HomeMy WebLinkAbout2720 Council Tree Ave - Special Inspections/Field Verification - 07/20/2011po 119?-
Q7a C) C
a(j " c ; l
FORT COLLINSMIDWEST INC. TA e e- /AZ)
3818 PLATTE CT. FORT COLLINS, CO. 80526
PHONE (970) 223-5421 FAX (970) 225-2814
TESTING, ADJUSTING &! BALANCING OF H.V.A.C. & HYDRONIC SYSTEMS
GENERAL INFORMATION
'PROJECT
LOCATION
ARCHITECT
' MECHANICAL ENGINEER
MECHANICAL CONTRACTOR
'BALANCING TECHNICIAN
DATE
/4 rD
PABLO'S PIZZA
FORT COLLINS, COLORADO .
INTEGRATED MECHANICAL, LLC
GARY HOOLEY HEATING & AIR CONDITIONING
WILLIAM C. HARRISON
JULY 2011 (REVISED)
ol
INSTRUMENTS USED
' VELGRID
SHORTRIDGE AIRDATA MULTIMETER
FLOW HOOD
SHORTRIDGE AIRDATA MULTIMETER
'ANEMOMETER
SPEED INDICATOR
SHIMPO DIGITAL TACHOMETER DT205B
AMMETER
FLUKE 36 TRUE RMS
'VOLTMETER
FLUKE 36 TRUE RMS
POWER HARMONICS ANALYZER
DIGITAL MICROMANOMETER
SHORTRIDGE AIRDATA MULTIMETER
' PRESSURE GAGE
PRESSURE GAGE -DIFFERENTIAL
ULTRASONIC FLOW METER
THERMOMETERS
IAQ METER CO2 & CO
1
PROJECT ALTITUDE 5000'
' SHORTRIDGE BAROMETRIC CORRECTION IS AUTOMATIC.
WILLIAM C. HARRISON IS A MEMBER OF THE ASSOCIATION OF ENERGY ENGINEERS,
AND IS A CERTIFIED TESTING, ADJUSTING AND BALANCING PROFESSIONAL.
18P A��
FORT COLLINS/MIDWEST, INC.
RECAP SHEET o�%;,5 61%7el lY'ee A-G/ee
PROJECT PABLO'S PIZZA
OPENING TYPE
SUPPLY
FCU-1
SUPPLY
FCU-2
TOTAL
SUPPLY
MAU-1
SUPPLY
FCU-1 MIN. O.S.A.
SUPPLY
FCU-2 MIN. O.S.A.
TOTAL O.S.A.
EXHAUST
EF-1
EXHAUST MAIN BUILDING EXHAUST
TOTAL
BUILDING PRESSURE 0.001
REQ'D
CFM
2220
2020
4240
1400
500
500
2400
2000
150
2150
FINAL
CFM
2326
1991
4317
1427
507
522
2456
1944
184
2128
REMARKS
REVISED
REVISED
REVISED