HomeMy WebLinkAbout7221 Fort Morgan Dr - Correspondence - 06/20/200206/20/2002 07:56 3033710333 AMI FIREPLACE CO INC PAGE 01/02
JUN-20-2002 10:19 P.02i02
e
No one builds a better fire
To: AMI Fireplace Co_ Inc.
Bruce Brown
Fm: Heat N Glo
Technical Service Dept.
Chris Smith
Re: Window clearances for vertical and horizontal
Date: 06-20-02
The drawing faxed to our department regarding a vertical termination cap DVK-TVCD is
required to be 12 inches from an openable window. The current distance is 34 inches and
therefore approved. Also, the perpendicular wall needs to be 24 inches from the cap and
this clearance is also met.
These clearances are required by ANSI standards listed in the manual. Horizontal and
vertical clearances to an openable window are the same standard.
I have included on page 3 of this fax my signature showing the approval of this
installation.
If you have any questions, please contact me at 1-800-6694328 or e-mail me at
smithc@heart tech.corn.
Sincerely,
Chris Smith
Tech Service
cs
TOTAL P.02