HomeMy WebLinkAbout2851 Exmoor Ln - Disclosures/Mechanical - 05/08/2014City of Fort Collins Residential Mechanical Systems Performance Report This form is a record of testing targets and results, with Pass/Fall outcomes. For Information on measurement tools and testing techniques, see the '.Residential New Construction Mechanical Systems Testing G uide." The guide and this form may be periodically updated; check the Building Services web site for the current version. This form must be completed and signed by an "Approved Agency," and submitted to Building Services as a requirement for receiving a C.O. Color key f k - , . Tar et 8 Measured value ' or` limit, to compare with PasaIF81Caution .Other data targetnrlimit> ��� Testing date(s) I 5- O - 1 "t ADCF = Air Density Correction Factor, based on tool, ADCF altitude(5000% air temperature throu gh tool Volumetric flow CFM 5000' = ADCF x Indicated flow CFM Local12. • •t Ventilationter Bath exhaust - Testing tech (initials A Flo Flow box _ _ Pltot tube duct traverse Air temp �/ , D p too — PassADCF ive flow hood _Other (note through tool (F lj Design Airflow Minimum Airflow Requirement Indicated Volumetric Exhaust Pickup Location (CFM (CFM 6000') 1+ Flow Flow Pass Fail 500011 Type of Operation (CFM) (CFM 6000') u501ntemiittent_ 20Continuous ? -= ,,r�am/� �`l. L ' 60 Intermittent '= 20 Continuous 9 75' c9L ❑- INk-4-� _ « 60 Intermittent -_ 20 Continuous; - 7..L1 i c� /,9 ❑ 60 Intermittent _ 20 Continuous; _ Q ❑ - 3 '60'Intennittent -_:20 Continuous- - 'El E31 - = 60 Intermittent^_ 20 Continuou'a. • , - 60 Intermittent 20 Continuous ❑_ - - _ i Testing.. i notes 1Kitchen exhaust N/A - hood does not vent to outside Testing tech (initials { I Oven fuel _G Electric Minimum airflow requirement (CFM 6000') + operation _ 106Infermt1tent _,26 Continuous !!! 'Measured airflow i Flo FlowboxFlowgridPitot ube traverse.. Tooi(ExterlortennInation —L Interior Exhaust illeduct_ t Air o gh Passive flow hood. � Flow rid Exhaust duet through ADCF too _ Powered flow hood Other (note below)' loeatio not OK) tool (F) I t Indicated flo - CFM Volumetric flo °r "` , " CFM 6000 i❑Pasa Q Fail 7] Testing . l notes _ Residential Mechanical Design Submittal V20140101 Page 1 • •Ventilation34 Systems other than sub -structural floor exhaust Testing tech (initials Code -minimum ventilation airflo T Design ventilation ' `p CFM 6000' CFM 5000' hs4on i (based on CFA and # of BR) airflo SystemItElan'ced IYtyponlyto CFM5000' Target ventilation airflow rang (cod120y. of desP�nflow' I Air Temp Measurement Method Tool Location Through ADCF I IndicatFlowed I VolFloo metric I Pass I Fail Total airflow 1�411A Passiveflow hoodexhaust w box _ Pilot tube traverseHO _ Flow collar _ Other (note below) Total _ N/A _ Passive flow hood - - - supply Flow box _ Pilot tube traverse, ❑ ❑ airflow -. Flow collar Other (note below) i When supply airflow is circulated by air handler fan, fan speed for measurement _.Heating, _Cooling `_ Continuous fan rlanced airflow in balanced s stems Average of measured CFM 5000' Target flow range �<z yy.��U'���� ` " '' Atoms--ti -.` CFM ((' t❑iPass fail supply+exhaustflo (average 6000' L:.. resting. -.. note Duct leakage data source _ Testing tech (initials): Energy rater (name, 6 company, testing date): House conditioned floor area em (Include full base ) - - Air temp sf through tool (F ADCF Maximum Allowed Duct Leakage Measured Duct Leakage Test Parameter and Conditions Normalized (CFM26 6000' 1100 sf) Absolute (CFM26 6000') Indicated (CFM26) Volumetric (CFM26 6000') System #1 stem #2 Leakage Type TimingAh Handler Passl ail I Pass ail Total leakage Rough -in eluded 4IIa} p riF - g: '. �`❑;. El Total leakage Rough -in Included - 6- Cl ❑l : ❑ ❑ Total leakage Complete Included 12 - �' .-❑ ❑ - ❑. Leakage Complete Included ..: $'.� '�. -- ❑ El ❑ ❑ Residential Mechanical Design Submittal V20140101 Page 2 Cooling For multiple sys ems, attach one page per system system # Which parts of house does it serve? Installed equipment (Be clear about which AC components are installed at time of testing) Testing tech (initials IManufacturer Model # Furnace or Boiler AC or Heat Pump Condenser AC or Hpa t Pump Coil 4scr�o�o - �G C Flits d Basic fiberglass Electrostatic 1 `. Type VBesic pleated Other: Thickness MERV LLL��bran Hl h�ffi6 leafed (Inches) (optional �111 " Static Cooling: Measured air flow through indoor coil Design cooling airflo=CFM 6000' . j (high stage Measured airflow I Teatino tech (Initials ie location SOP, )P) Testing tech (Initials) Target airflow Iimi (design +/-16%) �''� "s t '�� .Egg e- ,k ,�; CFM 6000' 014" no AC installed Flow grf t4- tool(gpll--�-�] El plate size 20 throw ADCF NSOP ( tool(FIE] i Measured airflow, no�CFM Indicated airtlo�CFM adJustmenUCOReCUO Measured AFx FRC TFSOP0 Flow Resistance Correction Facto Volumetric airfloCFM r❑Pass tl r Indicated AF x ADC 6000' Fail Heating: Gas manifold pressure (high stage) Testing tech (initials Manifold pressor �'. IwC Target manifold P a" 2"*to �z� +a IWC MeasuredIWC OEM spec @ 5000' limits (spec +/- 6%) . ?, „, • ,:. pressure Failn, ai Heating: Temperature rise Testing tech (initials " OEM temperature rise limits "', ` 2 to F IIII (high stage i " Sup p ,,Measured temps (F): ! — Return o Temp :> , YPasa Fail Caution: within 10F ❑ ,_„ ai ai ns ;gof top of range Residential Mechanical Design Submittal V20140101 Page 3 Testing tech (initials= Testing approach and targets F— r r&: No complete AC system '_❑NIA: House completed November -April (installing contractor responsible for testing In mmarher) ��V�7XV: Subcooling + SH check 'E]Noon-TXV: Superheat �E-OEM-specific: Approach ❑Other OEM -specific (documentation required) j Temperatures Condenser Non-TXV: Return Target 'PI ���IMP Target �° * � ' i (F): entering air temp apTarget air wet -bulb temp Superheata� subcoohn 4proach Subcooling Discharge �" Condenser Liqui Actual i� TXV Pass: Actual SC within +l- pressor c ? (PSI) saturation (SOW chart F lit F subcoolln s F 0—I !3 F of target SC, 2 F min temp (Cond T-Iiq line �u lnV Fail P0 Superheat Suction Eva orato P Suction Actual Non-TXV Pass: Actual SH P ressu PSI _• ( ) saturation ( a000 chart � F lin F su erhea F within +l- 6 F of target SH P (rr���ppp r9 temp p (Butt una T-evapNOn-TXV Fail TXV checks -❑Pass: Field4nstalled TXV installed in accordance with OEM ins tractions ❑Caution: Actual SH outside mfgr range Approach i ( Liquid IInF Actual approacF line T-condenser FJ1 "EIA roach Pass: Actual approach within +/-1 F of large t a t PP PP t9 approach temp (Liq ❑pproach Fail Testing note Register air flows I "I All registers are cut through finish materials and moving air - Pass Fail (Remainder of register air flow section under devel opment, not yet being enforced) Pressure balance Room Room -to -Core Measured (match names on plans, Include Pressure Drop Pressure basement if there is a door) Target Range (Pa) Drop (Pa) m e�. - -3 to +3. �r 5 -3fo+3 3 to +3 3fo+34,' 3to+3 3 to +3 f , .. e d V t 3=io+3 X Testing tech (initials l T_T n Residential Mechanical Design Submittal V20140101 Page 4 ,8. Combustion Safety V, bustio natura _ J=11ance safety testing t b — no pletedlfore v comb nation appliances Testing tech (initfa / Iiance Types table must be completed for every home ) i Annlianra_ tvnes Appliance inn NIA — ❑' Draft -hood (Natural -draft) .,: _.❑ Induced -draft JbilluLd:dDIAL ❑ Power- vent Direct- vent Powered sealed. combustion Electric , ❑.... Fumace#1 ❑. ❑ . Fumace#2 ❑- ;.. ❑ ❑- ❑ ❑. ❑ _ ❑Boiler#1 El El El El El El El ...Boiler#2 ❑ °- ❑,_.. . ... .❑ .. ... ._ ❑_. .:❑ ...... ...... ❑.. ,.. ❑.: :. Water heater#1 ❑- ❑ ❑ ❑ °. ::❑ ❑ Water heater#2 ❑ ❑.. _. ..❑.. _.. _ ❑ ❑ _. _ ❑,._.. _ ❑.. Fireplace #1 El El El El El El ET Fireplace #2 ❑ ❑ _ ❑ ❑ .❑ ❑ __... ❑,. i Other. EJ Worst -case depressurization performance Outdoor temperature=F GAZ pressure I BPI depressurization limit (Pa wrt outside) i Measured net CAZ depressurization (Pawn outside) OK (less negative) ( Caution (more negative) !Spillage �t BPI maximum limit (seconds d i Measured spillage duration (seconds Pass = duration not exceeding limit { ''Draft pressure t BPI limit (Pa wR CAZ, Measured (Pa wR CAZ s i Pass = pressure more negative than limit CO concentration In undiluted flue gas ? BPI maximum limit t i Measured CO Pass = CO level not exceeding limit Caution = CO level 26 to 100 ppm i Testing notes �g �, VOK ❑ OK ". ❑.;' Caution ❑- .❑•� Caution ❑ OK 'i'❑k` : Caution 60 , tr S Pass Fail _LJ 1pass LLJ lFail I L jPass I lFail x jFaii4 ❑ _ Pass �e❑ FairIf, 0: Pass �g tt�. sad❑p:. ❑ Pass INEAFall Residential Mechanical Design Submittal V20140101 Page 6 9. System'Gontrois .g � ➢ Testing tech System Controls Operating Per Desl n Intent Local exhaust (all fans) ❑- NIA ass 10 Fall Whole -house ventilation ❑ N/A ass ❑ Fall Sub -structural floor exhaust A ❑ Pass Fall Heating(all systems) ❑ N/A j0dipass I— Fail Cooling (all systems /A ; ❑ Pass Fall Technician #2 performing Inspection and testing doc umented on this report (Approved Agency) P-91I certify that the tests referenced above, In sections bearing my initials, were performed in accordance with protocols specified by the jCity of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. performance of the Installed mechanical Diaitallv signed k Dwayne Shamer Date:.2014.05.13 L-:7U -Ub-UU Residential Mechanical Design Submittal V20140101 Page 6