Depressurization Flow Coefficient, Ca
548.1
Depressurization Pressure Exponent, na
0.6973
Q at 75-Pa (CFM)
11,127.2
Air Barrier Envelope Area ft2
82,648
Air Leakage CFWft2 envelo a at 75-Pa
0.1346
95% Confidence Limits CFM/ft2envelo a @ 75-Pa
0.1341- 0.1351
Upper Limit Air Leakage CFM/ft2 envelo e ® 75-Pa
0.1351
Correlation Value, R2
0.9973
Equivalent Leakage Area, E LA ftz
8.5
Measured air tightness above the Protocol requirement
of O.25CFM/ft2envelope % , or PASS
PASS
Figure 3 - Depressurization Air Tightness Test Results
G. The equivalent leakage areas (EgLA) listed in Figures 2 and 3 are 10.8-ft2 and 8.5-ft2,
respectively. These values represent the theoretical equivalent "hole" sizes in the air
barrier test envelope if all leakage areas were combined into a single opening.
Pie Consulting & Engineering Page 8 of 9 C0111586.00 (010)
Air Barrier Performance Testing Report CSU EECL Jensen Consulting/CSURF
Pie hereby certifies that the results above are in conformance with the City of Fort Collins
Building Air Leakage Testing Protocol (2011-12-09).
The opinions and results described in this report are based on information available at the time
of the testing and preparation of this report. Should additional information or unknown
conditions be uncovered or made available, Pie Consulting & Engineering retains the right to
revise and supplement this report accordingly.
Sincerely,
Pie Consulting & Engineering
Prepared by,
Troy Rodvold
Building Science Specialist
�oY�Or�W,
42822
/ Whew Hemn
(` 142014 I:46 PM
FSS/ONA���
Reviewed by,
Matthew D. Heron, P.E., LEED® AP
Department Manager - Building Science Group
TSR:MDH:ta
Attachments: Attachment A: Air Tightness Performance Testing Raw Data and Analysis
Attachment B: Digital Photographs
Attachment C: Retrotec Calibration Data
k:12011\co11158600\task 010 - air barrier testing\05 reports attachments submittals\2014-01-14-csueecl-abtrpt.docx
Pie Consulting & Engineering Page 9 of 9 C0111586.00 (010)
ATTACHMENT A - AIR TIGHTNESS PERFORMANCE'
TESTING RAW DATA AND ANALYSIS