HomeMy WebLinkAbout3500 S College Ave - Correspondence/Other - 05/02/1978Page Three
BBA
5/2/78
be any other problems? Mr. Greenwood stated the building was calculated on the
basis as a retail store and now there would possibly be a community room in the
basement and possibly a restaurant. He felt the exits for these would be ok.
He stated there were 64 linear feet of exit required and 80 linear feet being
provided. MOTION MADE by William Brenner that a variance to eliminate the
requirement for 1—hour corridor walls be approved based upon the following
additional safety features:
1. Approximately 1000/ of additional lineal feet of exiting
will be provided.'
2. Length to exits — considerably shorter distance to exits
than the maximum allowed by Code.
3. Monitored early —warning fire —detection system.
4. The large ratio of public exitway area to leaseable
space = 1 sq.ft. of exit to 4.5 sq.ft. gross leaseable area.
5.- Design concept in which parallel exit ways totaling from 24 to 36
feet in width lead to exterior exits and are connected by several
cross corridors.
6., Approved automatic fire sprinkler system provided throughout the
building.
7. Owners agreement that no obstructions will be placed in exit ways
other than those inidcated on the approved plans reviewed Building
Board of Appeals.
SECONDED by Richard Hollar.
MOTION CARRIED UNANIMOUSLY.