HomeMy WebLinkAbout4900 Boardwalk Dr - Correspondence/Water and or Sewer - 05/24/1995Services
Water & Wastewater
Citv of Fort Collins
Cross -Connection Control Required
May 24, 1995
Permit Application # 23055
4900 Boardwalk Dr. B, 15 Unit Apart.
A backflow prevention assembly is required on the fire line riser at this address. This must be an
approved Double Check Backflow Assembly installed horizontally and accessible for testing. Call
for a test and inspection when assembly is installed. If there is an antifreeze loop a Reduced
Pressure Backflow Assembly is required on the loop. Prior approval must be obtained for a
vertical installation.
John Nelson
Cross -Connection Control Administrator
303-221-6677