Loading...
HomeMy WebLinkAbout2720 Council Tree Ave - Special Inspections/Field Verification - 03/21/2011COMcheck Software Version 3.8.1 Mechanical Compliance Certificate Q 7 a 0 COO A -la 'I / T A e e Pu c Y: L, f44� 90.1 (2007) Standard Section 1: Project Information Project Type: New Construction Project Title : Pablo's Pizza Construction Site: 4431 Corbett Dr. Fort Collins, CO Owner/Agent: Section 2: General Information Building Location (for weather data): Fort Collins, Colorado Climate Zone: 5b 81,01187 Designer/Contractor: Section 3: Mechanical Systems List uanti System Type & Description 2 FCU-1 & 2 (Single Zone) : Heating: 2 - Central Furnace, Electric, Capacity = 68 kBtu/h Cooling: 2 - Split System, Capacity = 60 kBtu/h, Efficiency = 13.00 SEER, Air -Cooled Condenser 1 MAU-1 (Single Zone) : Heating: 1 - Central Furnace, Gas, Capacity = 250 kBtu/h, Efficiency = 100.00% Ec 1 PWH-1: Gas Storage Water Heater, Capacity: 100 gallons, Input Rating: 199 Btu/h w/ Circulation Pump and Heat Trace Tape Installed, Efficiency: 95.00 % Et Section 4: Requirements Checklist Requirements Specific To: FCU-1 & 2 : 0 1. Equipment minimum efficiency: Split System: 13.0 SEER 0 2. Newly purchased equipment meets the efficiency requirements Requirements Specific To: MAU-1 : 0 1. Equipment minimum efficiency: Central Furnace (Gas): 80.0 % Ec Requirements Specific To: PWH-1 : Lj 1. Gas Storage Water Heater efficiency: 80.0 % Et (259 SL, kBtu/h) Lj 2. Hot water system sized per manufacturer's sizing guide Lj 3. All piping in circulating system insulated 4. All heat traced or externally heated piping insulated Lj 5. Hot water storage temperature adjustable down to 120°F or lower 6. Automatic time control of heat tapes and recirculating systems present 7. Controls will shut off operation of circulating pump between water heater/boiler and storage tanks within 5 minutes after end of heating cycle Generic Requirements: Must be met by all systems to which the requirement is applicable: 1. Load calculations per ASHRAE Fundamentals 0 2. Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2-hour occupant override, 10-hour backup 0 Exception: Continuously operating zones Ej 3. Hot water pipe insulation: 1 in. for pipes <=1.5 in. and 2 in. for pipes >1.5 in. Chilled water/refrigerant/brine pipe insulation: 1 in. for pipes <=1.5 in. and 1.5 in. for pipes >1.5 in. Project Title: Pablo's Pizza Report date: 03/21/11 Data filename: Y:\11-020-FRV-Pablos-Pizza\Correspondence\ComCheck-11-03-21.cck Page 1 of 6 LJ Exception: Where hoods are used to exhaust ventilation air that would otherwise exfiltrate or be exhausted by other fan systems. Exception: Certified grease extractor hoods that require a face velocity no >60 fpm. ❑ 19. Buildings with fume hood systems having an exhaust rate > 15,000 cfm has at least one of the following features: a) VAV hood exhaust and room supply systems capable of reducing exhaust and makeup air volume to 50% or less of design values. b) Direct makeup air supply equal to at least 75% of the exhaust rate, heated no warmer than 20F below room setpoint, cooled to no cooler than 3°F above room setpoint, no humidification added, and no simultaneous heating and cooling used for dehumidification control. c) Heat recovery systems to precondition makeup air from fume hood exhaust. Section 5: Compliance Statement Compliance Statement. The proposed mechanical design represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 3.8.1 and to comply with the mandatory requirements in the Requirements Checklist. Thomas Seaelhorst - P.E. 22 Mar 2011 Name - Title Signature Section 6: Post Construction Compliance Statement Date LJ HVAC record drawings of the actual installation and performance data for each equipment provided to the owner within 90 days after system acceptance. HVAC O&M documents for all mechanical equipment and system provided to the owner within 90 days after system acceptance. Written HVAC balancing report provided to the owner. The above post construction requirements have been completed. Principal Mechanical Designer -Name Signature CONING; / �� P✓e- 9 M d Date Project Title: Pablo's Pizza Report date: 03/21/11 Data filename: Y:\ii-020-FRV-Pablos-Pizza\Correspondence\ComCheck-11-03-21.cck Page 3 of 6 13//o�i8� 4. Service hot water piping, where required, must be insulated to 1/2 in. if pipe less than 1.5 in. nominal diameter. Larger pipe must be insulated to 1 in.. Pipe insulation will have a conductivity of less than 0.28 Btu.in/(h-ft2-°F). 5. Temperature controlling means must be provided to limit the maximum temperature of water delivered from lavatory faucets in public facility restrooms to 110°F. 6. Thermostats controlling both heating and cooling must be capable of maintaining a 50F deadband (a range of temperature where no heating or cooling is provided). Exception: Deadband capability is not required if the thermostat does not have automatic changeover capability between heating and cooling. Exception: Special occupancy or special applications where wide temperature ranges are not acceptable and are approved by the authority having jurisdiction. 7. Demand control ventilation (DCV) required for high design occupancy areas (>40 person/1000 ft2 in spaces >500 ft2) and served by systems with any one of 1) an air -side economizer, 2) automatic modulating control of the outdoor air damper, or 3) a design outdoor airflow greater than 3000 cfm. Exception: Systems with heat recovery. Exception: Multiple -zone systems without DDC of individual zones communicating with a central control panel. - Exception: Systems with a design outdoor airflow less than 1200 cfm. - Exception: Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm. 8. Where zone heating and cooling are controlled by separate zone thermostats, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) must be provided to prevent simultaneous heating and cooling to the zone. 9. Stair and elevator shaft vents must be equipped with motorized dampers capable of being automatically closed during normal building operation and interlocked to open as required by fire and smoke detection systems. All gravity outdoor air supply and exhaust hoods, vents, and ventilators must be equipped with motorized dampers that willautomatically shut when the spaces served are not in use. Exception: Ventilation systems serving unconditioned spaces. Exception: Gravity (non -motorized) dampers are acceptable in buildings less than three stories in height above grade. 10. Where a zone is served by a system(s) with both humidification and dehumidification capability, means (such as limit switches, mechanical stops, or software programming) must be provided to prevent simultaneous operation of humidification and dehumidification equipment. - Exception: Zones served by desiccant systems, used with direct evaporative cooling in series; Systems serving zones where specific humidity levels are required. 11. All freeze protection systems, including self-regulating heat tracing, must include automatic controls capable of shutting off the systems when outside air temperatures are above 40°F or when the conditions of the protected fluid will prevent freezing. Snow- and ice -melting systems must include automatic controls capable of shutting off the systems when the pavement temperature is above 50°F and no precipitation is falling, and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. 12. Duct and pipe insulation exposed to weather must be suitable for outdoor service; e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation must be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. Insulation covering chilled water piping, refrigerant suction piping, or cooling ducts located outside the conditioned space must include a vapor retardant located outside the insulation (unless the insulation is inherently vapor retardant), all penetrations and joints of which must be sealed. 13. Duct Sealing Requirements: a) Pressure sensitive tape used as the primary sealant is certified to comply with UL-181 A or UL-181 B, b) Longitudinal and transverse seams for ducts in unconditioned spaces, c) Longitudinal and transverse seams and duct wall penetrations for ducts outside the building, d) Transverse seams on buried ducts 14. Outdoor air supply and exhaust systems must have motorized dampers that automatically shut when the systems or spaces served are not in use. Dampers must be capable of automatically shutting off during preoccupancy building warm-up, cool -down, and setback, except when ventilation reduces energy costs (e.g., night purge) or when ventilation must be supplied to meet code requirements. Both outdoor air supply and exhaust air dampers must have a maximum leakage rate of 10(motorized)/20(non-motorized) cfm/ft2 at 1.0 in. w.g. when tested in accordance with AMCA Standard 500. Exception: Gravity (non -motorized) dampers are acceptable in buildings less than three stories in height. Exception: Systems with a design outside air intake or exhaust capacity of 300 cfm (140 Us) or less. 15. All supply and return ducts and plenum installed as part of an HVAC air distribution system must be thermally insulated: R-6 for supply air ducts located outside the building, in ventilated attics and in unvented attic above insulated ceiling, R-1.9 for supply air ducts in unvented attic with roof insulation, R-3.5 for supply air duct insulation in unconditioned and underground spaces, R-3.5 for return air ducts located outside the building, in ventilated attics and in urivented attic above insulated ceiling. 16. Where humidistatic controls are provided, such controls must prevent reheating, mixing of hot and cold air streams, or other means of simultaneous heating and cooling of the same air stream. Exception: Capability to first reduce flow rate. Exception: Cooling capacity <80 kBtu/h and capability to unload cooling equipment. Exception: Cooling capacity <40 kBtu/h. Project Title: Pablo's Pizza Report date: 03/21/11 Data filename: Y:\11-020-FRV-Pablos-Pizza\Correspondence\ComCheck-11-03-21.cck Page 5 of 6