HomeMy WebLinkAbout2842 Council Tree Ave - Special Inspections/Field Verification - 02/24/2012w
NEBB Certification # 3235 JEDI Balancing, Inc. Certification#BB009025C
568 Briggs Street
P.O. Box 525 / 8
Erie, CO. 80516
Phone (720) 839-5333
Fax (303) 828-0768
Website: www.iedibalancing.com
Certified Test; Adjust; & Balance Report
Project
Address
Contractor
Architect
Mechanical Engineer
Balance Technicians
Date
Job Number
'D'ABB Technici&II
1Vatnc Donald Pl t
TABB IDt BDO65617 r
Superyf r
Not VpUS't
Tip Toe Nail Salon
2842 Council Tree Ave Suite 125 FT Collins, CO
Comfort Air
Unknown
NFE Engineering Services
Ethan Smith
January 9°i 2012
2012-3378
AID
a0Y28
ft TeatYap. AC,u�a�N,GyaO6taklp,�Otlt.pu
' fANNBRRB Technician
Name: Gmgory Burn
TA IU IDi BB2057927T
� EXDira Uon Dnui 1Li1/2011
NM Vc4WUnlza
pinwr
9B000OOSC
SuFmrv' Or a0729
121311201
DONiLLD V4 PITfSER
CERTIFICATION .
\3235 12r;,
Exp. 3137l
vee�
2" 214 _ I -�-
1/9
Fly
wpot TA F44i ey
Roof Top Unit
PROJECT: TIP TOE NAIL SALON
LOCATION: FORT COLLINS, CO
PROJECT #: 2012-3378
SYSTEM/UNIT: RTU-01
AREA:
Unit Data
Unit Manufacturer
CARRIER
Unit Model Number
48TCFA05A2A6A
Unit Serial Number
1111G30286
Total CFM Design
1600
Outside Air CFM Design
828
Total Connected CFM
1600
Starter Data
RTU-01 / Supply Fan
Starter Manufacturer
thermally protected
Test Data
Total CFM Actual
1605
Outside Air CFM Actual
0
Return Air CFM Actual
1605
RTU-01 / Supply Fan
Fan RPM Actual
1030
Motor Volts 1
460
Motor Amps 1
1.2
RTU-01 Supply Outlet Summary
DATE: 1 /9/2012
CONTACT: Trevor Ouain
AUTHOR: Greg Barnes
Tested By: Ethan Smith
Test Date: January 06, 2012
Motor Data
RTU-01 I Supply Fan
Motor Manufacturer
GENTEO
Motor HP
1
Motor RPM
1650
Motor Rated Volts
460
Motor Phase
1
Sheave Data
RTU-01 I Supply Fan
Motor Sheave Model
1 v134
Motor Sheave Bore
5/8" in.
Fan Sheave Model
AFD44
Fan Sheave Bore
5/8" in.
Number of Belts
1
Belt Size
AX35
Test Pressures
CA Damper Position
N/A %
Filter SP In
-0.21 in. we
Filter SP Out
NO ACCESS in. we
Cool Coil SP In
NO ACCESS in. we
Cool Coil SP Out
-0.40 in. we
Fan SP In
-0.40 in. we
Fan SP Out
0.31 in. we
System / Unit
Type of
Reading
Outlet
Type
AK
Factor
Design
Reading
Min
Reading
Prelim
Reading
% Prelim
Deviation
Final
Reading
% Final
Deviation
Outlet-01
SD
190
240
126
200
105
Outlet-02
SD
190
180
95
180
95
Outlet-03
SD
80
140
175
80
100
Outlet-04
SD
190
25
13
185
97
Outlet-05
SD
190
200
105
190
100
Outlet-06
SD
1 1-1—
200
105
185
97
Outlet-07
SD
190
170
89
185
97
Outlet-08
SD
190
230
121
200
105
Outlet-09
SD
190
225
118
200
105
Totals:
-
-
-
1,600
-
1,610
101 %
1,605
100
* Notes
✓EDI Balancing, Inc. Page 1 of 1
5/9
Fan Unit
PROJECT: TIP TOE NAIL SALON
LOCATION: FORT COLLINS, CO
PROJECT #: 2012-3378
SYSTEM/UNIT: EF-B
AREA:
Unit Data
Fan Manufacturer GROAN
Fan Model Number 684-0I2684F-A
Rated CFM 80
Total Connected CFM 80
Starter Data
Starter Manufacturer thermally protected
Test Data
Total CFM Actual 80
Fan RPM Actual DIRECT DRIVE
Motor Volts 1 Actual 121
Motor Amps 2 Actual 0.5
EF-B Exhaust Inlet Summary
r
err•r
DATE: 1/9/2012
CONTACT: Trevor Quain
AUTHOR: Greg Barnes
Tested By: Ethan Smith
Test Date: January 06, 2012
Motor Data
Motor Manufacturer BROAN
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps 0.5
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
S
System / Unit
Face Area
AK Factor
Outlet
Type
Prelim
Reading
Final
Reading
Design
Reading
%Final
Deviation
Inlet-01
TOTAL
80
80
80
0
100
Totals:
-
-
-
80
80
80
100
* Notes
✓ED/ Balancing, Inc. Page 1 of2
6/9
LY
i"PIP IF X
Fan Unit
PROJECT: TIPTOE NAIL SALON
LOCATION: FORT COLLINS, CO
PROJECT #: 2012-3378
SYSTEM/UNIT: EF-H
AREA:
Unit Data
Fan Manufacturer PENNSARRY
Fan Model Number FX11R
Fan Serial Number F11A135804
Rated CFM 828
Total Connected CFM 820
Starter Data
Starter Manufacturer thermally protected
Test Data
Total CFM Actual 810
Motor Volts 1 Actual 121
Motor Amps 1 Actual 1.6
EF-H Exhaust Inlet Summary
r—
DATE: 1/9/2012
CONTACT: Trevor Quain
AUTHOR: Greg Barnes
Tested By: Ethan Smith
Test Date: January 06, 2012
Motor Data
Motor Manufacturer fasco
Motor HP 116
Motor RPM 1550
Motor Rated Volts 115
Motor Phase 1
Motor FL Amps 1.5
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual -0.21 in. we
Fan SP Out Actual ATMOSPHERE in. we
System / Unit
Face Area
AK Factor
Outlet
Type
Prelim
Reading
Final
Reading
Design
Reading
% Final
Deviation
Inlet-01
ER
195
195
205
95
Inlet-02
ER
210
210
205
102
Inlet-03
ER
195
210
205
102
Inlet-04
ER
195
195
205
95
Totals:
-
-
-
795
810
820
99 %
* Notes
JED/ Balancing, Inc. Page 2 of
7/9