HomeMy WebLinkAbout2869 Rigden Pkwy - Disclosures/Blower Door Test - 09/12/2013BUILDING LEAKAGE TEST Date of Test: 9-12-13 Customer: Bridgefield Homes Fort Collins, CO 80525 Test File: Bridgefield 2869 Rigden Pkwy-BD Technician: Paul Higman Project Number: Building Address: 2869 Rigden Parkway Fort Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 1016 CFM50 (+/- 1.4 %) (50 Pa = 0.2 w.c.) 2.40 ACH50 0.4296 CFM50/ft2 floor area 2. Leakage Areas: 111.4 in2 ( +/- 5.8 %) Canadian EgLA @ 10 Pa 61.4in2(+/ 9.5 %) LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 92.5 ( +/- 15.0 %) Exponent (n) = 0.613 ( +/- 0.040 ) ' Correlation Coefficient = 0.98716 4. Test Settings: Test Standard: CGSB Test Mode: Depressurization Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 60.8 CFM 0.14 ACH 15.2 CFM per person 2. Estimated Design Infiltration Rate: Winter: 103.6 CFM Summer: 58.1 CFM 0.24 ACH 0.14 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: , , BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 9-12-13 Test File: Bridgefield 2869 Rigden Pkwy-BD Building Information Location Cllmate Information , Volume 25429 Ventilation Weather Factor � 0.87 Surtace Area Energy Climate Factor 17.00 FloorArea 2365 Heating Degree Days 6020 Height 16 Cooling Degree Days I 287 #of Bedrooms 3 Design Winter Wind Speed � 9.0 mph #of Occupants 4 Design Summer Wind Speed 7.0 mph Year of Construction Design Winter Temp Diff � 69 deg F Wind Shield M Design Summer Temp Diff � 16 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information . Type Manufacturer Model Seriat Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 , , , BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 9-12-13 Test File: Bridgefield 2869 Rigden Pkwy-Bp Depressurizatlon Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) 75.0 84.0 Data.Polnts - Data Entered Manually Nominal Baseline Adjusted Fan Nomina.l Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration -4.9 n/a n/a -60.2 -55.7 35.1 1077 1086 0.1 Ring A -55.0 -50.5 29.4 988 996 -2.5 Ring A -50.6 -46.0 28.1 967 975 0.9 Ring A -45.2 -40.7 246.4 929 937 4.7 Ring B -40.3 -35.8 191.5 820 827 -0.0 Ring B -35.0 -30.4 138.4 698 704 -6.1 Ring B -30.2 -25.6 125.1 664 670 -0.8 Ring B -25.4 -20.8 104.0 606 611 2.8 Ring B -4.2 Na n/a Deviations from Standard CGSB -Test Parameters - Correlation coefficient(0.987) outside of acceptable limits. . - % Error for one or more of the data test points is greater than 6%. _ � . , BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 9-12-13 Test File: Bridgefield 2869 Rigden Pkwy-BD Comments House WRT Garage = �8.5pa I , �