HomeMy WebLinkAbout3114 Bryce Dr - Disclosures/Blower Door Test - 05/05/2014BUILDING LEAKAGE TEST Date of Test: 05/05/2014 Technician: Doug Groff Test File: Meritage Blower Door Customer: Meritage Homes Building Address: 3114 Bryce Drive- Final Reports 7400 E Orchard Rd Fort Collins, CO 80525 Greenwood Village, Colorado 80111 Phone Test Results 1. Airflow at 50 Pascals: (50 Pa = 0.2 w.c.) 2. Leakage Areas: 3. Minneapolis Leakage Ratio: 4. Building Leakage Curve: 5. Test Settings: 1032 CFM (+/- 0.0 %) 1.75 ACH 0.33 CFM per ft2 floor area 0.15 CFM50 per ft2 surface area Flow Coefficient (C) = 851.6 ( +/- 0.6 % Exponent (n) = 0.049 ( +/- 0.002 ) Correlation Coefficient = 0.99846 Test Standard: = CGSB Test Mode: = Depressurization Equipment = Model 3 Minneapolis Blower Door Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 357.7 CFM 0.61 ACH 2. Estimated Design Infiltration Rate: Winter: 436.8 CFM 0.74 ACH Summer: 248.2 CFM 0.42 ACH 3. Recommended Whole Building Mechanical 0.0 CFM Ventilation Rate: (based on ASHRAE 62.2) Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 Date of Test: 05/05/2014 Test File: Meritage Blower Door Building Conditions Inside Temperature: 72 deg F Heating Fuel: Gas Outside Temperature: 75 deg F Heating Fuel Cost: # of Stories 2.0 Heating Efficiency: Heating Degree Days: 6020 Wind Shield: M Cooling Fuel Cost: # of Occupants Cooling SEER: Cooling Degree Days: 287 # of Bedrooms: 3.0 Volume: 35338 ft3 Ventilation Weather Factor: 0.87 Surface Area: 6726 ft2 Energy Climate Factor: 17.0 Floor Area: 3165 ft2 Design Winter Wind Speed: 9.0 mph Design Winter Temp Diff: 69 deg F Design Summer Wind Speed: 7.0 mph Design Summer Temp Diff: 16 deg F Comments GARAGE WRT HOUSE: 47.5 Pa @ 50 Pa BUILDING LEAKAGE TEST Page 3 Date of Test: 05/05/2014 Test File: Meritage Blower poor Data Points: Data Entered Manually Nominal Temperature Building Fan Pressure Nominal Adjusted Fan Baseline Pressure (Pa) (Pa) Flow Flow % Error Configuration Std Dev (Pa) -3.7 n/a +/- 0.00 -65.0 32.6 1040 1043 0.0 Ring A -60.0 32.3 1035 1038 -0.0 Ring A -55.0 32.0 1030 1033 -0.0 Ring A -50.0 31.7 1025 1028 -0.0 Ring A -45.0 31.4 1020 1023 0.0 Ring A BtiRGESS `""�`��`�'� ''y,oarc.tie /Aog�" r \ 1'�c ❑ f�Z �,^ �J�g C �� ���� �� �� ,�s _ ,.�.K�.,,:� t�. CON�TftLLTI05 'm'� �' '�� ., mx/ C�\SIiLTA\T$ :'i,�.� `!:1iY.�4�'f: :i�c�Cvw °'Ds',»iE�;F"� AIR LEAKAGE REPORT Date: May 05,2014 Rating No.: 0502201101 53 Buildirx3 Name: Meritage 3552 Full Rating Org.: Burgess Inc Owner's Name: Phone No.: 214-888-7260 Property: 3114 Bryce Drive Rater's Name: Robert Hutchinson Address: Fort Collins,CO 80525 Rater's No.: 7479033 Builder's Name: Meritage Homes � Weather Sde: Ft.Collins,CO Rating Type: Confirmed File Name: 3114 Bryce Dr.blg Rating Date: 5/5/14 Blower door test Whole House Infiltration Heating Cooling NaturalACH: 0.11 0.08 ACH @ 50 Pascals: 1.74 1.74 CFM @ 25 Pascals: 653 653 CFM @ 50 Pascals: 1025 1025 Eff.LeakageArea: [sq.in] 56.3 56.3 , SpecficLeakageArea: 0.00012 0.00012 ELA/100sfshell: [sq.in] 0.84 0.84 Duct Leakage Leakage to Outside Units Ducts Main Ducts Up CFM @ 25 Pascals: 0 0 CFM25 l CFMfan: 0.0000 0.0000 CFM25/CFA: 0.0000 0.0000 CFM per Std 152: N/A NIA CFM per Std 152/CFA: N/A N/A CFM @ 50 Pascals: 0 0 Eff.LeakageArea: [sq.in] 0.00 0.00 Thermai Efficiency: N/A N/A Total Duct Leakage Units CFM25/CFA CFM25/CFA Total Duct Leakage: 0.0600 0.0356 Ventilation Mechanical: AirCycler Sensible Recovery Eff.(%): 0.0 Total Recovery Eff.(%): 0.0 Rate(cfm): 121 Hours/Day: '122 Fan Watts: 150.0 Coo ling Ve ntilatio n: N atura I Ventilatio n ASHRAE 62.2-2010 Ventilation Requirements For this home to wmply withASHRAE Standard 622-2010 Ventila6on and Acceptable IndoorAir Qualily in Low-Rise Residential Buildings,a minimum of 62 cfm of inechanical ventifation must be provided continuously, 24 hours per day. ARernataey,an intermittently operating mechanical ventilation system may be used'rfthe ventilation rate is adjusted accordingly. For example,a 123 cfrn mechanical ventilation system wouki need to operate 12 hours per day,as long as the system operates to provide required average ventilation once each hour. REM/Rate-Residential Energy Analysis and Rating Software v14.4 This information does not constitute any warranty of energy cost or savings. OO 1985-2013Archi[ectural Energy Corporation,Boukler,Colorado.