LARIMER COUNTY HEALTH DEPARTMENT
Adrienne LeBallly, MD, MPH, Director
August 7, 1991
John G-. Giuli-ano _ --
Guiliano and Father
1708 East Lincoln
Fort Collins, CO 80524
Dear Mr. Giuliano:
BOARD OF HEALTH
Kent N. Campbell, JD, Fort Collins
President
Pamela Howard, Loveland
Vice President
Kenneth W. Curtis, Jr., MD. MPH, Fort Collins
Eldon Savage, PhD, MPH, Fort Collins
Glenn W. Wellman, OD, MPH, Estes Park
1525 Blue Spruce Drive, Fort Collins, Colorado 80524
General Health 498-6700 Environmental Health 498-6775
The plans and specifications submitted for the construction of Little Suigan
Cafe located at 3500 South College Avenue, Fort Collins, Colorado, have been -
reviewed by this department. The following items were not clearly specified in the
plans or were not in compliance with the Rules and Regulations Governing the
Sanitation of Food Service Establishments in the State of Colorado. These items
must be clearly specified in writing or be modified to be in compliance with the
above regulations prior to approval of the submitted plans. All plans must be
approved prior to commencement of construction.
1. All food service equipment must be NSF (National Sanitation Foundation)
approved or its equivalent. Custom made equipment and used equipment cannot be
approved until it is visually inspected.
2 All gas equipment-(e:g':; fryer, -Tempura" range, burner -range, etc.) must be —
installed in such a way as to permit easy cleaning around this equipment. It
is recommended that gas lines be long enough to allow the equipment to be
pulled far away from the wall for cleaning or to install pop -off valves on the
gas lines to allow the equipment to be completely disconnected from the gas
lines and the wall.
Be advised that no appurtenances, such as; syrup lines, carbonators, drop -in
cold plates, drain lines or bottle holders are permitted in potable ice bins or
ice machines or any unit used to store potable ice.
The kitchen exhaust hood must be NSF (National Sanitation Foundation) approved
or its equivalent; must be constructed of stainless steel when located over
grease cooking equipment; must overhang all food service equipment which
produce grease vapors, steam, fumes, smoke, etc. not less than-6 inches beyond
the edge of the cooking surface on all open sides.
BOARD OF COUNTY COMMISSIONERS
Courtlyn W. Hotchkiss M. J. 'Moe' Mekelburg Daryle W. Klassen
District I District 11 District III
7 �
John G. Giuliano
August 7, 1991
Page 2
Make up air must be filtered, tempered (during winter months) and mechanically
introduced into the establishment at a volume equal to or greater than what is
being exhausted; must be distributed through several registers to establish
necessary air patterns so as not to short circuit exhaust systems; the kitchen
should be under a slight negative pressure so that make up air can be exhausted
through the kitchen exhaust system after it moves from the dining area into the
kitchen.
The kitchen exhaust hood switch must be interlocked with the make up air
system.
All hoods, approved or not, must be visually inspected and approved in writing
by this department prior to installation.
The ventilation system,is_approved at this- time.
5. Restrooms must be provided with mechanical ventilation to the outside air.
6. Since the total seating capacity of the establishment is 66, the following
restroom fixtures will be required: men's room: 1 water closet, 1 sink and 1
urinal. Women's room: 1 water closet and 1 sink.
7. The A.O. Smith water heater, model BT 155 (140 gallons/hour) is approved.
8. Be advised that the 3-compartment sink tubs must be large enough to submerge
all equipment and utensils used in food preparation and food storage.
9. Provide a deep basin mop sink for the purpose of filling mop buckets and
cleaning mops. This sink must be provided with hot and cold running water.
Provide mop hangers or hooks around the mop sink to hang and air dry mops.
10. Be advised that all hand sinks must be provided with hot and cold running water
under pressure through a mixing valve; single service hand towels from a
dispenser and soap.
11. All drain lines from equipment such as; ice machines, ice bins, drink
--. dispensers, drink overflow -drains,_ refrigeration/freezer_ units, must be
directed to a floor drain or floor sink and be properly air gapped.- —
12. Floor sinks must not be installed under equipment where they cannot be cleaned.
All floor sinks and floor drains must be installed so that they are flush with
the finished floor.
13. Provide information noting the location and size of the grease trap.
14. All plumbing and electrical conduit are to be installed within and behind walls
or below floors. Exposed water pipes, sewer lines, or electrical conduit
running along walls or floors are not approved.
15. All outer openings including doors and windows must be kept closed, or
permanent screens must be installed on outer openings that will be left open
periodically.
16. Be advised that all exit and restroom doors must be fitted with self -closures.
John G. Giuliano
August 7, 1991
Page 3
17. Be advised that a rubber strip or threshold must be installed on all outside
doors to eliminate the gap between the floor and the door so as to prevent
insect infestation.
18. Be advised, 30 foot candles of light are required on all working surfaces and
20 foot-candles of light on all other surfaces and equipment in the kitchen,
storage areas, service counter, restrooms, utensil washing area, and all food
prep areas. All lights in the above areas, excluding the restrooms, must be
shielded in an approved manner.
19. Floors, walls, ceilings, counter tops, storage shelves, cabinets and all work
surfaces located within the kitchen, storage rooms, mop area, restrooms,
serving area, dishwashing areas, and all food prep areas must be of an approved
material that -is smooth, -easily -cleanable, nonabsorbent-and of- a light color.
20. All paints used on the walls and ceilings must be: commercial grade; washable,
without removing the paint when cleaned; light in color. An epoxy type paint
or high gloss paint is recommended.
20. All floor/wall and stationary equipment floor junctures in the kitchen, storage
rooms, mop area, restroom, serving area, dishwashing areas, and all food prep
areas must be provided with approved concave coving.
21. All equipment, cabinets, and counters that are not easily moveable must be: a)
spaced so that floors, walls, and exterior surfaces of equipment can be easily
cleaned; or b) be sealed to adjoining walls, equipment, cabinets, or counters.
Hard to clean areas, spaces or gaps are not approved.
22. Be advised that the lowest shelf of all storage shelves located in all kitchen
areas, storage rooms, and the walk-in(s) must be situated at least six inches
up off the floor.
23. The outside dumpster storage area must be located on or above a smooth surface
of nonabsorbent material such as concrete or asphalt.
24. Provide an approved -area away-from--food-opera,tions,_food storage and utensil
washing facilities for the storage of toxic materials and surplus cleaning
items.
25. Provide an approved area for the proper storage of employee's personal items;
coats, clothing, etc.
26. Please be advised that the following items are required in the establishment at
the time of the opening inspection and thereafter:
a) stab food thermometer (0' to 220°F)
b) food grade plastic gloves
c) approved sanitizer
d) test strips for your sanitizer
The above items can be submitted either in written form or as an addendum to
the plans submitted. The written plans submitted are approved at this time. Be
advised approval of plans, including the above modifications, does not constitute
John G. Giuliano
August 7, 1991
Page 4
acceptance of the completed structure. An inspection of the premises must be
conducted by this department prior to approval for operation and licensure of the
establishment. Failure to follow the recommended changes may prevent or delay the
licensure of this establishment. Any approval of the plans will be null and void
if construction is not commenced within 120 days.
Please notify the department at least 48 hours prior to your opening date so
that a final acceptance inspection can be performed.
A state food service license and this department's written approval is
necessary prior to opening.
Please feel free to contact this department if questions -arise, or if I can be
of further service at 498-6775.