HomeMy WebLinkAbout4856 Innovation Dr - Special Inspections/Field Verification - 04/21/2014Lawrence He Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-01
AREA:
Unit Manufacturer
Trane
Unit Model Number
YSC120A4RMAOF0001
Unit Serial Number
205100857L
Unit Discharge
Vertical/Down
U-01 / Supply Fan
Fan Type
Forward Curve
Fan Size
12" ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
U-01 I Filter Bank
Filter Manufacturer
Koch
Filter Type
Pleated
Filter Quantity
4
Filter Size
20x25x2
(E)RTU-01 / Supply Fan
Installed Thermal Internal
Total CFM Design 4000 CFM
Total CFM Actual 4038 CFM
Outside Air CFM Design None Shown CFM
Fan RPM Actual
680 RPM
Motor Volts 1
489 Volts
Motor Volts 2
490 Volts
Motor Volts 3
490 Volts
Motor Amps 1
4.0 Amps
Motor Amps 2
3.9 Amps
Motor Amps 3
4.0 Amps
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor HP
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Motor Service Factor
NE_ BB
4
2389
Tested By: Emerson Moore
Test Date: April 16, 2014
Motor Sheave Make
Motor Sheave Model
Motor Sheave Diam.
Motor Sheave Bore
Motor Operating Diameter
Fan Sheave Make
Fan Sheave Model
Fan Sheave Diam.
Fan Sheave Bore
Number of Belts
Belt Size
Sheave Center Line
Fan SP In Actual
Fan SP Out Actual
External SP In Actual
External SP Out Actual
Unit External SP Actual
FilterlCoil SP In
FilterlCoil SP Out
GE
56HZ
3 HP
1725 RPM
208-230/460 Volts
3
60 Hz
9.4-9.2/4.6 Amps
1.15
Browning
Adjustable
3 1/4 in.
7/8 in.
3 1/4 in.
Browning
AK59
5 3/4 in.
1 in.
1
A35
11 1/2 in.
-0.78 in. we
0.25 in. we
-0.45 in. we
0.25 in. we
0.7 in. we
-0.45 in. we
-0.78 in. we
L. H Finn and Associates
Final Report Page 14 of 41
r
Lawrence H. Finn & Associates, Inc. N E B B
2389
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-06 (Cont.)
AREA:
(E)RTU-06 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
Tested By: Emerson Moore
Test Date: April 16, 2014
Outlet-01
238
N
24x24
225
202
226
90
100
Outlet-02
238
N
24x24
225
178
221
79
98
Outlet-03
238
N
24x24
225
212
219
94
97
Outlet-04
238
N
24x24
275
365
273
133
99
Outlet-05
238
N
2424
275
276
267
100
97
Outlet-06
238
R
24x24
250
256
243
102
97
Outlet-07
238
R
24x24
250
263
245
105
98
Outlet-08
238
N
24x24
225
196
224
87
100
Outlet-09
238
R
24x24
250
232
251
93
100
Outlet-10
238
R
24x24
250
159
244
64
98
Outlet-11
238
N
24x24
225
216
231
96
103
Outlet-12
239
N
24x24
225
168
223
75
99
Outlet-13
239
R
250
254
252
102
101
Outlet-14
239
R
;24x24;
250
220
248
88
99
* Notes
L. H Finn and Associates
Final Report
Page 23 of 41
74-1
Lawrence H. Finn & Associates, Inc. N E B B
2389
Roof Top Unit
PROJECT: F+yy Media (Bldg #2) DATE: 4/21/2014
LOCATION: Fort Collins, CO CONTACT: Dave Reichel
SYSTEM/UNIT: (E)RTU-07
Tested By: Emerson Moore
AREA:
Test Date: April 16, 2014
Unit Manufacturer
Trane
(E)RTU-07 / Supply Fan
Unit Model Number
YCD210C4HCDA
Motor Manufacturer
Marathon
Unit Serial Number
Z50101560D
Motor Frame
184TZ
Unit Discharge
Vertical/Down
Motor HP
7.5 HP
(E)RTU-07 / Supply Fan
Motor RPM
3460 RPM
Fan Type
Forward Curve
Motor Rated Volts
460 Volts
Fan Size
12" ID
Motor Phase
3
Fan Class
1
Motor Hertz
60 Hz
Fan Arrangement
DWDI
Motor FL Amps
8.8 Amps
Fan Discharge
Horizontal
Motor Service Factor
1.15
(E)RTU-07 / Filter Bank
Nominal Efficiency
87.5 %
Filter Manufacturer
Koch
Power Factor
90.5
Filter Type
Pleated
Filter Quantity
2/4
Filter Size
20x2Ox2/2Ox25x2
7(E)RTU-07 / Supply Fan
Installed The Internal
Total CFM Design 7000 CFM
Total CFM Actual 6737 CFM
Outside Air CFM Design None Shown CFM
Fan RPM Actual
1514 RPM
Motor Volts 1
490 Volts
Motor Volts 2
490 Volts
Motor Volts 3
489 Volts
Motor Amps 1
8.1 Amps
Motor Amps 2
8.7 Amps
Motor Amps 3
8.4 Amps
Motor Sheave Make
Browning
Motor Sheave Model
VP60
Motor Sheave Diam.
6 in.
Motor Sheave Bore
1 1/8 in.
Motor Operating Diameter 5 1/4 in.
Fan Sheave Make
Browning
Fan Sheave Model
BK120
Fan Sheave Diam.
12 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
BX68
Sheave Center Line
20 in.
Fan SP In Actual
-1.77 in. we
Fan SP Out Actual
0.31 in. we
External SP In Actual
-0.95 in. we
External SP Out Actual
0.31 in. we
Unit External SP Actual
1.26 in. we
Filter/Coil SP In
-0.95 in. we
Filter/Coil SP Out
-1.77 in. we
L. H Finn and Associates
Final Report
Page 24 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-07 (Cont.)
AREA:
(E)RTU-07 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
N EB
2389
Tested By: Emerson Moore
Test Date: April 16, 2014
Outlet-01
237
R
24x24
250
229
237
92
95
Outlet-02
237
R
24x24
250
230
236
92
94
Outlet-03
236
CD
24x24
250
215
242
86
97
Outlet-04
236
CD
2424
250
223
242
89
97
Outlet-05
233
N
2424
200
184
194
92
97
Outlet-06
233
N
2424
200
137
189
69
95
Outlet-07
233
N
24x24
200
172
186
86
93
Outlet-08
233
N
24x24
200
150
188
75
94
Outlet-09
233
N
2424
200
189
192
95
96
Outlet-10
233
N
2424
200
138
187
69
94
Outlet-11
235
N
2424
175
221
167
126
95
Outlet-12
233
N
24x24
200
193
j 192
97
96
Outlet-13
233
N
24x24
200
186
193
93
97
Outlet-14
233
N
24x24
200
165
190
83
95
Outlet-15
233
N
24x24
200
178
189
89
95
Outlet-16
233
N
2424
200
155
192
78
96
Outlet-17
233
N
24x24
200
236
193
118
97
Outlet-18
233
N
24x24
225
213
225
95
100
Outlet-19
233
N
2424
225
227
219
101
97
Outlet-20
232
N
24x24
225
220
217
98
96
Outlet-21
232
N
24x24
225
197
209
88
93
Outlet-22
232
N
24x24
225
212
214
94
95
Outlet-23
232
N
24x24
225
237
218
105
97
Outlet-24
232
N
24x24
225
200
217
89
96
Outlet-25
232
N
2424
225
209
220
93
98
Outlet-26
232
N
24x24
225
193
218
86
97
Outlet-27
232
N
24x24
225
211
217
94
96
Outlet-28
232
N
24x24
225
258
220
115
98
Outlet-29
232
N
24x24
225
216
223
96
99
Outlet-30
220
N
24x24
150
230
148
153
99
Outlet-31
219
N
24x24
200
264
196
132
98
Outlet-32
218
N
24x24
225
243
218
108
97
Outlet-33
233
N
24x24
150
284
149
189
99
* Notes
L. H. Finn and Associates
Final Repoli
Page 25 of 41
Lawrence He Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (N)RTU-01
AREA:
Unit Manufacturer
Trane
Unit Model Number
4YCC3018A1040BA
Unit Serial Number
13501 HXG9H
Unit Discharge
Vertical/Down
Fan Type
Forward Curve
Fan Type
Forward Curve
Fan Size
10"ID
Fan Size
10" ID
Fan Class
1
Fan Class
1
Fan Arrangement
DWDI
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
Fan Discharge
Horizontal
U-01 / Filter Bank
Fitter Manufacturer
EZ KLEEN
Filter Type
Washable
Filter Quantity
1
Filter Size
16x20x1
(N)RTU-01 / Supply Fan
Installed Thermal Internal
Installed Thermal Internal
Total CFM Design
800 CFM
Total CFM Actual
859 CFM
Outside Air CFM Design
160 CFM
Outside Air CFM Actual
168 CFM
Return Air CFM Design
640 CFM
Return Air CFM Actual
691 CFM
DATE: 4/21 /2014
CONTACT: Dave Reichel
r
NE BB
_.
2389
Tested By: Wade Wilson
Test Date: April 16, 2014
Motor Manufacturer
Emerson
Motor Manufacturer
Genteq
Motor Frame
48Y
Motor HP
.87 HP
Motor HP
1/8 HP
Motor RPM
1075(2 SPD) RPM
Motor RPM
825 RPM
Motor Rated Volts
460 Volts
Motor Rated Volts
208-230 Volts
Motor Phase
1
Motor Phase
1
Motor Hertz
60 Hz
Motor Hertz
60 Hz
Motor FL Amps
3.3 Amps
Motor FL Amps
1.0 Amps
(N)RTU-01 / Supply Fan
Motor Sheave Make Direct Drive
Motor Sheave Make Direct Drive
Fan SP In Actual
-0.18 in. we
Fan SP Out Actual
0.26 in. we
External SP In Actual
-0.01 in. we
External SP Out Actual
0.26 in. we
OA Damper Pos Actual
18 %
RA Damper Pos Actual
82 %
Unit External SP Actual
0.27 in. we
Fitter SP In
0.0 in. we
Filter SP Out
- 0.01 in. we
Coil SP In
- 0.01 in. we
Coil SP Out
- 0.18 in. we
Fan RPM Actual
Direct Drive RPM
L
I
Fan RPM Actual
Direct Drive RPM
Motor Vohs 1
490 Volts
Motor Volts 1
211 Volts
Motor Amps 1
1.0 Amps
(N)RTU-01 Supply Outlet Summary
"Outlet-qOl205
R 24x24
200
267
214
134 107
Outlet-02 205
R 24x24
200
256
217
128 109
Outlet-03 205
R 24x24
200
192
215
96 108
Outlet-04 205
R 24x24
200
237
213
119 107
L. H. Finn and Associates
Final Report
Page 26 of 41
r ♦ r
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (N)RTU-01 (Cont.)
AREA:
* Notes
DATE: 4/21 /2014
CONTACT: Dave Reichel
NB
2389
Tested By: Wade Wilson
Test Date: April 16, 2014
L.H Finn and Associates
Final Report
Page 27 of 41
Lawrence He Finn & Associates, Inc. NEE
2389
Fan Coil
PROJECT: F+N/ Media (Bldg #2) DATE: 4/21/2014
LOCATION: Fort Collins, CO CONTACT: Dave Reichel
SYSTEM/UNIT: AC-01
AREA: 208
Filter Manufacturer
Filter Type
Filter Oty
Filter Size
Unit Location
Total CFM Design
Total CFM Actual
OSA Design
Motor Volts Tl-T2
Motor Volts T2-T3
Motor Volts T1-T3
Amps T1
Amps T2
Amps T3
Fan RPM Actual
Unit E.S.P. Design
Unit E.S.P. Actual
E.S.P. In
E.S.P. Out
Liebert
MERV 8
1
2
20x25x2
3720 CFM
3774 CFM
NA CFM
494 Volts
491 Volts
492 Volts
2.8 Amps
2.9 Amps
2.7 Amps
887 RPM
0.5 In. wc.
0.25 In. wc.
-0.18 In. wc.
0.07 In. wc.
AC-01 Supply Outlet Summary
* Notes
Motor Manufacturer
Motor HP
Motor RPM
Motor Phase
Motor Hertz
Motor Service Factor
Motor Rated Volts
Motor FL Amps
Power Factor
Nominal Efficiency
Motor Sheave Make
Motor Sheave Model
Motor Sheave Diam.
Motor Sheave Bore
Fan Sheave Make
Fan Sheave Model
Fan Sheave Diam.
Fan Sheave Bore
Number of Belts
Belt Size
Sheave Center Line
Tested By: Emerson Moore
Test Date: April 16, 2014
US Motor
3
1750 RPM
3
60 Hz
1.15
208-230/460
7.0-6.3/3.1 Amps
78.9
84 %
Browning
1VP50
5 in.
7/8 in.
Browning
BK95H
9 1/2 in.
1 in.
1
B52
16 in.
L. H Finn and Associates
Final Report
Page 28 of 41
Lawrence H. Finn & Associates, Inc. ANT
2389
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-01 (Cont.)
AREA:
(E)RTU-01 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
Tested By: Emerson Moore
Test Date: April 16, 2014
"Out01
234
R
24x24
175
194
173
111
99
Outlet-02
234
N
24x24
175
156
172
89
98
Outlet-03
233
N
24x24
225
193
228
86
101
Outlet-04
233
R
24x24
225
197
231
88
103
Outlet-05
233
N
24x24
225
196
232
87
103
Outlet-06
233
R
24x24
225
231
225
103
100
Outlet-07
233
N
24x24
225
191
236
85
105
Outlet-08
233
R
24x24
225
200
224
89
100
Outlet-09
233
R
24x24
225
178
226
79
100
Outlet-10
233
N
24x24
225
168
227
75
101
Outlet-11
233
R
24x24
225
235
227
104
101
Outlet-12
233
N
24x24
225
197
232
88
103
Outlet-13
233
R
24x24
225
225
229
100
102
Outlet-14
231
CD
24x24
325
298
319
92
98
Outlet-15
230
CD
24x24
225
187
228
83
101
Outlet-16
229
CD
24x24
225
175
231
78
103
Outlet-17
228
CD
24x24
200
195
196
98
98
Outlet-18
228
CD
24x24
200
189
202
95
101
* Notes
L. H. Finn and Associates
Final Report Page 15 of 41
Lawrence He Finn & Associates, Inc. Nil9
2389
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-02
AREA:
Unit Manufacturer
Unit Model Number
Unit Serial Number
Unit Discharge
Fan Type
Fan Size
Fan Class
Fan Arrangement
Fan Discharge
Filter Manufacturer
Filter Type
Filter Quantity
Filter Size
Trane
YSC060A4RHAOGD101
203100082L
Vertical/Down
Forward Curve
8"ID
1
DWDI
Vertical/Down
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor HP
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Tested By: Emerson Moore
Test Date: April 16, 2014
Emerson
48Y
1 HP
1075(2 SPD) RPM
460 Volts
1
60 Hz
3.2 Amps
Koch
Pleated (E)RTU-02 / Supply an
2 Motor Sheave Make Direct Drive
20x30x1 71
(EIRTU-02 / Supply Fan
Installed Thermal Internal
Total CFM Design 2000 CFM
Total CFM Actual 2067 CFM
Outside Air CFM Design None Shown CFM
Fan RPM Actual Direct Drive RPM
Motor Volts 1 490 Volts
Motor Amps 1 2.0 Amps
(E)RTU-02 Supply Outlet Summary
Fan SP In Actual
-0.68 in. we
Fan SP Out Actual
0.33 in. we
External SP In Actual
-0.12 in. we
External SP Out Actual
0.33 in. we
Unit External SP Actual
0.45 in. we
Fier/Coil SP In
-0.12 in. we
Filter/Coil SP Out
-0.68 in. we
Outlet-01
221
CD
2424
250
176
262
70
105
Outlet-02
222
CD
24x24
250
221
257
88
103
Outlet-03
223
CD
24x24
250
178
265
71
1D6
Outlet-04
224
CD
24x24
250
300
260
120
104
Outlet-05
227
N
2424
250
261
253
104
101
Outlet-06
227
N
24x24
250
401
264
160
106
Outlet-07
226
CD
2424
250
283
252
113
101
Outlet-08
225
CD
24x24
250
279
254
112
102
* Notes
L. N. Finn and Associates
Final Report Page 16 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-03
AREA:
Unit Manufacturer
Trane
Unit Model Number
YSC072A4RMA0BD001
Unit Serial Number
203100034L
Unit Discharge
Vertical/Down
J-03 / Supply Fan
Fan Type
Forward Curve
Fan Size
10"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
J-03 / Filter Bank
Filter Manufacturer
Koch
Filter Type
Pleated
Filter Quantity
4
Filter Size
16x25x2
(E)RTU-03 / Supply Fan
Installed Thermal Internal
Total CFM Design 2405 CFM
Total CFM Actual 2304 CFM
Outside Air CFM Design None Shown CFM
Fan RPM Actual
828 RPM
Motor Volts 1
490 Volts
Motor Volts 2
490 Volts
Motor Volts 3
490 Volts
Motor Amps 1
1.3 Amps
Motor Amps 2
1.4 Amps
Motor Amps 3
1.5 Amps
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor HP
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Motor Service Factor
r
NE BB
2389
Tested By: Emerson Moore
Test Date: April 16, 2014
GE
56
1 HP
1725 RPM
200-230/460 Volts
3
60 Hz
3.2-4.0/2.0 Amps
1.5
Motor Sheave Make
Browning
Motor Sheave Model
Adjustable
Motor Sheave Diam.
3 3/4 in.
Motor Sheave Bore
5/8 in.
Motor Operating Diameter 3 in.
Fan Sheave Make
Browning
Fan Sheave Model
AK64
Fan Sheave Diam.
6 1/4 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
A32
Sheave Center Line
10 in.
Fan SP In Actual
-0.25 in. we
Fan SP Out Actual
0.16 in. we
External SP In Actual
-0.13 in. we
External SP Out Actual
0.16 in. we
Unit External SP Actual
0.29 in. we
Filter/Coil SP In
-0.13 in. we
Filter/Coil SP Out
-0.25 in. we
L. H. Finn and Associates
Final Report Page 17 Of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-03 (Cont.)
AREA:
(E)RTU-03 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
r
KTB
2389
Tested By: Emerson Moore
Test Date: April 16, 2014
"Outlet-"01210
CD
24x24
100
92
98
92
98
Outlet-02
211
CD
24x24
200
191
189
96
95
Outlet-03
212
CD
24x24
200
152
188
76
94
Outlet-04
213
CD
24x24
200
209
195
105
98
Outlet-05
214
CD
24x24
200
187
191
94
96
Outlet-06
215
CD
24x24
200
195
194
98
97
Outlet-07
216
CD
24x24
225
131
217
58
96
Outlet-08
217
R
24x24
270
198
267
73
99
Outlet-09
217
R
24x24
270
230
253
85
94
Outlet-10
217
R
24x24
270
169
257
63
95
Outlet-11
217
R
24x24
270
223
255
83
94
* Notes
L. H. Finn and Associates
Final Report Page 18 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-04
AREA:
Unit Manufacturer
Trane
Unit Model Number
YSC048A4RMAOFD101
Unit Serial Number
203100050L
Unit Discharge
Vertical/Down
U-04 / Supply Fan
Fan Type
Forward Curve
Fan Size
10"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
U-04l Filter Bank
Filter Manufacturer
Koch
Filter Type
Pleated
Filter Quantity
2
Filter Size
20x25x2
(EIRTU-04 / Supply Fan
Installed Thermal Internal
Total CFM Design 1600 CFM
Outside Air CFM Design None Shown CFM
Fan RPM Actual Direct Drive RPM
Motor Volts 1 491 Volts
Motor Amps 1 1.8 Amps
(E)RTU-04 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
174-1
NE, 1B
2389
Tested By: Emerson Moore
Test Date: April 16, 2014
Motor Manufacturer
Emerson
Motor Frame
48Y
Motor HP
0.87 HP
Motor RPM
1075(2 SPD) RPM
Motor Rated Volts
460 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
3.3 Amps
(E)RTU-041 Supply Fan
Motor Sheave Make Direct Drive
Fan SP In Actual
-0.55 in. we
Fan SP Out Actual
0.39 in. we
External SP In Actual
-0.07 in. we
External SP Out Actual
0.39 in. we
Unit External SP Actual
0.46 in. we
Fiter/Coil SP In
-0.07 in. we
Filter/Coil SP Out
-0.55 in. we
Vili 1 lunk
4.
Atsa sarveiii
Type
Vii LWW76
a :..AK .
Factor
Design
Min? _
Reading
ko iilraii
Final
Deviation
7% al
Deviation
Outlet-01
206
N
24x24
200
263
217
132
109
Outlet-02
206
N
24x24
200
246
210
123
105
Outlet-03
206
N
24x24
200
232
217
116
109
Outlet-04
206
N
24x24
200
239
220
120
110
Outlet-05
207
R
24x24
300
473
330
158
110
Outlet-06
207
R
24x24
300
403
330
134
110
Outlet-07
233
N
24x24
200
47
217
24
109
' Notes
L. N Finn and Associates
Final Report Page 19 Of 41
Lawrence He Finn & Associates, Inc. N- Be
2389
Roof Top Unit
PROJECT: F+W Media (Bldg #2) DATE: 4/21/2014
LOCATION: Fort Collins, CO CONTACT: Dave Reichel
SYSTEM/UNIT: (E)RTU-05 Tested By: Emerson Moore
AREA: Test Date: April 16, 2014
Unit Manufacturer Trane
(E)RTU-05 / Supply Fan
Unit Model Number YSC120A4RMA0FD001
Motor Manufacturer GE
Unit Serial Number 205100817L
Motor Frame 56HZ
Unit Discharge Vertical/Down
Motor HP 3 HP
(E)RTU-05 / Supply Fan
Motor RPM 1725 RPM
Fan Type Forward Curve
Motor Rated Volts 208-230/460 Volts
Fan Size 12" ID
Motor Phase 3
Fan Class 1
Motor Hertz 60 Hz
Fan Arrangement DWDI
Motor FL Amps 9.4-9.2/4.6 Amps
Fan Discharge Vertical/Down
Motor Service Factor 1.15
(E)RTU-05 / Filter Bank
Filter Manufacturer Koch
Filter Type Pleated
Filter Quantity 4
(E)RTU-05 / Supply Fan
Filter Size 20x25x2
Motor Sheave Make Browning
Motor Sheave Model 1VP34
Motor Sheave Diam. 3 1/4 in.
Motor Sheave Bore 7/8 in.
(E)RTU-05 / Supply Fan
Motor Operating Diameter 3 in.
Installed Thermal Internal
Fan Sheave Make Browning
Fan Sheave Model AK59
Fan Sheave Diam. 5 3/4 in.
Fan Sheave Bore 1 in.
Total CFM Design 3950 CFM
Number of Belts 1
Total CFM Actual 3835 CFM
Belt Size A35
Outside Air CFM Design None Shown CFM
Sheave Center Line 12 in.
(E)RTU-05 / Supply Fan
Fan RPM Actual 992 RPM
Motor Volts 1 488 Volts
Motor Volts 2 489 Volts
Fan SP In Actual -0.57 in. we
Motor Volts 3 490 Volts
Fan SP Out Actual 0.1 in. we
Motor Amps 1 3.6 Amps
External SP In Actual -0.2 in. we
Motor Amps 2 3.6 Amps
External SP Out Actual 0.1 in. we
Motor Amps 3 3.4 Amps
Unit External SP Actual 0.3 in. we
Filter/Coil SP In -0.20 in. we
Filter/Coil SP Out -0.57 in. we
L. H Finn and Associates
Final Report Page 20 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-05 (Cont.)
AREA:
(E)RTU-05 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
Nam, BB
2389
Tested By: Emerson Moore
Test Date: April 16, 2014
"Out01
200
R
24x24
300
286
284
95
95
Outlet-02
202
R
2424
300
380
295
127
98
Outlet-03
240
CD
2424
300
384
292
128
97
Outlet-04
201
N
24x24
300
236
287
79
96
Outlet-05
240
N
24x24
250
205
237
82
95
Outlet-06
240
N
24x24
250
212
238
85
95
Outlet-07
240
N
24x24
250
219
243
88
97
Outlet-08
240
N
24x24
275
265
274
96
100
Outlet-09
240
N
24x24
250
215
234
86
94
Outlet-10
240
N
24x24
250
194
250
78
100
Outlet-11
240
CD
24x24
300
355
298
118
99
Outlet-12
240
N
24x24
300
224
300
75
100
Outlet-13
204
N
24x24
300
275
285
1 92
95
Outlet-14
203
R
24x24
325
368
318
113
98
* Notes
L. H. Finn and Associates
Final Report Page 21 of 41
Lawrence He Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #2)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-06
AREA:
Unit Manufacturer
Trane
Unit Model Number
YSC102A4RLA0BD001
Unit Serial Number
203100069L
Unit Discharge
Vertical/Down
U-06 / Supply Fan
Fan Type
Forward Curve
Fan Size
12"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
J-06/ Filter Bank
Filter Manufacturer
Koch
Filter Type
Pleated
Filler Quantity
4
Filter Size
20x25x2
(E)RTU-061 Supply Fan
Installed Thermal Internal
Total CFM Design 3400 CFM
Total CFM Actual 3367 CFM
Outside Air CFM Design None Shown CFM
Fan RPM Actual
742 RPM
Motor Volts 1
491 Volts
Motor Volts 2
490 Volts
Motor Volts 3
490 Volts
Motor Amps 1
3.2 Amps
Motor Amps 2
3.1Amps
Motor Amps 3
3.2 Amps
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor HP
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Motor Service Factor
NE BB
2389
Tested By: Emerson Moore
Test Date: April 16, 2014
GE
145T
2 HP
1725 RPM
200-230/460 Volts
3
60 Hz
6.3-6.2/3.1 Amps
1.15
Motor Sheave Make
Browning
Motor Sheave Model
1VL40
Motor Sheave Diam.
3 3/4 in.
Motor Sheave Bore
7/8 in.
Motor Operating Diameter 3 in.
Fan Sheave Make
Browning
Fan Sheave Model
AK74
Fan Sheave Diam.
7 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
A37
Sheave Center Line
11 1/2 in.
Fan SP In Actual
Fan SP Out Actual
External SP In Actual
External SP Out Actual
Unit External SP Actual
Filter/Coil SP In
Filter/Coil SP Out
-0.31 in. we
0.21 in. we
-0.1 in. we
0.21 in. we
0.31 in. we
-0.1 in. we
-0.31 in. we
L. H Finn and Associates
Final Report Page 22 of 41