HomeMy WebLinkAbout4856 Innovation Dr - Special Inspections/Field Verification - 04/21/2014 (2)Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave., Suite 220 — Eaton, CO 80615
Phone (970) 454-5351 — Fax (970) 454-5391
2389
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
DATE
4/21/14
PROJECT
F + W Media
Innovation Campus Bldg 1 & 2
4856 / 4868 Innovation Drive
Fort Collins, CO
ARCHITECT
Waring Associates
1875 Lawrence, Suite 700
Denver, CO
ENGINEER
MDP Engineering Group, P.C.
1800 Glenarm Place, Suite 800
Denver, CO
CONTRACTOR
Academy Heating & Cooling
1205 2nd Street
Eaton, CO
� I �
Lawrence He Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (N)RTU-03
AREA:
Unit Manufacturer
Unit Model Number
Unit Serial Number
Unit Discharge
Fan Type
Fan Size
Fan Class
Fan Arrangement
Fan Discharge
Filter Manufacturer
Filter Type
Filter Quantity
Filter Size
Trane
YSC048E4EHA1SD001000
140912389L
Vertical/Down
Forward Curve
10"ID
1
DWDI
Vertical/Down
Purolator
Disposable
2
20x3Ox2
7(N)RTU-03 / Suooly Fan
nstalled Thermal Internal
Total CFM Design
1600 CFM
Total CFM Actual
1615 CFM
Outside Air CFM Design
320 CFM
Outside Air CFM Actual
336 CFM
Return Air CFM Design
1280 CFM
Return Air CFM Actual
1279 CFM
DATE: 4/21 /2014
CONTACT: Dave Reichel
NE_ BB
2389
Tested By: Wade Wilson
Test Date: April 16, 2014
Motor Manufacturer
Marathon
Motor Frame
56
Motor HP
1 HP
Motor RPM
1725 RPM
Motor Rated Volts
200-2301460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
4.0-5.0/2.5 Amps
Motor Service Factor
1.5
Motor Sheave Make
Browning
Motor Sheave Model
1VL34
Motor Sheave Diam.
3-1/4 in.
Motor Sheave Bore
5/8 in.
Motor Operating Diameter 2-1/2 in.
Fan Sheave Make
Browning
Fan Sheave Model
AK49
Fan Sheave Diam.
4-3/4 in.
Fan Sheave Bore
3/4 in.
Number of Belts
1
Belt Size
AX26
Sheave Center Line
8-1/2 in.
U-03 / Supply Fan
Fan SP In Actual -0.31 in. we
Fan RPM Actual 1006 RPM
Fan SP Out Actual 0,19 in. we
Motor Volts 1 489 Volts
OA Damper Pos Actual 19 %
Motor Volts 2 490 Volts
RA Damper Pos Actual 81 %
Motor Votts 3 488 Volts
Unit External SP Design 1.0 in. we
Motor Amps 1 1.6 Amps
Unit External SP Actual 0.26 in. we
Motor Amps 2 1.5 Amps
Filter/Coil SP In -0.07 in. we
Motor Amps 3 1.6 Amps
Filter/Coil SP Out -0.31 in, we
(N)RTU-03 Supply Outlet Summary
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Faalmr
Maximum
Prelim
Reading
Maximum % Prelim
Final Deviation
% Final
DeeikMon
Outlet-01
110
N
24x24
320
;;9C,
317 124
99
Outlet-02
110
N
24x24
320
400
330 125
103
Outlet-03
110
N
24x24
320
461
322 144
101
Outlet-04
110
N
24x24
320
405
329 127
103
Outlet-05
110"may{
N
24x24
320
372
317 116
99
ll
ti
* Notes
L. H Finn and Associates
Final Report
Page 12 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (N)RTU-04
AREA:
DATE: 4/21 /2014
CONTACT: Dave Reichel
NE, BB
2389
Tested By: Wade Wilson
Test Date: April 16, 2014
Unit Manufacturer Trane
(N1RTU-04 / Supply Fan
Unit Model Number YSC060E4EHA1 ND001000
Motor Manufacturer Marathon
Unit Serial Number 140912475L
Motor Frame 56
Unit Discharge Vertical/Down
Motor HP 1 HP
(N)RTU-04 / Supply Fan
Motor RPM 1725 RPM
Fan Type Forward Curve
Motor Rated Volts 200-230/460 Volts
Fan Size 10"ID
Motor Phase 3
Fan Class 1
Motor Hertz 60 Hz
Fan Arrangement DWDI
Motor FL Amps 4.0-5.0/2.5Amps
Fan Discharge Vertical/Down
Motor Service Factor 1.5
(N)RTU-04 / Filter Bank
Filter Manufacturer Purolator
Filter Type Disposable
Filter Quantity 2
(N)RTU-04 / Supply Fan
Filter Size 20x3Ox2
Motor Sheave Make Browning
Motor Sheave Diam. 3-1/4 in.
Motor Sheave Bore 5/8 in.
Motor Operating Diameter 2 1/2 in.
(N)RTU-04 / Supply Fan
Fan Sheave Make Browning
Installed Thermal Internal
Fan Sheave Model AK44
Fan Sheave Diam. 4-1/4 in.
Fan Sheave Bore 3/4 in.
Number of Belts 1
Total CFM Design 2000 CFM
Belt Size AX26
Total CFM Actual 1999 CFM
Sheave Center Line 8-1/2 in.
Outside Air CFM Design 400 CFM
Test P�@SSUFBS
Outside Air CFM Actual 389 CFM
Return Air CFM Design 1600 CFM
Return Air CFM Actual 1610 CFM
Fan SP In Actual -0.40 in. we
(N1RTU-04 / Supply Fan
Fan SP Out Actual 0.20 in. we
Fan RPM Actual 1019 RPM
OA Damper Pos Actual 23 %
Motor Volts 1 490 Volts
RA Damper Pos Actual 77 %
Motor Volts 2 491 Volts
Unit External SP Design 1.0 in. we
Motor Volts 3 491 Volts
Unit External SP Actual 0.40 in. we
Motor Amps 1 1.5 Amps
Filter/Coil SP In -0.20 in. we
Motor Amps 2 1.4 Amps
Filter/Coil SP Out -0.40 in. we
Motor Amps 3 1 A Amps
(N)RTU-04 / Supply Fan
Fan TSP Actual 0.60 in. we
(N)RTU-04 Supply Outlet Summary
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
133
SWR
18x12
400
418
404
105
101
Outlet-02
133
SWR
18x12
400
618
396
155
99
Outlet-03
133
SWR
18xl2
400
496
397
124
99
Outlet-04
133
SWR
18x12
400
453
399
113
100
Outlet-05
133
SWR
1802
400
456
403
114
101
* Notes
L. H. Finn and Associates
Fina/Report Page 13 of 41
Lawrence H. Finn & Associates, Inc. Ni. B
2389
Fan Unit
PROJECT: F+W Media (Bldg #1) DATE: 4/21/2014
LOCATION: Fort Collins, CO CONTACT: Dave Reichel
SYSTEM/UNIT: TF-01
AREA:
Fan Manufacturer
Twin City Fan
Fan Model Number
T400
Fan Type
Forward Curve
Fan Size
6" ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Horizontal
Installed Thermal Internal
Total CFM Design
300 CFM
Total CFM Actual
325 CFM
Fan RPM Actual
Direct Drive RPM
Motor Volts 1
120 Volts
Motor Amps 1
1.0 Amps
SP In Actual
-0.07 in. we
SP Out Actual
0.09 in. we
Total SP Design
0.25 in. we
Total SP Actual
0.16 in. we
TF-01 Exhaust Inlet Summary
" Notes
Tested By: Josh Behrendsen
Test Date: April 16, 2014
Motor Manufacturer
Broan
Motor RPM
Direct Drive RPM
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
1.3 Amps
Motor Sheave Make WrectWnve�
L.N. Finn and Associates
Final Report
Page 29 of 41
• g / �{o0 9l8
.. r
Lawrence H. Finn & Associates, Inc.
11441 55 S. Elm Ave, Suite 220 — Eaton, CO 80615
2389 Phone (970) 454-5351 — Fax (970) 454-5391
PROJECT: F + W Media
Innovation Campus Bldg 1 & 2
ADDRESS: 4856 / 4868 Innovation Drive
Fort Collins, CO
The data presented in this report is an exact record of the system performance
and was obtained in accordance with NEBB Standard Procedures. Any
variances from design quantities which exceed NEBB tolerances are noted
throughout the report.
The air distribution systems have been tested & balanced and final adjustments
have been made in accordance with NEBB "Procedural Standards for Testing,
Adjusting, Balancing of Environmental Systems" and the project specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATER/21/14
The hydronic distribution systems have been tested & balanced and final
adjustments have been made in accordance with NEBB "Procedural Standards
for Testing, Adjusting, Balancing of Environmental Systems" and the project
specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATER/21/14
SUBMITTED & CERTIFIED BY
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
TAB SUPERVISOR: David C. Reichel
REG. NO.: 2389 SIGNATURE:
DATE: 4/21/14 CERTIFICATION EXPIRATION DATE: 3/31/2016
Lawrence He Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-04
AREA:
Unit Manufacturer
Carrier
Unit Model Number
48TFE009-M601AA
Unit Serial Number
0101G30445
Unit Discharge
Vertical/Down
U-04 / Supply Fan
Fan Type
Forward Curve
Fan Size
12"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
U-04 / Filter Bank
Filter Manufacturer
Koch
Filter Type
Pleated
Filter Quantity
4
Filter Size
16x20x2
(E)RTU-04 / Supply Fan
Installed Thermal Internal 77
Total CFM Design 3425 CFM
Total CFM Actual 3601 CFM
Outside Air CFM Design None Shown CFM
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Motor Service Factor
2389
Tested By: Joe Castanon
Test Date: April 15, 2014
GE
56HZ
1725 RPM
208-230/460 Volts
3
60 Hz
10.2/4.8 Amps
1.15
Motor Sheave Make
Browning
Motor Sheave Model
Adjustible
Motor Sheave Diam.
5-1/2 in.
Motor Sheave Bore
7/8 in.
Motor Operating Diameter 4-3/4 in.
Fan Sheave Make
Maurey
Fan Sheave Model
Fixed
Fan Sheave Diam.
8-1/2 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
A-53
Sheave Center Line
17-1/2 in.
Fan RPM Actual 919 RPM
Motor Volts 1 491 Volts
Fan SP In Actual -0.70 in. we
Motor Volts 2 491 Volts
Fan SP Out Actual 0.60 in. we
Motor Volts 3 491 Volts
Unit External SP Actual 0.85 in. we
Motor Amps 1 4.0 Amps
Filter/Coil SP In -0.25 in. we
Motor Amps 2 4.1 Amps
Filter/Coil SP Out -0.70 in. we
Motor Amps 3 4.0 Amps
(E)RTU-04 / Supply Fan
Fan TSP Actual 1.3 in, we
L.H. Finn and Associates
Final Report Page 4 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-04 (Cont.)
AREA:
(E)RTU-04 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
NNIP
2389
Tested By: Joe Castanon
Test Date: April 15, 2014
Ptlet-Ot
109
N
24x24
225
220
239
98
106
Outlet-02
109
N
24x24
225
203
238
90
106
Outlet-03
108
CD
24x24
225
353
235
157
104
Outlet-04
See Print
N
24x24
225
196
237
87
105
Outlet-05
107
CD
24x24
225
399
237
177
105
Outlet-06
106
CD
24x24
225
373
241
166
107
Outlet-07
See Print
N
24x24
225
188
235
84
104
Outlet-08
105
N
24x24
250
349
254
140
102
Outlet-09
105
N
24x24
250
175
251
70
100
Outlet-10
103
CD
24x24
225
327
241
145
107
Outlet-11
102
CD
24x24
225
207
242
92
108
Outlet-12
See Print
N
24x24
225
124
235
55
104
Outlet-13
101
CD
24x24
225
276
237
123
105
Outlet-14
100
R
24x24
225
283
239
126
106
Outlet-15
100
R
24x24
225
283
240
126
107
Notes
L. H Finn and Associates
Final Report Page 5 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-05
AREA:
Unit Manufacturer
Carrier
Unit Model Number
48TFDO06-6010A
Unit Serial Number
510OG24521
Unit Discharge
Vertical/Down
U-05 / Supply Fan
Fan Type
Forward Curve
Fan Size
8"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
U-05 I Filter Bank
Filter Manufacturer
Koch
Filter Type
Pleated
Filter Quantity
2
Filter Size
16x25x2
(E)RTU-05 / Supply Fan
Installed Thermal Internal
Total CFM Design 2000 CFM
Total CFM Actual 1977 CFM
Outside Air CFM Design Not Shown CFM
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Motor Service Factor
NJ101
2389
Tested By: Joe Castanon
Test Date: April 15, 2014
GE
56Y
1725 RPM
208-230/460 Volts
3
60 Hz
5.2/2.6 Amps
1.15
Motor Sheave Make
Browning
Motor Sheave Model
Adjustable
Motor Sheave Diam.
4 in.
Motor Sheave Bore
5/8 in.
Motor Operating Diameter 3-3/4 in.
Fan Sheave Make
Maurey
Fan Sheave Model
AC58
Fan Sheave Diam.
5-3/4 in.
Fan Sheave Bore
5/8 in.
Number of Belts
1
Belt Size
A40
Sheave Center Line
13-1/4 in.
Fan RPM Actual 1177 RPM
Motor Volts 1 490 Volts
Fan SP In Actual -0.50 in. we
Motor Volts 2 491 Volts
Fan SP Out Actual 0.40 in. we
Motor Volts 3 490 Volts
Unit External SP Actual 0.55 in. we
Motor Amps 1 1.6 Amps
Filter/Coil SP In -0.15 in. we
Motor Amps 2 1.7 Amps
Filter/Coil SP Out -0.50 in. we
Motor Amps 3 1.6 Amps
(E)RTU-05 / Supply Fan
Fan TSP Actual 0.90 in. we
L.H.. Finn and Associates
Fina/Report Page 6 of 41
r
Lawrence H. Finn & Associates, Inc. NE: BB
2389
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-05 (Cont)
AREA:
(E)RTU-05 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
Tested By: Joe Castanon
Test Date: April 15, 2014
Outlet-01
See Print
N
24x24
225
229
227
102
101
Outlet-02
121
N
24x24
150
151
153
101
102
Outlet-03
122
N
24x24
50
81
52
162
104
Outlet-04
116
CD
24x24
225
226
224
100
100
Outlet-05
115
CD
24x24
225
220
222
98
99
Outlet-06
114
CD
24x24
225
200
223
89
99
Outlet-07
113
CD
24x24
225
199
219
88
97
Outlet-08
112
CD
24x24
225
254
224
113
100
Outlet-09
111
R
24x24
225
f 199
216
88
96
Outlet-10
111
R
24x24
225
230
217
102
96
* Notes
L.H. Finn and Associates
Final Report
Page 7 of 41
Lawrence He Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-06
AREA:
Unit Manufacturer
Carder
Unit Model Number
48TFDO12-601QA
Unit Serial Number
510OG34025
Unit Discharge
Vertical/Down
J-06 / Supply Fan
Fan Type
Forward Curve
Fan Size
12"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
Filter Manufacturer
Koch
Filter Manufacturer
Koch
Filter Type
Pleated
Filter Type
Pleated
Filter Quantity
4
Filter Quantity
4
Filter Size
20x2Ox2
Filter Size
20x2Ox2
(E)RTU-06 / Supply Fan
Installed Thermal Internal
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Motor Service Factor
r
NE BB
2389
Tested By: Joe Castanon
Test Date: April 16, 2014
GE
56Y
1725 RPM
208-230/460 Volts
3
60 Hz
7.5/3.4 Amps
1.15
Motor Sheave Make
Browning
Motor Sheave Model
Adjustable
Motor Sheave Diam.
4 3/4 in.
Motor Sheave Bore
7/8 in.
Motor Operating Diameter 4 1/4 in.
Fan Sheave Make
Browning
Fan Sheave Model
Fixed
Fan Sheave Diam.
7 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
A51
Sheave Center Line
17 1/2 in.
Total CFM Design 4000 CFM
Total CFM Actual 4261 CFM
Fan SP In Actual -1.20 in. we
Outside Air CFM Design None Shown CFM
Fan SP Out Actual 0.90 in. we
U-06 / Supply Fan
Unit External SP Actual 1.55 in. we
Fan RPM Actual 988 RPM
Fiter/Coil SP In -0.65 in. we
Motor Volts 1 491 Volts
Filter/Coil SP Out -1.20 in. we
Motor Volts 2 490 Volts
IEEIRTU-06 / Supply Fan
Motor Volts 3 491 Volts
Fan TSP Actual 2.10 in. we
Motor Amps 1 5.4 Amps
Motor Amps 2 5.2 Amps
Motor Amps 3 5.2 Amps
L. H. Finn and Associates
Final Report
Page 8 of 41
Lawrence H. Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-06 (Cont.)
AREA:
(E)RTU-06 Supply Outlet Summary
DATE: 4/21 /2014
CONTACT: Dave Reichel
NEE BB
2389
Tested By: Joe Castanon
Test Date: April 16, 2014
Outlet-01
125
CD
24x24
200
471
213
236
107
Outlet-02
123
N
24x24
150
137
161
91
107
Outlet-03
123
N
24x24
150
132
159
88
106
Outlet-04
123
N
24x24
150
114
160
76
107
Outlet-05
123
N
24x24
150
152
158
101
105
Outlet-06
123
N
24x24
150
206
162
137
108
Outlet-07
123
N
24x24
150
114
158
76
105
Outlet-08
123
N
24x24
150
179
160
119
107
Outlet-09
123
N
24x24
150
144
161
96
107
Outlet-10
123
N
24x24
150
243
158
162
105
Outlet-11
123
N
24x24
150
135
160
90
107
Outlet-12
123
N
24x24
150
159
158
106
105
Outlet-13
123
N
24x24
150
117
158
78
105
Outlet-14
123
N
24x24
150
177
159
118
106
Outlet-15
123
N
24x24
150
153
160
102
107
Outlet-16
123
N
24x24
150
244
161
163
107
Outlet-17
123
N
24x24
150
112
160
75
107
Outlet-18
126
CD
24x24
100
192
107
192
107
Outlet-19
127
CD
24x24
100
227
105
227
105
Outlet-20
128
CD
24x24
100
220
107
220
107
Outlet-21
129
CD
24x24
100
179
107
179
107
Outlet-22
130
CD
24x24
100
181
108
181
108
Outlet-23
130
N
24x24
150
141
159
94
106
Outlet-24
130
N
24x24
150
194
162
129
108
Outlet-25
130
N
24x24
150
160
161
107
107
Outlet-26
130
N
24x24
150
154
161
103
107
Outlet-27
130
N
24x24
150
260
159
173
106
Outlet-28
130
N
24x24
150
52
159
35
106
* Notes
L. H. Finn and Associates
Fina/Report Page 9 of 41
Lawrence He Finn & Associates, Inc. NE BB
2389
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (E)RTU-07
AREA:
Unit Manufacturer
Carrier
Unit Model Number
48TFD005-M-601AA
Unit Serial Number
0101 G20477
Unit Discharge
Vertical/Down
J-07 / Supply Fan
Fan Type
Forward Curve
Fan Size
9"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
J-07 / Filter Bank
Fitter Manufacturer
Koch
Filter Type
Pleated
Fiker Quantity
2
Fiker Size
16x25x2
(E)RTU-07 / Supply Fan
Installed Thermal Internal
Total CFM Design 1600 CFM
Total CFM Actual 1674 CFM
Outside Air CFM Design None Shown CFM
DATE: 4/21 /2014
CONTACT: Dave Reichel
Tested By: Wade Wilson
Test Date: April 16, 2014
Motor Manufacturer
GE
Motor Frame
56Y
Motor RPM
1725 RPM
Motor Rated Volts
208-230/460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
5.2/2.6 Amps
Motor Service Factor
1.15
Motor Sheave Make
Browning
Motor Sheave Model
Adjustable
Motor Sheave Diam.
4 in.
Motor Sheave Bore
5/8 in.
Motor Operating Diameter 3 in.
Fan Sheave Make
Maurey
Fan Sheave Diam.
4 3/4 in.
Fan Sheave Bore
5/8 in.
Number of Belts
1
Belt Size
A39
Sheave Center Line
14 in.
Fan RPM Actual 1092 RPM
Fan SP In Actual -0.5 in. we
Motor Volts 1 491 Volts
Fan SP Out Actual 0.9 in. we
Motor Volts 2 490 Volts
External SP In Actual -0.25 in. we
Motor Volts 3 490 Volts
External SP Out Actual 0.9 in. we
Motor Amps 1 1.5 Amps
Unit External SP Actual 1.15 in. we
Motor Amps 2 1.6 Amps
Fitter/Coil SP In -0.25 in. we
Motor Amps 3 1.6 Amps
Fitter/Coil SP Out -0.5 in. we
(E)RTU-07 Supply Outlet Summary
Outlet-01
134
N
24x24
300
359
323
120
108
Outlet-02
132
N
24x24
225
378
233
168
104
Outlet-03
132
N
24x24
225
308
231
137
103
Outlet-04
132
N
24x24
225
283
230
126
102
Outlet-05
132
N
24x24
225
322
232
143
103
Outlet-06
135
N
24x24
200
279
213
140
107
Outlet-07
135
N
24x24
200
210
212
105
106
ss 11
rode
.i -"
✓ .....:..
r y
�, ,_.,._
y
...,,. :..
..
* Notes
L. H Finn and Associates
Final Report
Page 10 of 41
Lawrence He Finn & Associates, Inc.
Roof Top Unit
PROJECT: F+W Media (Bldg #1)
LOCATION: Fort Collins, CO
SYSTEM/UNIT: (N)RTU-02
AREA:
Unit Manufacturer
Trane
Unit Model Number
YSC036E4EHAOOC8
Unit Serial Number
140912391 L
Unit Discharge
Vertical/Down
U-02 / Supply Fan
Fan Type
Forward Curve
Fan Size
10"ID
Fan Class
1
Fan Arrangement
DWDI
Fan Discharge
Vertical/Down
U-02 / Filter Bank
Filter Manufacturer
Purolator
Filter Type
Disposable
Filter Quantity
2
Filter Size
20x3Ox2
I�
(N)RTU-021 Supply Fan
Installed Thermal Internal
Total CFM Design
1200 CFM
Total CFM Actual
1290 CFM
Outside Air CFM Design
240 CFM
Outside Air CFM Actual
242 CFM
Return Air CFM Design
960 CFM
Return Air CFM Actual
1048 CFM
DATE: 4/21 /2014
CONTACT: Dave Reichel
Motor Manufacturer
Motor Frame
Motor HP
Motor RPM
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
Motor Service Factor
NE BB
2389
Tested By: Wade Wilson
Test Date: April 16, 2014
Marathon
56
1 HP
1725 RPM
200-230/460 Volts
3
60 Hz
4.0-5.0/2.5 Amps
1.5
Motor Sheave Make
Browning
Motor Sheave Model
1 VL34
Motor Sheave Diam.
3 1 /4 in.
Motor Sheave Bore
5/8 in.
Motor Operating Diameter 2 1/2 in.
Fan Sheave Make
Browning
Fan Sheave Model
AK51
Fan Sheave Diam.
5 in.
Fan Sheave Bore
3/4 in.
Number of Belts
1
Belt Size
AX26
Sheave Center Line
8 in.
U-02 / Supply Fan
Fan SP In Actual -0.14 in. we
Fan RPM Actual 1033 RPM
Fan SP Out Actual 0.30 in. we
Motor Volts 1 491 Volts
OA Damper Pos Actual 22 %
Motor Volts 2 490 Volts
RA Damper Pos Actual 78 %
Motor Volts 3 491 Volts
Unit External SP Design 1.0 in. we
Motor Amps 1 1.6 Amps
Unit External SP Actual 0.38 in. we
Motor Amps 2 1.6 Amps
Filter/Coil SP In -0.08 in. we
Motor Amps 3 1.4 Amps
Filter/Coll SP Out -0.14 in. we
(N)RTU-02 Supply Outlet Summary
System I Unit
Area Served
Outlet
Type
Size LxW 10
AK
Factor
Maximum
Design
Pngm Maximum
RMdIpO ilmil
% Prelim
9"Wilmt
% F
Outlet-01
i i 9
N
24x24
250
287 262
115
105
Outlet-02
119
N
24x24
250
425 271
170
108
Outlet-03
119
N
24x24
250
424 265
170
106
Outlet-04
118
R
24x24
225
394 244
175
108
Outlet-05
118
R
24x24
225
310 248
138
110
* Notes
L. H. Finn and Associates
Final Report Page 11 of 41