HomeMy WebLinkAbout4501 Boardwalk Dr - Correspondence/Water and or Sewer - 03/17/1998Citv of Fort Collins
March 17, 1998
Water Utilities
Stormwater • Water • Wastewater
Cross -Connection Control Required
Permit Application # 37036
4501 Boardwalk Dr., Install 10' Spa
A backflow prevention assembly is required on the water service to the spa. This must be an
approved Reduced Pressure Backflow Assembly installed horizontally and accessible for
testing. This assembly is designed to discharge water under a backpressure situation when the
second check is fouled. It is also capable of a full discharge if the first check is fouled. Because
of the possibility of this occurring the assembly must be installed in a location where there is
adequate drainage for the size of the service.
A Reduced Pressure Backflow Assembly is also required on the water service to the pool. This
must be installed prior to any tees or connections.
Call for an inspection when assemblies are installed and tested.
All backflow preventer installations must provide adequate clearances on all sides of the
backflow preventer. If there are any questions concerning these backflow preventers please
contact this office.
John Nelson
Cross -Connection Control Administrator
970-221-6677
P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6681