HomeMy WebLinkAbout2333 Strawfork Dr - Disclosures/Blower Door Test - 07/11/20140
0
GS Services
Date of Test: 7/11/2014
Customer: Bartran Homes
Fort Collins, CO
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve:
BUILDING LEAKAGE TEST
GS Services
2000 S. College Ave
Suite 308
Fort Collins, Co 80525
Test File: Bartran Homes 2333 Strawfork -Res5 BD
Technician: Paul Higman
Project Number:
Building Address: 2333 Strawfork
Fort Collins, CO 80525
1377 CFM50 (+/- 1.4 %)
2.32 ACH50
75.7 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 193.4 (+/- 10.7 %)
Exponent (n) = 0.502 ( +/- 0.030 )
Correlation Coefficient = 0.99783
4. Test Settings: Test Standard: RESNET Mufti -Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 77.8 CFM
0.13 ACH
2. Estimated Design Infiltration Rate: Winter: 125.4 CFM Summer: 83.3 CFM
0.21 ACH 0.14 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
Paul
Higman
Digitally signed by: Paul
Higman
DN: CN = Paul Higman
C=US
Date: 2014.07.15 08:38:
22-06'00'
No Text
No Text
No Text