Loading...
HomeMy WebLinkAbout2720 Council Tree Ave - Special Inspections/Field Verification - 07/20/2011po 119?- Q7a C) C a(j " c ; l FORT COLLINSMIDWEST INC. TA e e- /AZ) 3818 PLATTE CT. FORT COLLINS, CO. 80526 PHONE (970) 223-5421 FAX (970) 225-2814 TESTING, ADJUSTING &! BALANCING OF H.V.A.C. & HYDRONIC SYSTEMS GENERAL INFORMATION 'PROJECT LOCATION ARCHITECT ' MECHANICAL ENGINEER MECHANICAL CONTRACTOR 'BALANCING TECHNICIAN DATE /4 rD PABLO'S PIZZA FORT COLLINS, COLORADO . INTEGRATED MECHANICAL, LLC GARY HOOLEY HEATING & AIR CONDITIONING WILLIAM C. HARRISON JULY 2011 (REVISED) ol INSTRUMENTS USED ' VELGRID SHORTRIDGE AIRDATA MULTIMETER FLOW HOOD SHORTRIDGE AIRDATA MULTIMETER 'ANEMOMETER SPEED INDICATOR SHIMPO DIGITAL TACHOMETER DT205B AMMETER FLUKE 36 TRUE RMS 'VOLTMETER FLUKE 36 TRUE RMS POWER HARMONICS ANALYZER DIGITAL MICROMANOMETER SHORTRIDGE AIRDATA MULTIMETER ' PRESSURE GAGE PRESSURE GAGE -DIFFERENTIAL ULTRASONIC FLOW METER THERMOMETERS IAQ METER CO2 & CO 1 PROJECT ALTITUDE 5000' ' SHORTRIDGE BAROMETRIC CORRECTION IS AUTOMATIC. WILLIAM C. HARRISON IS A MEMBER OF THE ASSOCIATION OF ENERGY ENGINEERS, AND IS A CERTIFIED TESTING, ADJUSTING AND BALANCING PROFESSIONAL. 18P A�� FORT COLLINS/MIDWEST, INC. RECAP SHEET o�%;,5 61%7el lY'ee A-G/ee PROJECT PABLO'S PIZZA OPENING TYPE SUPPLY FCU-1 SUPPLY FCU-2 TOTAL SUPPLY MAU-1 SUPPLY FCU-1 MIN. O.S.A. SUPPLY FCU-2 MIN. O.S.A. TOTAL O.S.A. EXHAUST EF-1 EXHAUST MAIN BUILDING EXHAUST TOTAL BUILDING PRESSURE 0.001 REQ'D CFM 2220 2020 4240 1400 500 500 2400 2000 150 2150 FINAL CFM 2326 1991 4317 1427 507 522 2456 1944 184 2128 REMARKS REVISED REVISED REVISED