HomeMy WebLinkAbout2250 Thoreau Dr - Disclosures/Blower Door Test - 01/30/2014BUILDING LEAKAGE TEST Thermal Concepts 6617 S. College ave Fort Collins, CO 80525 Date of Test: 1-30-14 Test File: Journey Homes 2250 Thoreau Dr -BD Customer: Journey. Homes Technician: Paul Higman Project Number: Greeley, CO 80634 Building Address: 2250 Thoreau Dr Fort Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 1013 CFM50 (+/-1.5 %) (50 Pa = 0.2 w.c.) 3.71 ACH50 0.5724 CFM50/ft2 floor area 2. Leakage Areas: 53.5 in2 (+/- 9.8 %) Canadian EgLA @ 10 Pa 19.5 in2 (+/- 15.6 %) LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 15.7 ( +/- 24.3 %) Exponent (n) = 1.066 ( +/- 0.063 ) Correlation Coefficient = 0.98960 4. Test Settings: Test Standard: CGSB Test Mode: Depressurization Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 19.3 CFM 0.07 ACH 2. Estimated Design Infiltration Rate: Winter: 32.9 CFM Summer: 18.4 CFM 0.12 ACH 0.07 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 1-30-14 Test File: Journey Homes 2250 Thoreau Dr-BD Building Infortnation Location Climate Infortnation Volume 16388 Ventilation Weather Factor 0.87 Surface Area Energy Climate Factor 17.00 FloorArea 1770 Heating Degree Days 6020 Height 16 Cooling Degree Days 287 #of Bedrooms 3 Design Winter Wind Speed 9.0 mph #of Occupants Design Summer Wind Speed 7.0 mph Year of Construction 2014 Design Winter Temp Diff 69 deg F Wind Shield M Design Summer Temp Diff 16 deg F Heating and Cooling Cost and Efficiency Infortnation Heating Fuel Gas Heating Fuel Cost Heating Efficiency% Cooling Fuei Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3(110� Default Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 1-30-14 Test File: Joumey Homes 2250 Thoreau Dr-BD Depressurization Test: Environmental Data Indoor Temperature(A°F) Outdoor Temperature(A°F) 69.0 40.0 Data Points-Data Entered Manually Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) %Error Configuration -1.2 n/a n/a �0.2 -59.1 44.2 1206 1172 -3.1 Ring A -55.2 -54.1 37.9 1119 1088 -1.2 Ring A -50.2 -49.1 32.8 1043 1014 2.1 Ring A �5.2 �4.1 28.6 975 948 7.1 Ring A -40.1 -39.0 184.5 805 783 0.8 Ring B -35.9 -34.8 137.6 696 677 -1.6 Ring B -30.2 -29.1 89.7 563 547 -3.6 Ring B -25.9 -24.8 60.2 462 449 �.2 Ring B -1.1 nJa n/a Deviations from Standard CGSB-Test Parameters - n value(1.066)outside of acceptable limits. - Correlation coefficient(0.990)outside of acceptable limits. - %Error for one or more of the data test points is greater than 6%. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 1-30-14 Test File: Joumey Homes 2250 Thoreau Dr-BD Comments House wrt Garage=-47.4pa