HomeMy WebLinkAbout2720 Council Tree Ave - Special Inspections/Field Verification - 01/17/2012BALANCE REPORT
PROJECT.
SHAWERMIZER
2720 COUNCIL TREE AVE SPACE #312
FORT COLLINS, CO 80525
PREPARED FOR:
AIR COMFORT
REPORT ISSUE DATE:
JANUARY 17, 2012
ARI PROJECT NO.:
11513
PREPARED BY:
4;7AIR- RIGHT, INC. _-
747 Sheridan Unit 88
Lakewood, Colorado 80214
Phone: (303) 232-5145
Fax (303) 232-1238
e-mail: airright@aol.com
http.-IAvww.air-rightinc.com
N
(-1%-12-
(K7 AIR- RIGHT, INC.
PROJECT: SHAWERMIZER
AIR HANDLER UNIT DATA
MANUFACTURER
CAPTNE AIRE
MODEL
A3-D750-G18
SERIAL
1427994
FAN TYPE
FC
DESIGN CFM
6450 @ 1.0: ESP
MIN OSA
6,450
STARTER DATA
MANUFACTURER
ALLEN-BRADLEY
MODEL
193-K
SIZE/THERMAL NO.
ADJ
RANGE
5.5-7.5
SET AT (HZ)
6.41
REQ. THERMAL
PROVIDED
RATING (AMPS)
NA
AIRFLOW DATA
SUPPLY CFM
6,660
OSA CFM
6,660
RETURN CFM
NA
AIR APPARATUS
TEST REPORT
UNIT: MAU-1
MOTOR NAMEPLATE DATA
MANUFACTURER
W EG
HP
R.P.M.
5
1755
PHASE
FRAME
3
184T
S.F.
TYPE
1.15
-
VOLTS
AMPS
460
6.41
THERMALLY PROTECTED
YES
DRIVE DATA
MOTOR DRIVE
2VP42
MOTOR BORE
1-1/8"
FAN DRIVE
2BK66H
FAN BORE
H-1-3/16"
NO. BELTS & SIZE
2BX55
ROTATION
CORRECT
DRIVE CHANGE
TEST DATA
INITIAL
FINAL
FAN R.P.M.
870
VOLTAGE
483-483-484
AMPERAGE
5.8-6.1-6.0
-0.12" FILTER -0.32" HEART -0.66"
J
NOTES:
NAC
PAGE: 04
1
=A/R- R/GHT, �Nc. = AIR APPARATUS
�� TEST REPORT
PROJECT: SHAWERMIZER UNIT: (E)AHU-090
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER CARRIER MANUFACTURER GE
MODEL 40RMOORSBWIHC HP R.P.M. -L522.6 1725
SERIAL 0508U38784 PHASE FRAME 3 56Y
FAN TYPE FC S.F. TYPE 1.15 -
DESIGN CFM 3000 @ 0.7" ESP VOLTS AMPS 460 4.0
MIN OSA 750 THERMALLY PROTECTED YES
STARTER DATA DRIVE DATA
MANUFACTURER YASKAWA MOTOR DRIVE 1VL44
MODEL V1000 MOTOR BORE 5/8"
SIZE/THERMAL NO. VFD FAN DRIVE AK84
RANGE 0-60 HZ FAN BORE 1"
SET AT (H� 822 NO. BELTS &SIZE 1 A39
REQ. THERMAL NA ROTATION CORRECT
RATING (AMPS) NA DRIVE CHANGE NA
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 3,010 FAN R.P.M. 822
OSA CFM 760 VOLTAGE 487�85�88
EXHAUST CFM 2,550 AMPERAGE 1.5-1.6-1.6
-0.11" FILTER NAC COOL -0.42" � HEAT 0.13"
J
NOTES:
PAGE: 05
=AIR- R/GHT, mrc. = FAN TEST
�,� REPORT'
PROJECT: s�weR;,o�R
FAN NUMBER KEF-1 KEF-2
UNIT DATA UNIT DATA UNIT DATA
MANUFACTURER CAPIIVE AIRE CAPTNE AIRE
CUE-098-A-X RDUS-U2200CA RDUS-U2165CA
11775980906 1427994 1427994
DESIGN CFM 4200 @ 1.75" ESP 2250 @ 1.5" ESP
MOTOR DATA MOTOR DATA MOTOR DATA
MANUFACTURER WEG WEG
MOTOR HP RPM 2 1710 1.5 1720
PHASE TYPE 3 - 3 -
S.F. FRAME 1.15 48 1.15 56C
VOLTS AMPS 208-230/460 6.2-6.12/3.06 208-230/460 4.7-4.42/2.21
DRIVE DATA DRIVE DATA DRIVE DATA
MOTOR DRIVE BORE 2VP42 7/8" 1VL40 5/S"
FAN DRIVE BORE 26K50 LX1-7/16" 1AK39 1"
NO. BELTS SIZE 2 BX43 1 AXi2
DRNE CHANGE ROTATION - CORRECT - CORRECT
STARTER DATA STARTER DATA STARTER DATA
MFG. MODEL ALLEN-BRADLEY 193-K ALLEN-BRADLEY 193-K
SIZE RANGE ADJ 4.5-6.3 ADJ 3.5-4.8
SETAT(AMPS) REQTHERM 6.2 PROVIDED 4.7 PROVIDED
THERMAL PROTECTION BY STARTER BY STARTER
TEST DATA TEST DATA TEST pATA
CFM VOLTS 4300 207-207-207 2350 207-207-207
RPM AMPS 1135 5.1-5.2-5.6 1300 3.0-3.0-3.1
( 0 2 �/o � d I jo
NOTES: '
PAGE: 06
,. =A/R- R1GHT, �nrc. _= AI R T E RM I NAL
�'�r/
TEST REPORT
PROJECT: SHAWERMIZER SYSTEM: SUPPLY & EXHAUST
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SI� AK VEL CFM VEL CFM VEL CFM
(E)AHU-090 1 CD 24 X 24 100 105
2 CD 24 X 24 100 100
3 CD 24 X 24 100 95
4 CD 24 X 24 50 50
5 CD 24 X 24 350 355
6 CD 24 X24 325 335
7 CD 24 X24 325 330
8 CD 24 X24 325 325
9 CD 24 X 24 325 320
10 CD 24 X 24 500 490
11 CD 24 X 24 500 505
TOTAL 3000 3010
MUA-1 1 CD 24X24 375 385
2 CD 24 X 24 375 390
3 CD 24 X 24 460 475
4 CD 24 X 24 470 500
5 CD 24 X 24 470 485
6 CD 24 X 24 470 505
7 CD 24 X 24 470 500
8 Fi00D 150 X 18 3360 3470
TOTAL 6450 6710
KEF-1 1 HOOD 139X13.2 13.27 4200 324 4300
KEF-2 1 HOOD 43X13.75 4.11 1000 251 1030
KEF-2 1 HOOD 68X13.75 6.49 1250 203 1320
TO� ES: 2350
PAGE: 07