Loading...
HomeMy WebLinkAbout1108 Bateleur Ln - Disclosures/Air Sealing - 12/14/2010DUCT LEAKAGE TEST Date of Test: 12-13-10 Technician: Paul Higman Test File: Gary Hooley 1108 Bateleur Ln Customer: Gary Hooley Heating and Air Building Address: 1108 Bateleur Ln 1314 Webster Ave Fort Collins, CO 80521 Fort Collins, CO 80524 Phone: 970-493-3272 Fax: Test Results 1. Measured Duct Leakage: 281.4 CFM / 53.1 sq. in.(+/-18178614382971749000000000000000 2. Duct Leakage as a Percent of System Airflow: 20.1 % 3. Duct Leakage as a Percent of Building Floor Area: 11.7 % 4. Leakage Split: Supply Side: Return Side: 5. Duct Leakage Curve: Flow Coefficient (C): 40.8 Exponent (n): 0.600 (Assumed) 6 Test Settings: Test Mode: Pressurization Test Pressure: 25.0 Pa Equipment: Series B Minneapolis Duct Blaster Test Type: Total Leakage (Duct Blaster Only) Building and System Parameters: Floor Area: 2410 sq. ft. System Airflow: 1400 CFM Supply Leakage Split: % Return Leakage Split: % Average Supply Operating Pressure: Pa Average Return Operating Pressure: Pa Supply Leakage Penalty: Return Leakage Penalty: Percentage of Measured Leakage Connected to Outside: % (0.0 CFM) . � �� �9.3 DUCT LEAKAGE TEST Page 2 Date of Test: 12-13-10 Test File: Gary Hooley 1108 Bateleur Ln Data Points -Data Entered Manually: � Duct Fan Fan Flow Fan Pressure{Pa) Pressure(Pa) (CFM) % Error Configuration -0.1 n/a 25.0 46.4 280 0.0 Ring 1 0.5 n/a Comments