HomeMy WebLinkAbout833 Snowy Plain Rd - Special Inspections/Engineering - 03/10/2010Irerracon
March 10 2010
Shadow Creek Homes
2861 W 120th Avenue Suite 240
Westminster Colorado 80234
Attn Mr Toby Terhune
Re Exterior Perimeter Drain Observation
Provincetowne Residential Development
833 Snowy Plain Road — Lot 6 Block 4
Fort Collins Colorado
Terracon Project No 20075058
A representative of Terracon Consultants Inc (Terracon) observed the Installed perimeter drain at
the subject site on February 22 2010 The purpose of these services was to
Observe that properly sized pipe and gravel had been placed as recommended
Observe that the perimeter drain system had been placed at the locations
recommended in the Geotechnical Engineering Report Terracon Consultants Inc
Project No 20075058
Confirm that the perimeter drain system had been sloped to a sump pit for discharge
Based upon our limited on site observations the observed drain appeared to have been
constructed in general accordance with the provided plans and the referenced geotechnical
engineering report It should be noted that our observation services were performed on an as
requested basis and only when requested by the above listed client or their designated
representative We offer no opinion regarding materials and/or construction not observed by
Te, racon representatives This letter is provided solely for the benefit for the above listed client
and does not impact in any way the rights and obligations of third parties including contractors
and subcontractors who may have provided the materials and/or construction services tested or
observed
Sincerely �p0 REG/S�
Terracon Consultants F
v cg C
v
' 42184
?OO 3/10/10
Joels C Malama P E /ONAL���`
Department Manager/ Geotechnica ervice!
Copies to Addressee (2)
Mike Walker CET
Manager/Construction Services
Terracon Consultants Inc 301 North Howes Fort Collins Colorado 80521
P 19701 484 0359 F 19701 484 0454 terracon corn
Irerracon
February 22 2010
Shadow Creek Homes
2861 W 1200 Avenue Suite 240
Westminster Colorado 80234
Attn Mr Toby Terhune
Re Foundation Footing Sizes Wall Steel and CEE Observations
Provincetowne Residential Development
833 Snowy Plain Road — Lot 6 Block 4
Fort Collins Colorado
Terracon Project No 20075068
Dear Mr Terhune
A representative from Terracon observed the interior and exterior foundation footing sizes and
wall steel reinforcement including the concrete encased electrode (CEE) for the above
referenced lot on February 10 and February 15 2010 as requested
Based upon our limited on site observations the foundations were constructed and the
observed steel appeared to have been placed in general accordance with the provided plans
and specifications
It should be noted that our observation services were performed on an as requested basis and
only when requested by the above listed client or their designated representative Terracon s
services do not include surveying of the locations or elevations of foundations elements We
offer no opinion regarding material and/or construction not observed by Terracon
representatives This letter is provided solely for the benefit for the above listed client and does
not impact in any way the rights and obligations of third parties including contractors and
subcontractors who may have provided the materials and/or construction services observed
Sincerely
Terracon Consultants
loels C Malama P E
Department Manager/
Copies to Addressee (2)
��p0 REG/.9
C
O�S �
' 42184
41
14,
2i22n 0
w L�
Walker CET
ke
Manager/Construction Services
Terracon Consultants Inc 301 North Howes
Fort Collins Colorado 80521
P [9701 484 0359 F [9701 484 0454
terracon com
Irerracon
March 9 2010
Shadow Creek Homes
2861 W 120th Avenue Suite 240
Westminster Colorado 80234
Attn Mr Toby Terhune
Re Foundation Damp Proofing Observation
Provincetowne Residential Development
833 Snowy Plain Road — Lot 6 Block 4
Fort Collins Colorado
Terracon Project No 20075058
A representative of Terracon Consultants Inc (Terracon) performed a foundation damp proofing
observation at the subject site on February 22 2010
The purpose of these services was to observe that damp proofing was in locations of below grade
basement foundation walls enclosing habitable space areas in general accordance with Foundation
Damp proofing 2003 International Residential Code (IRC) Section R406 The observation did not
include measurement of the coating thickness or determining the type of coating used
Based on our limited observation the foundation damp proofing appeared to have been applied in
general accordance with the above mentioned standards It should be noted that our observation
services were performed on an as requested basis and only when requested by the above listed client
or their designated representative We offer no opinion regarding materials and/or construction not
observed by Terracon representatives This letter is provided solely for the benefit for the above listed
client and does not impact in any way the rights and obligations of third parties including contracto s
and subcontractors who may have provided the materials and/or construction services observed
Sincerely
Terracon Consultants
p0 REG/sj
Fes'" C
81�
42184
3/09110 '44
s/otiAI_E�CJ
Joels C Malama P E
Department Manager/ Geotechnical Services
Copies to Addressee (2)
Mike 4LW!Iker CET
Manager/Construction Services
Terracon Consultants Inc 301 North Howes Fort Collins Colorado 80521
P 19701 484 0359 F 1970] 484 0454 terracon corn