HomeMy WebLinkAbout1108 Bateleur Ln - Disclosures/Air Sealing - 12/14/2010DUCT LEAKAGE TEST
Date of Test: 12-13-10 Technician: Paul Higman
Test File: Gary Hooley 1108 Bateleur Ln
Customer: Gary Hooley Heating and Air Building Address: 1108 Bateleur Ln
1314 Webster Ave Fort Collins, CO 80521
Fort Collins, CO 80524
Phone: 970-493-3272
Fax:
Test Results
1.
Measured Duct Leakage:
281.4 CFM / 53.1 sq. in.(+/-18178614382971749000000000000000
2.
Duct Leakage as a Percent of System Airflow:
20.1 %
3.
Duct Leakage as a Percent of Building Floor Area:
11.7 %
4.
Leakage Split: Supply Side:
Return Side:
5.
Duct Leakage Curve: Flow Coefficient (C):
40.8
Exponent (n):
0.600 (Assumed)
6
Test Settings: Test Mode:
Pressurization
Test Pressure:
25.0 Pa
Equipment:
Series B Minneapolis Duct Blaster
Test Type:
Total Leakage
(Duct Blaster Only)
Building and System Parameters:
Floor Area: 2410 sq. ft.
System Airflow: 1400 CFM
Supply Leakage Split: %
Return Leakage Split: %
Average Supply Operating Pressure: Pa
Average Return Operating Pressure: Pa
Supply Leakage Penalty:
Return Leakage Penalty:
Percentage of Measured Leakage Connected to Outside: % (0.0 CFM)
. � �� �9.3
DUCT LEAKAGE TEST Page 2
Date of Test: 12-13-10 Test File: Gary Hooley 1108 Bateleur Ln
Data Points -Data Entered Manually: �
Duct Fan Fan Flow Fan
Pressure{Pa) Pressure(Pa) (CFM) % Error Configuration
-0.1 n/a
25.0 46.4 280 0.0 Ring 1
0.5 n/a