HomeMy WebLinkAbout3664 Galileo Dr - Disclosures/Blower Door Test - 11/26/2013BUILDING LEAKAGE TEST
Date of Test: 11/26/2013
Customer: Village Homes
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve:
Test File: Untitled
Technician:
Project Number:
Building Address: 3664 Galileo Dr
1033 CFM50 (+/- 0.6 %)
1.70 ACH50
56.8 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 363.8 ( +/- 14.7 %)
Exponent (n) = 0.267 ( +/- 0.036 )
Correlation Coefficient = 0.98854
4. Test Settings: Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
47.4 CFM
0.08 ACH
9.5 CFM per person
Winter: 69.2 CFM Summer: 50.8 CFM
0.11 ACH 0.08 ACH
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 11/26/2013 Test File: Untitled
Building Information Location Climate Information
Volume
36491
Surface Area
8681
Floor Area
3556
Height
9
# of Bedrooms
4
# of Occupants
5
Year of Construction
Wind Shield
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
297
Design Winter Wind Speed
7.3 mph
Design Summer Wind Speed
9.4 mph
Design Winter Temp Diff
73 deg F
Design Summer Temp Diff
15 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
Default
Micromanometer
Energy Conservatory
DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 11/26/2013 Test File: Untitled
Depressurization Test:
Environmental Data
Indoor Temperature (°F)
Outdoor Temperature (°F)
Altitude (ft)
70.0
48.0
1 5280.0
Data Points - Data Entered Manually
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
-1.5
n/a
n/a
-66.0
-64.8
40.3
-64.0
-62.8
40.0
-62.0
-60.8
38.7
-60.0
-58.8
39.0
-58.0
-56.8
38.0
-56.0
-54.8
36.7
-54.0
-52.8
36.1
-52.0
-50.8
35.3
-50.0
-48.8
34.8
-0.9 '
n/a
n/a
Time Averaging Period: 10
1153
1105
-0.2
Ring A
1148
1100
0.2
Ring A
1130
1083
-0.5
Ring A
1134
1087
0.7
Ring A
1120
1073
0.4
Ring A
1101
1055
-0.4
Ring A
1092
1046
-0.2
Ring A
1081
1036
-0.2
Ring A
1073
1028
0.2
Ring A
Deviations from Standard RESNET Multi -Point Test - Test Parameters
None.
- * n value outside of normally accepted limits.
- * correlation coefficient outside of normally accepted limits.
* n value and/or correlation coefficient limits are not officially part of the RESNET Multi -Point Test
Standard..
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 11/26/2013 Test File: Untitled
Comments
None
Tested garage connection to home at 49 pascals at . Passes Ft Collins requirement of 45 or higher
The connection to the CAZ was NA because all appliances are sealed combustion.