HomeMy WebLinkAbout1123 W Elizabeth St - Special Inspections/Field Verification - 06/06/2011b1((�oK
w El zal eJ/ s i
I I
FORT COLLINSMIDWEST INC.
3818 PLATTE CT. FORT COLLINS, CO. 80526
PHONE (970) 223-5421 FAX (970) 225-2814
TESTING, ADJUSTING & BALANCING OF H.V.A.C. & HYDRONIC SYSTEMS
GENERAL INFORMATION
PROJECT
LOCATION
ARCHITECT
MECHANICAL ENGINEER
MECHANICAL CONTRACTOR
BALANCING TECHNICIAN
DATE
INSTRUMENTS USED
VELGRID
FLOW HOOD
ANEMOMETER
SPEED INDICATOR
AMMETER
VOLTMETER
POWER HARMONICS ANALYZER
DIGITAL MICROMANOMETER
PRESSURE GAGE
PRESSURE GAGE -DIFFERENTIAL
ULTRASONIC FLOW METER
THERMOMETERS
IAQ METER CO2 & CO
PARADISE NAILS & SPA
FORT COLLINS, COLORADO
WILLIAM C. HARRISON
JUNE 2011
SHORTRIDGE AIRDATA MULTIMETER
FLUKE 36 TRUE RMS
FLUKE 36 TRUE RMS
SHORTRIDGE AIRDATA MULTIMETER
PROJECT ALTITUDE 5000'
' SHORTRIDGE BAROMETRIC CORRECTION IS AUTOMATIC.
WILLIAM C. HARRISON IS A MEMBER OF THE ASSOCIATION OF ENERGY ENGINEERS,
AND IS A CERTIFIED TESTING, ADJUSTING AND BALANCING PROFESSIONAL.
//D 3 W f-/;zab e.fA ST
8//o1689
FORT COLLINS/MIDWEST, INC.
EQUIPMENT DATA
PROJECT PARADISE NAILS & SPA
(A) FAN UNIT # INLINE FAN SUPPLY
MAKE BROAN
MODEL # L-700 (FROM SCHEDULE)
SERIAL # NO NAMEPLATE
RATING NOT GIVEN
(B) MOTOR *NO ACCESS
TYPE
HORSEPOWER
MEAS. VOLTS (L/L)
MEAS. VOLTS (L/G) 122
INITIAL AMPS
FINAL AMPS 1.2
(C) STARTER NONE
EXIST. THERMALS
REQ'D. THERMALS
REMARKS BUILT IN OVERLOAD PROTECTION
(D) SHEAVES
DRIVEN
DRIVER
DRIVEN CHANGE
DRIVER CHANGE
INITIAL RPM
DIRECT DRIVE
DIRECT DRIVE
(E) STATIC PRESSURE IN INCHES
RATED PF/EFF
RATED SPEED
RATED VOLTS
RATED AMPS
PHASE
SERVICE FACTOR
FRAME
SIZE
EXIST AMP RATING
REQ'D AMP RATING
BORE SIZE
BORE SIZE
BELTS/SIZE
BELT CHANGE
FINAL RPM
FILTER
IN
OUT
DROP
HEAT COIL
IN
OUT
DROP
COOL COIL
IN
OUT
DROP
FAN
IN
- 0.306 OUT
0.232 RISE 0.538
(F) MEAS. AIR FLOW
REQ'D. 700 CFM
FINAL 756 CFM
DIRECT DRIVE
PAGE 1
eYA sal
BIM /6g
FORT COLLINS/MIDWE T, INC.
EQUIPMENT DATA
PROJECT PARADISE NAILS & SPA
(A) FAN UNIT # INLINE FAN EXHAUST
MAKE BROAN
MODEL # L-700 (FROM SCHEDULE)
SERIAL # NO NAMEPLATE
RATING NOT GIVEN
(B) MOTOR *NO ACCESS
TYPE
HORSEPOWER
MEAS. VOLTS (L/L)
MEAS. VOLTS (L/G) 122
INITIAL AMPS
FINAL AMPS 1.2
(C) STARTER NONE
EXIST. THERMALS
REQ'D. THERMALS
REMARKS BUILT IN OVERLOAD PROTECTION
(D) SHEAVES
DRIVEN
DRIVER
DRIVEN CHANGE
DRIVER CHANGE
INITIAL RPM
DIRECT DRIVE
DIRECT DRIVE
(E) STATIC PRESSURE IN INCHES
RATED PF/EFF
RATED SPEED
RATED VOLTS
RATED AMPS
PHASE
SERVICE FACTOR
FRAME
SIZE
EXIST AMP RATING
REQ'D AMP RATING
BORE SIZE
BORE SIZE
BELTS/SIZE
BELT CHANGE
FINAL RPM
FILTER
IN
OUT
DROP
HEAT COIL
IN
OUT
DROP
COOL COIL
IN
OUT
DROP
FAN
IN
- 0.313 OUT
0.105 RISE 0.418
(F) REMARKS
DIRECT DRIVE
PAGE 2
S-�
FORT COLLINS/MI WEIT, INC.
AIR BALANCE DATA
PROJECT PARADISE NAILS & SPA
SYSTEM EXHAUST
FINAL
OPENING TYPE
SIZE
CFM
EXHAUST-1 CD
2408
193
EXHAUST-2 CD
2408
198
EXHAUST-3 CD
2408
308
TOTAL
699
REMARKS
PAGE 3