Loading...
HomeMy WebLinkAbout2008 Caribou Dr - Special Inspections/Backflow - 05/11/2004City of Fort Collins May 11, 2004 Utilities electric • stormwater • wastewater • water Cross -Connection Control Required Permit Application #130401792 2008 Caribou Dr., NEW CONSTRUCTION OF WOOD FRAME COMMERICAL OFFICE BLDG A backflow prevention assembly is required on the water service. This must be an approved Reduced Pressure Backflow Assembly installed horizontally and accessible for testing. This assembly is designed to discharge water under a backpressure situation when the second check is fouled. It is also capable of a full discharge if the first check is fouled. Because of the possibility of this occurring, the assembly must be installed in a location where there is adequate drainage for the size of the service. In addition an approved, listed expansion tank or other device designed for thermal expansion control is required. If there is a lawn irrigation system, an approved backflow preventer is required. A separate permit is required for a lawn irrigation system. Call for an inspection when assemblies are installed and tested. All backflow preventer installations must provide adequate clearances on all sides of the backflow preventer. If there are any questions concerning these backflow preventers please contact this office. John Nelson Cross -Connection Control Administrator 970-221-6677 700 Wood St. • P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6700 • FAX (970) 221-6619 • TDD (970) 224-6003 e-mail: utilities@fcgov.com . www.fcgov.com/utilities