Loading...
HomeMy WebLinkAbout508 W Trilby Rd - Special Inspections/Engineering - 04/07/2010CSE Consultants 4710 S College Ave Ft. Collins CO 80525 phtfax (970) 282 8005 e mail rllcse@gwestoffice net Field Report Field Report No 1 Project Good Samaritan Society Facade Renovation 508 W Trilby Road Fort Collins Colorado Project No C9045 7 Architect Belford Watkins Group LLC Contractor Holsinger Drywall Date April 2010 Time 10 05 am Weather clear 44 degrees Observations and comments are as follows 1 The light gage steel framing for the cornice feature at the perimeter of the roof level is in progress The light gage steel framing is near completion at the South Elevation between the South Entry and the southwest comer of the building, and at the southern half of the West Elevation Refer to Addendum No 1 dated February 4 2010 regarding framing requirements 2 The 3 5/8 depth steel studs that are being used have 1 1/4 width flanges instead of the specified 1 5/8 width flanges and appear to be 20 gage Cemco Viper Studs We have reviewed the steel studs used and they are acceptable structurally 3 The light gage steel framing has been installed somewhat differently than the Addendum No 1 drawings In general the vertical stud was coped at the top and the vertical and horizontal studs have been connected with 4 to 5 # 10 Tek screws An angle will be required at the intersection of the vertical and horizontal studs to accommodate the roof sheathing 6 on center screw attachment requirements Refer to the attached sketch regarding the facade framing 4 The comer framing is being installed somewhat differently than the Drawings and is acceptable 5 The top clip angle at the vertical stud appears to be installed per the drawings 6 At the L3x3 at the bottom of the vertical stud the angle is currently attached to the existing brick with the Kwik Con II (Tapcon style) screws at a spacing of approximately 16 to 24 inches add additional screws so that the maximum spacing is 12 per the Drawings CSE Consultants Ron L Lindburg P E TYPICAL ROOF SHEATHING 15/32 TREATED PLYWOOD w/ PANEL IDENTIFICATION INDEX = 32/16 SCREW w/ #10 SELF DRILLING SCREWS SPACED ® 6 AT PERIMETER k ALL SUPPORTED PANEL EDGES AND 0 12 IN FIELD OF PANELS SEE ARCH FOR FASCIA AND COPING CONT 8 x 22 go FURRING CHANNEL CONTINUOUS L2x2x 20 GAGE COPE VERT do CONNECT w/ (4) #10 TEKS HILT] i, 0 x 2; KWIK-CON-II ® 12 (E) ROOF JOISTS (E) 6-2-4 MASONRY WALL 6 CMU GROUTED SOLID AT TOP OF WALL do BRICK VENEER E Cons1uUants 4710 S College Ave Fort Collins CO 80525 Ph 970-282-8005 Fax 970-282-8005 e-mail rllcse®gwestoffice net CSE Project No C9045-7 5 CONT 18 x 22 go STUD CLIP ANGLE 12 x 11 x 0-5 minimum x 16 gage AT EACH STUD w/ (2) HILT] 16 0 x 14 KWIK-CON-II ANCHORS AT BRICK AND (3) #10 SCREWS AT STUD WALL do SOFFIT SHEATHING SEE ARCHITECTURAL 30 x 15 x 20 gage (33 mils) FRAMING VERTICAL, HORIZONTAL & BRACING ®24 SEE ARCH FOR DIMENSIONS CONTINUOUS L3x3x 20 gage ANGLE w/ J10 SELF DRILLING SCREW ® 16 ANGLE TO BOTTOM TRACK ATTACH L3x3 w/ HILTI � 0 x 1 J KWIK-0ON-lI 0 12 TYPICAL FACADE FRAMING S2O ; = 1-0 GOOD SAMARITAN SOCIETY FORT COLLINS VILLAGE FACADE RENOVATION 508 W TRIL9Y ROAD APRIL 7 2010 FIELD REPORT No 1