HomeMy WebLinkAbout417 W Magnolia St - Correspondence/Addition or Alteration - 03/10/2011j) Q M �l Paige 1 of 1 Russell Hovland From: Russell Hovland Sent: Thursday, March 10, 2011 5:01 PM To: 'Chris Freeland' Cc: Mike Gebo; 'Carie Dann'; 'Ron Gonzales'; Joe Jaramillo; Lisa Schoenfeld; Steve Seefeld Subject: RE: New West options - Plans - final.pdf Chris, Regarding the Lincoln Center addition project, Mike Gebo and PFA have reviewed this request to not sprinkle 2 existing areas in the Lincoln Center and below is the response. I . The installation of a 2-hour fire -wall separating the existing non -sprinkled office area from the remainder of the building is approved as this meets current code and the office area is within allowable area per code. 2. The request to not fire -sprinkle the mezzanine level storage area is denied and this area must be fully sprinkled. Even with a 2-hour fire -barrier separation this room is still part of the west building and this west half must be sprinkled for allowable area and to allow the additions. 3. Please contact PFA to inquire if they need any sprinkler plan revisions submitted. Russ Hovland Plans Examiner I d 2 2 7 Building Services City of Fort Collins 970-416-2341 From: Chris freeland [mailto:cfreeland@aller-lingle-massey.com] Sent: Monday, March 07, 2011 11:04 AM To: Russell Hovland Subject: New West options - Plans - final.pdf Russ Here are the drawings for the rated wall we had discussed. Chris Chris Freeland, AIA LEED AP cfreeland@aIler-tingle-massey.com Aller • Lingle • Massey Architects 712 Whalers Way Building B, Suite 100 Fort Collins, CO 80525 (970) 223 - 1820 www.aller-lingle-massey.com 03/11/2011