HomeMy WebLinkAbout2712 S College Ave - Special Inspections/Field Verification - 01/08/2014IF�'1302I �2
w//eye_ A4e.
JFG
Aff .
ENGINEERING, INC. 1833 MTN VIEW RD.. SEDALIA CO (303) 688-9044
GENERAL INFORMATION
PROJECT
LOCATION
ELEVATION
ARCHITECT
MECH. ENG.
CONTRACTOR
BAL. CREW
DATE
I JPG JOB #
I INSTRUMENTS USED
MITSUBISHI DEALERSHIP (PRELIMINARY)
FORT COLLINS,CO
THE BALLARD GROUP
HORIZON MECHANICAL SOLUTIONS
ERIC CONNER, DEREK GRIFFITH
DECEMBER 2013
3166
CALIBRATION DATE: Jan 12, 2013
AMPMETER/VOLTMETER
FLuke 32
525666
ANEMOMETER
Davis A/2 Ball Brg.
JPG-17
PRESSURE GAGE -DIFFER
FLO-DESIGN 12C1386 0-300"
JPG-1
SPEED INDICATOR
Biddle 9920
786293
VELOMETER
Shortridge ADM-870
M98083
METHOD OF BALANCE
Supply Diffusers are read with a capture hood using a Shortridge Air Data Meter.
Exhaust and return inlet registers read with Shortridge Air Data Meter and Flow Hood.
Y ['
110
ENGINEER/NG
EQUIPMENT DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
EQUIPMENT INFORMATION
UNIT# EF-3 MAKE PENN BARRY
MODEL# ZJ1 SERIAL# G13AV36451
RATING 100 CFM @ 0.50" ESP
MOTOR DATA
MAKE FASCO H.P. 125 WATTS PF/EFF NOT GIVEN /NOT GIVEN
TYPE U63S61 PH. 1 RATED SPEED 1550
MEAS.VOLTS 120 SF. NOT GIVEN RATED VOLTS 115
MEAS.AMPS 1.3 FR. NOT GIVEN RATED AMPS 1.4
STARTER DATA
MAKE NONE MODEL
SIZE. ENCLOSURE CLASS
THERMALS (EXISTING) AMP RATING
THERMALS (REQUIRED)AMP RATING
OTHER BUILT IN OVERLOAD
DRIVE DATA
DRIVEN SHEAVE DIRECT DRIVE BORE
DRIVER SHEAVE BORE
BELT SIZE NO. BELTS
TURNS TO MAX MOTOR ADJUST-INCHES
DRIVE CHANGE BELT CHANGE
INITIAL/FINAL RPM / FINAL AMPS 1.3
PRESSURE INFORMATION ,
FAN IN ATMOS" OUT 0.14" - "
Remarks: REQUIR = 100 CFM FINAL= 172 CFM p
NO SP ED CONTROLLER �� � � [�
n������ h�
D �
��
� � �.�k��`'ST
u�`�.�C
T
Page 15 of 19
ENGINEER/NG
EQUIPMENT DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
EQUIPMENT INFORMATION
UNIT# EF-4 MAKE
MODEL# SERIAL#
RATING 2600 CFM @ 0.15" ESP
MOTOR DATA
MAKE H.P. PF/EFF /
TYPE PH. RATED SPEED
MEAS.VOLTS SF. RATED VOLTS
MEAS. AMPS FR. RATED AMPS
STARTER DATA
MAKE MODEL
SIZE ENCLOSURE CLASS
THERMALS (EXISTING)AMP RATING
THERMALS (REQUIRED)AMP RATING
OTHER
DRIVE DATA
DRIVEN SHEAVE BORE
DRIVER SHEAVE BORE
BELT SIZE NO. BELTS
TURNS TO MAX MOTOR ADJUST-INCHES
DRIVE CHANGE BELT CHANGE
INITIAUFINAL RPM / FINAL AMPS
PRESSURE INFORMATION
IN " OUT " - "
Remarks: REQUIRED =2,500 CFM FINAL= 2,171 CFM
NO ACCESS TO MOTOR OR SHEAVES TO SPEED UP
Page 16 of 19
ENG/NEERING
RECTANGULAR DUCT TRAVERSE REPORT
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
SYSTEM EF-4 LOCATION/ZONE
AIR TEMP. (°F) DUCT S.P.
DUCT REQUIRED MEASURED
SIZE 26 X 24 SQ.FT. 4.33 FPM 577 CFM 2500 FPM 501.00 CFM 2171
POSITION 1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 413 425 605 561
2
3
4
5
6
7
8
9
10
11
12
13
14
velocity 413 425 605 561
Subtotals
NOTE: Instrumentation used: Airdata Multimeter
Velocity readings are automatically corrected for altitude and temperature.
(2004/4 )_ ( 501.00 FPM) (4.33 SQ.FT. )= 2171 CFM
Remarks:
Page 17 of 19
ENGINEERING
EQUIPMENT DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
EQUIPMENT INFORMATION
UNIT# EF-5 MAKE PENN BARRY
MODEL# ZJ1 SERIAL# G13AV36450
RATING 80 CFM @ 0.25" ESP
MOTOR DATA
MAKE FASCO H.P. 125 WATTS PF/EFF NOT GIVEN/NOT GIVEN
TYPE U63SB1 PH. 1 RATED SPEED 1550
MEAS.VOLTS 120 SF. NOT GIVEN RATED VOLTS 115
MEAS.AMPS 1.1 FR. NOT GIVEN RATED AMPS 1.4
STARTER DATA
MAKE NONE MODEL
SIZE ENCLOSURE CLASS
THERMALS (EXISTING)AMP RATING
THERMALS (REQUIRED)AMP RATING
OTHER BUILT IN OVERLOAD
DRIVE DATA M
DRIVEN SHEAVE DIRECT DRIVE BORE
DRIVER SHEAVE BORE
BELT SIZE NO. BELTS
TURNS TO MAX MOTOR ADJUST-INCHES
DRIVE CHANGE BELT CHANGE
INITIAL/FINAL RPM / FINAL AMPS 1.1
PRESSURE INFORMATION
FAN IN ATMOS" OUT 0.01" - "
Remarks: REQUIRED =80 CFM FINAL=83 CFM
SPEED CONTROLLER SET AND MARKED
Page 18 of 19
ENGIIVEERING
EQUIPMENT DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
EQUIPMENT INFORMATION
UNIT# RTU-1 MAKE TRANE
MODEL# YHC092F3RHA09C001 SERIAL# 133311013L
RATING 3,200 CFM @ 0.75" ESP
MOTOR DATA
MAKE NO ACCESS H.P. PF/EFF /
TYPE PH. RATED SPEED
MEAS. VOLTS SF. RATED VOLTS
MEAS.AMPS 5.6 FR. RATED AMPS
STARTER DATA
MAKE FACTORY INSTALLED MODEL
SIZE ENCLOSURE CLASS
THERMALS (EXISTING)AMP RATING
THERMALS (REQUIRED)AMP RATING
OTHER
DRIVE DATA
DRIVEN SHEAVE DIRECT DRIVE BORE
DRIVER SHEAVE BORE
BELT SIZE NO. BELTS
TURNS TO MAX MOTOR ADJUST-INCHES
DRIVE CHANGE BELT CHANGE
INITIAUFINAL RPM / FINAL AMPS 5.6
PRESSURE INFORMATION
FILTER IN -0.27" OUT NO ACCESS" - "
COOLING COIL IN NO ACCESS" OUT -0.48" - "
FAN IN -0.48" OUT NO ACCESS" - "
HEATING COIL IN NO ACCESS" OUT 1.27" - "
Remarks: UNIT FINALLED AT MINIMUM ( 18% -600 CFM)OUTSIDE AIR REQUIRED = 3,200 CFM FINAL= 3,469 CFM
SPEED CONTROLLER SET AND MARKED
Page 3 of 19
ENGINEERlNG
AIR BALANCE DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
SYSTEM RTU-2 LOCATION
SIZE REQUIRED FINAL MINIMUM HEATING
OPENING
PLAN ACTUAL AREA VEL CFM VEL CFM VEL CFM VEL CFM
ZD2-1
1 24/8 24/8 1.0 130 130 138 138 0 0 0 0
2 24l8 24/8 1.0 130 130 134 134 0 0 0 0
TOTAL 260 272
ZD2-2
1 24/8 24/8 1.0 140 140 138 138 0 0 0 0
2 24/8 24/8 1.0 140 140 144 144 0 0 0 0
TOTAL 280 282
ZD-2-3
1 24/8 24/8 1.0 180 180 177 177 0 0 0 0
2 24/8 24/8 1.0 180 180 180 180 0 0 0 0
TOTAL 360 357
Page 7 of 19
ENGINEERING
AIR BALANCE DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
SYSTEM RTU-2 LOCATION
SIZE REQUIRED FINAL MINIMUM HEATING
OPENING
PLAN ACTUAL AREA VEL CFM VEL CFM VEL CFM VEL CFM
ZD2-4
1 24/8 24/8 1.0 150 150 148 148 0 0 0 0
2 24l10 24/10 1.0 330 330 332 332 0 0 0 0
3 24/10 24/10 1.0 345 345 340 340 0 0 0 0
4 24/8 24/8 1.0 120 120 122 122 0 0 0 0
TOTAL 945 942
Page 8 of 19
ENGINEERlNG
AIR BALANCE DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
SYSTEM RETURN LOCATION
SIZE REQUIRED FINAL MINIMUM HEATING
OPENING
PLAN ACTUAL AREA VEL CFM VEL CFM VEL CFM VEL CFM
RTU-2
1 24X24 24X24 1.0 820 820 800 800 0 0 0 0
2 24X24 24X24 1.0 320 320 312 312 0 0 0 0
3 12"O 12"O 0.79 684 540 675 533 0 0 0 0
TOTAL 1680 1645
Page 9 of 19
ENGINEERING ,
EQUIPMENT DATA I
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
EQUIPMENT INFORMATION
UNIT# MAU-1 MAKE CAPTIVE AIRE
MODEL# SERIAL#
RATING 2,500 CFM @ 0.75" ESP
MOTOR DATA
MAKE WEG H.P. 2.0 PF/EFF 0.8/77.0
TYPE NOT GIVEN PH. 3 RATED SPEED 1710
MEAS. VOLTS 208/208/208 SF. 1.15 RATED VOLTS 208-230/460
MEAS. AMPS 6.0/6.1/6.1 FR. E56 RATED AMPS 6.2-6.0/3.06
STARTER DATA
MAKE FACTORYINSTALLED MODEL
SIZE ENCLOSURE CLASS
THERMALS (EXISTING)AMP RATING
THERMALS (REQUIRED)AMP RATING
OTHER
DRIVE DATA
DRIVEN SHEAVE AK54 ` BORE 1"
DRIVER SHEAVE 1VP40 BORE 7/8"
BELT SIZE AX45 NO. BELTS 1
TURNS TO MAX 2 MOTOR ADJUST-INCHES OUT 5" IN 0"
DRIVE CHANGE AK 69 BELT CHANGE A48
INITIAUFINAL RPM 800/700 FINAL AMPS 6.0/6.1/6.1
PRESSURE INFORMATION
FILTER IN ATMOSPHERE" OUT -0.07" - '
EVAP IN -0.07" OUT -0.20" DROP 0.13"
, FAN IN -0.74" OUT 0.08" RISE 0.82"
Remarks: UNIT FINALLED AT 100%OUTSIDE AIR REQUIRED = 2,500 CFM FINAL= 3,361 CFM
LEFT HIGH DUE TO DRY EVAP PAD
Page 10 of 19
ENGINEERING
AIR BALANCE DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
SYSTEM SUPPLY LOCATION
SIZE REQUIRED FINAL MINIMUM HEATING
OPENING
PLAN ACTUAL AREA VEL CFM VEL CFM VEL CFM VEL CFM
MAU-1
1 18X6 17X5 0.59 466 275 634 374 0 0 0 0
2 18X6 17X5 0.59 466 275 620 366 0 0 0 0
3 18X6 17X5 0.59 551 325 761 449 0 0 0 0
4 18X6 17X5 0.59 551 325 - 727 429 0 0 0 0
5 18X6 17X5 0.59 551 325 702 414 0 0 0 0
6 18X6 17X5 0.59 551 325 753 444 0 0 0 0
7 18X6 17X5 0.59 551 325 725 428 0 0 0 0
8 18X6 17X5 0.59 551 325 775 457 0 0 0 0
TOTAL 2500 3361
Page 11 of 19
ENGlNEERING
EQUIPMENT DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
EQUIPMENT INFORMATION
UNIT# EF-1 MAKE PENN BARRY
MODEL# ZJ1 SERIAL# G13AV36457
RATING 80 CFM @ 0.25" ESP
MOTOR DATA
MAKE FASCO H.P. 125 WATTS PF/EFF NOT GIVEN/NOT GIVEN
TYPE U63SB1 PH. 1 RATED SPEED 1550
MEAS.VOLTS 120 SF. NOT GIVEN RATED VOLTS 115
MEAS.AMPS 1.1 FR. NOT GIVEN RATED AMPS 1.4
STARTER DATA
MAKE NONE MODEL
SIZE ENCLOSURE CLASS
THERMALS (EXISTING)AMP RATING
THERMALS (REQUIRED)AMP RATING
OTHER BUILT IN OVERLOAD
DRIVE DATA
DRIVEN SHEAVE DIRECT DRIVE BORE
DRIVER SHEAVE BORE
BELT SIZE NO. BELTS
TURNS TO MAX MOTOR ADJUST-INCHES
DRIVE CHANGE BELT CHANGE
INITIAUFINAL RPM / FINAL AMPS 1.1
PRESSURE INFORMATION
FAN IN ATMOS" OUT 0.01" - "
Remarks: REQUIRED=80 CFM FINAL=83 CFM
SPEED CONTROLLER SET AND MARKED
Page 13 of 19
ENGlNEER/NG
EQUIPMENT DATA
PROJECT MITSUBISHI DEALERSHIP (PRELIMINARY)
EQUIPMENT INFORMATION
UNIT# EF-2 MAKE PENN BARRY
MODEL# ZJ1 SERIAL# G13AV36455
RATING 80 CFM @ 0.25" ESP
MOTOR DATA
MAKE FASCO H.P. 125 WATTS PF/EFF NOT GIVEN/ NOT GIVEN
TYPE U63SB1 PH. 1 RATED SPEED 1550
MEAS.VOLTS 120 SF. NOT GIVEN RATED VOLTS 115
MEAS.AMPS 1.0 FR. NOT GIVEN RATED AMPS 1.4
STARTER DATA
MAKE NONE MODEL
SIZE ENCLOSURE CLASS
THERMALS (EXISTING)AMP RATING
THERMALS (REQUIRED)AMP RATING
OTHER BUILT IN OVERLOAD
DRIVE DATA
DRIVEN SHEAVE DIRECT DRIVE BORE
DRIVER SHEAVE BORE
BELT SIZE NO. BELTS
TURNS TO MAX MOTOR ADJUST-INCHES
DRIVE CHANGE BELT CHANGE
INITIAUFINAL RPM / FINAL AMPS 1.0
PRESSURE INFORMATION
FAN IN ATMOS" OUT 0.01" - "
Remarks: REQUIRED=80 CFM FINAL =79 CFM
SPEED CONTROLLER SET AND MARKED
Page 14 of 19