25 September 1992I����
p � 1D
Mr. Kevin Zdenek
Esprit C.M. Inc.
1220 South College Avenue
Fort Collins, CO 80524
Dear Mr. Zdenek:
The plans and specifications _submitted for the construction of
SchlotzskyIs,, 4212 South College Avenue,. Fort Collins, Colorado, have -been
reviewed by this department. The following items were not clearly specified
in the plans or were not in compliance with the Rules and Regulations
Governing the Sanitation of Food Service Establishments in the State of
Colorado. These items must be clearly specified in writing or be modified to
-be in compliance with the above regulations prior to approval of the
submitted plans. The plans are approved at this time.:
1) All food service equipment must be NSF (National Sanitation Foundation)
approved or its equivalent. Custom made equipment and used equipment
cannot be approved until it is visually inspected. The following
equipment is not approved at this time due to lack of information and/or
lack of NSF approval. The Federal display case is not NSF approved and
this will require visual i`nsp`ection - - - -
2) Be advised, sufficient conveniently located refrigeration facilities
must be provided to assure the maintenance of potentially hazardous food
at the required temperatures during storage and preparation. If the
Department finds the provided refrigeration to be inadequate, more will
be required.
3) Be advised, all gas equipment (e.g. cheesemelter) must be installed in
such a way as to permit easy cleaning around this equipment. It is
recommended that gas lines be long enough to allow the equipment to be
pulled far away from the wall for cleaning or to install pop -off valves
on the gas lines to allow the equipment to be completely disconnected
from the gas lines and the wall. Heavy equipment should also be mounted
on casters to allow for easy mobility. Flexible gas lines noted are
approved.
BOARD OF COUNTY COMMISSIONERS
Courtlyn W. Hotchkiss M. J. "Moe' Mekelburg Daryle W. Klassen
District I District 11 District (!I
Mr. Zdenek
September 25, 1992
Page 2
4) Be advised that no appurtenances, such as syrup lines, carbonators,
drop -in cold plates, drain lines or bottle holders are permitted in
potable ice bins or ice machines or any unit used to store potableAce.
5) This operation is not approved for any type of grease cooking.
6) The kitchen exhaust hood must be NSF (National Sanitation Foundation)
approved or its equivalent; must be constructed of stainless steel when
located over grease cooking equipment; must overhang all equipment not
less than 6 inches beyond the edge of the cooking surface on all open
sides.
Please provide locations of all make up air registers along with CFM
ratings of outside air introduced into the establishment. (Outside air
from sources other than the hood.)
Make up air must be filtered, tempered during winter months (when
exhaust exceeds 2500 cfm), and mechanically introduced into the
establishment at a volume equal to or greater than what is being
exhausted; must be distributed to establish necessary air patterns so
as not to short circuit exhaust systems; ,the kitchen should be under a
slightly negative pressure so that make up air can be exhausted through
the kitchen exhaust system after it moves from the dining area into the
kitchen.
The kitchen exhaust hood switch must be interlocked with the make up air
system.
7) Restrooms must be provided with mechanical ventilation to the outside
air. Submit information indicating if ventilation is provided and the
cfm rating of the exhaust fans.
8) Restroom fixtures are based upon the requirements of the Uniform
Plumbing Code. The total seating capacity of the establishment is 56.
_ —The following restroom fixtures will be required: men's room: 1 water
closet, 1 sink and 1 urinal. Women's room:-1 water closet and 1 sink.
Provide information on addition of urinal.
9) A commercial water heater that can achieve a minimum recovery rate of
133 gallons/hour if gas is required.
The A.O. Smith water heater, model BT155 (141 gallons /hour) is
approved.
10) Be advised that the 3-compartment sink tubs must be large enough to
submerge all equipment and utensils used in food preparation and food
storage.
Be advised, drainboards must be self draining and at least 24" in length
in establishments using single service utensils and 36" in length when
multi -use dishes are used. Twenty-four inch drainboards are approved as
submitted.
Mr. Zdenek
September 25, 1992
Page 3
11) Be advised, the mop sink must be provided with hot and cold running
water. Provide mop hangers or hooks around the mop sink to hang and air
dry mops.
12) An approved stainless steel vegetable sink with a minimum of one 18 inch
drain board must be provided if fresh vegetables are prepared as part of
a standard menu item. Be advised, this sink must be indirectly drained
to the sewer. Vegetable submitted is approved.
13) Be advised, hand sinks must be easily accessible in all rooms where food
is prepared or utensils are washed. The present location of the hand
sinks are approved.
14) Be advised that all handsinks must be provided with hot and cold running
water under pressure through a mixing valve, single service hand towels
from a dispenser, and soap.
15) Be advised, all drain lines from equipment such as: vegetable sinks,
the 3-compartment sink, ice machines, ice bins, drink dispensers, drink
overflow drains, refrigeration/freezer units, and cold tables holding
ice must be directed to a floor drain or floor sink and be properly air
gaped. Drainage of equipment as submitted is approved.
16) Floor sinks must not be installed under equipment or cabinetry where
they cannot be cleaned. All floor sinks and floor drains mustbe
installed so that they are flush with the finished floor.
17) Be advised, all plumbing and electrical conduit are to be installed
within and behind walls or below floors. Exposed water pipes, sewer
lines, or electrical conduit running along walls or floors are not
approved.
18) Be advised, all outer openings including doors and windows must be kept
closed, or permanent screens must be installed on outer openings that
will be left open periodically.
19) Be advised that all exit and restroom doors must be fitted with self -
closures.
20) Be advised that a rubber strip or threshold must be installed on all
outside doors to eliminate the gap between the floor and the door so as
to prevent insect infestation.
21) Be advised, 30 foot candles of light are required on all working
surfaces and 20 foot-candles of light on all other surfaces and
equipment in the kitchen, storage areas, service counter, restrooms,
utensil washing area, janitor's closet, all food prep areas and at self
service counter. All lights in the above areas, excluding the restrooms
and janitors closet, must be shielded in an approved manner. Be
advised, all lights inside equipment must also be shielded.
22) Be advised, floors, walls, ceilings, counter tops, storage shelves,
cabinets and all work surfaces located within the kitchen, storage
rooms, janitor's closet, restrooms, serving area, dishwashing areas, and
Mr. Zdenek
September 25, 1992
Page 4
all food prep areas must be of an approved material that is smooth,
easily cleanable, nonabsorbent and of a light color.
23) All paints used on the walls and ceilings must be: commercial grade;
washable, without removing the paint when cleaned; light in color. A
high gloss paint is recommended.
24) Be advised, all floor/wall junctures and stationary equipment floor
junctures in the kitchen, storage rooms, janitor's closet, restroom,
serving area, dishwashing areas, and all food prep areas must be
provided with approved concave coving.
25) All equipment, cabinets, and counters that are not easily moveable must
be: a) spaced so that floors, walls, and exterior surfaces of equipment
can be easily cleaned; or b) be sealed to adjoining walls, equipment,
cabinets, or counters. Hard to clean areas, spaces or gaps are not
approved.
26) Be advised that the lowest shelf of all storage shelves located in all
kitchen areas, storage rooms, and the walk-in(s) must be situated at
least six inches up off the floor.
27) Be advise, the outside dumpster storage area must be located on or above
a smooth surface of nonabsorbent material such as concrete or asphalt.
28) Toxic materials and surplus cleaning items must be stored away from food
operations, food storage and utensil washing facilities. Storage of
these materials in mopsink area is approved.
29) Provide an approved area for the proper storage of employee's personal
items, such as: coats, clothing, etc. Submit a proposed location.
30) Please be advised that the following items are required in the
establishment at the time of the opening inspection and thereafter:
a) stab food thermometer (0 to 220 F)
b) food grade plastic gloves and/or finger cots
c) approved sanitizer
d) test strips for the sanitizer
The above items (# 6, 8, & 29) can be submitted either in written form
or as an addendum to the plans submitted. The written plans submitted are
approved at this time. Be advised approval of plans, including the above
modifications, does not constitute acceptance of the completed structure. An
inspection of the premises must be conducted by this department prior to
approval for operation and licensure of the establishment. Failure to follow
the recommended changes may prevent or delay. the licensure of this
establishment. If construction is not commenced within 120 days, any
approval of the plans will be null and void and plans will have to be
resubmitted along with a $75.00 plan review fee fora second review.
Please notify the department at least 48 hours prior to your opening
date so that a final acceptance inspection can be performed.
Mr. Zdenek
September 25, 1992
Page 5
This department's written approval and the receipt of a completed state
food service license application and applicable fees is necessary prior to
opening.
Please feel free to contact this department if questions arise, or if I
can be of further service at 498-6775.
Sincerely,'
Gary Rd"thbarth
Sanitarian
GR/my