Loading...
HomeMy WebLinkAbout856 Campfire Dr - Disclosures/Blower Door Test - 04/03/2014BUILDING LEAKAGE TEST Date of Test: 03/28/2014 Technician: Doug Groff Test File: DR Horton Blower door Customer: DR Horton 7600 E Orchard Rd #350-S Greenwood Village, Colorado 80111 Phone Building Address: 856 Campfire Drive - Final Reports Fort Collins, Colorado 80524 Test Results 1. Airflow at 50 Pascals: 1150 CFM ( +/- 0.1 %) (50 Pa = 0.2 w.c.) 2.40 ACH 0.36 CFM per ft2 floor area 2. Leakage Areas: 3. Minneapolis Leakage Ratio: 0.17 CFM50 per ft2 surface area 4. Building Leakage Curve: Flow Coefficient (C) = 880.4 ( +/- 1.0 %) Exponent (n) = 0.068 ( +/- 0.003 ) Correlation Coefficient = 0.99759 5. Test Settings: Test Standard: = CGSB Test Mode: = Depressurization Equipment = Model 3 Minneapolis Blower Door Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 302.2 CFM 0.63 ACH 2. Estimated Design Infiltration Rate: Winter: 463.7 CFM 0.97 ACH Summer: 263.5 CFM 0.55 ACH 3. Recommended Whole Building Mechanical 0.0 CFM Ventilation Rate: (based on ASHRAE 62.2) Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: B1303938 BUILDING LEAKAGE TEST Page 2 Date of Test: 03/28/2014 Test File: DR Horton Blower door Building Conditions Inside Temperature: 70 deg F Heating Fuel: Gas Outside Temperature: 45 deg F Heating Fuel Cost: # of Stories 2.0 Heating Efficiency: Heating Degree Days: 6020 Wind Shield: M Cooling Fuel Cost: # of Occupants Cooling SEER: Cooling Degree Days: 287 # of Bedrooms: 4.0 Volume: 28771 ft3 Ventilation Weather Factor: 0.87 Surface Area: 6892 ft2 Energy Climate Factor: 17.0 Floor Area: 3238 ft2 Design Winter Wind Speed: 9.0 mph Design Winter Temp Diff: 69 deg F Design Summer Wind Speed: 7.0 mph Design Summer Temp Diff: 16 deg F Comments GARAGE WRT HOUSE: 49.9 Pa @ 50 Pa B1303938 BUILDING LEAKAGE TEST Page 3 Date of Test: 03/28/2014 Test File: DR Horton Blower door Data Points: Data Entered Manually Nominal Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow Temperature Adjusted Flow % Error Fan Configuration Baseline Std Dev (Pa) -14.6 n/a +/- 0.00 -65.0 42.3 1180 1152 0.1 Ring A -60.0 41.5 1170 1142 -0.0 Ring A -55.0 40.8 1160 1132 -0.1 Ring A -50.0 40.1 1150 1123 -0.1 Ring A -45.0 39.4 1140 1113 0.1 Ring A B1303938