February 12, 2013 2956 29th Street, Unit 21
Greeley, Colorado 80631
Phone: (970) 506-9244
Fax: (970) 506-9242
Luxury Homes of Northern Colorado
PO Box 271969
Fort Collins, Colorado 80527
•
U
Attn: Matt Tschetter
Re: Drilled Pier Observation
4�1203 Mountain Home Driver
Lemay Avenue Estates
Northern Colorado Geotech Project No. 063-11
On February 4, 2013, a representative of Northern Colorado Geotech performed a drilled pier
observation for a residence under construction at the above referenced address in Fort Collins,
Colorado.
The drilled piers were observed for pier diameter, length, bearing strata, plumb, and condition. We
observed piers along the north and southwest corner of basement. Piers were observed to be 12-inch
diameter and 35 feet in length at the locations observed. Groundwater was encountered during the
drilling, and placement of concrete was accomplished by means of a concrete pump truck as each
pier was drilled. It is our opinion that the drilled piers we observed were constructed in general
accordance with the geotechnical engineering report recommendations (Northern Colorado Geotech
Project No.063-11, dated September 5, 2012).
If you have any questions about this letter or if we may be of further assistance, please do not hesitate
to contact us at (97Q1.,1+ &--9244.
Sincerely,
NORT / RI
Doug L g
President
l� �O Ca c`
G. Weeks, R?EQ1 L
'resident rL?
A d esseer(2Y; 01�' F
1
Northern
• Colorado
Geotech
February 12, 2013 2956 29th Street, Unit 21
Greeley, Colorado 80631
Phone: (970) 506-9244
Fax: (970) 506-9242
Luxury Homes of Northern Colorado
PO Box 271969
Fort Collins, Colorado 80527
•
is
Attn: Matt Tschetter
Re: Foundation Excavation Observation
1203 Mountain Home Drive
Lemay Avenue Estates
Northern Colorado Geotech Project No. 063-11
On' January 29, 2013 a representative of Northern Colorado Geotech performed .an excavation
observation for a residence under construction at the above referenced site in Fort Collins, Colorado.
The soil exposed at the upper and lower foundation level consisted of lean clay with sand. These
materials are similar to those encountered by Northern Colorado Geotech during our subsurface
exploration at the site (Project No. 063-11, dated September 5, 2012). Based on our observations
and the recommendations of the geotechnical engineering report, it is our opinion that the proposed
residence should be supported by a drilled pier .foundation system. The foundation should be
designed in accordance with the recommendations and specifications provided in the geotechnical
engineering report.
Bedrock was encountered within 2 feet of the lower foundation level. Therefore we recommend the
installation of an exterior perimeter drain around the lower level of the structure. The dewatering
system should be constructed in accordance with recommendations of the geotechnical engineering
report.
If you have any questions about this letter or if we may be of further assistance, please do not hesitate
to contact us at (97D4,AQ5-9244.
NORTHE
Doug Lea
President
X
by' G
eks2 'P,,EE .".�
dent 'Q
iID
E
11
ADVANCED
ENGINEERING, LLC
STRUCTURAL DRAINAGE DRAFTING
March 4, 2013
Mr. Matt Tschetter
Luxury Homes of Northern Colorado
P.O. Box 271969
Ft. Collins, CO 80527
RE: Lot 47 Lemay Avenue Estates, 1203 Mountain Home Drive, Ft. Collins, Colorado
Advanced Engineering, LLC Project Number 1771-01-04B
Dear Mr. Tschetter:
On February 25 and 26, 2013 we visually observed the foundation wall teinfotdWplaced in the
forms for the residence being constructed at the above referenced site: It is our opinion the
reinforcement was in general conformance with our Foundation Plan, Project Number 1771-01-04A,
and our recommendations for field modifications as required by site conditions.
We also observed the UFER ground rod was embedded in the concrete at the northeast corner of the
foundation.
The conclusions presented in this letter are not intended to cover structural items other than those
listed, site grading/elevations, setbacks, subsurface soil conditions, or architectural features of the
building. Thank you for the opportunity to serve you, feel free to call if you have any questions.
Sincerely,
Advanced Engineering, LLC
Jason E. Baker, P.E.
OQP•N•E
33739
.,3-8-13
146 Barberry Place, Loveland, Colorado 80537 Telephone 970-278-1909 Fax 970-278-1910
n
U
ADVANCED
ENGINEERING, LLC
STRUCTURAL DRAINAGE DRAFTING
March 11, 2013
Mr. Matt Tschetter
Luxury Homes of Northern Colorado
P.O. Box 271969
Ft. Collins, CO 80527
RE: Lot 47, Lemay Avenue Estates, 1203 Mountain Home, Ft. Collins, Colorado
Advanced Engineering, LLC Project Number 1771-01-04C
Dear Mr. Tschetter:
On March 5 and 7, 2013 we visually observed the exterior pe�rnneter drain and�damp proofinglfor
the residence being constructed at the above referenced site. It is our opinion the perimeter drain is
in general conformance with the soils report by Northern Colorado Geotech, Project Number063-11,
dated September 5, 2012.
The conclusions presented in this letter are not intended to cover items other than those listed, site
grading/elevations, setbacks, subsurface soil conditions, structural, or architectural features of the
building. Thank you for the opportunity to serve you, feel free to call if you have any questions.
Sincerely,
Advanced Engineering, LLC
Jason E. Baker, P.E.
Pp0 REG��.,
nN.E
33739
3— 13 /3.•��
► !ONN-�
146 Barberry Place, Loveland, Colorado 80537 Telephone 970-278-1909 Fax 970-278-1910
ADVANCED
• �ENGINEERINC39 LLC
STRUCTURAL DRAINAGE DRAT-TING
March 20, 2013
Mr. Matt Tschetter
Luxury Homes of Northern Colorado
P.O. Box 271969
Ft. Collins, CO 80527
RE: Lot 47, Lemay Avenue Estates, 1203 Mountain Home, Ft. Collins, Colorado
Advanced Engineering, LLC Project Number 1771-01-04D
Dear Mr. Tschetter:
On March 18 & 19, 2013 we visually observed the[reinforcing and decking foi the structural floor.
It is our opinion the wall and structural floor reinforcement were in general conformance with our
Foundation Plan, Project Number 1771-01-04A.
• The conclusions presented in this letter are not intended to cover structural items other than those
listed, site grading/elevations, setbacks, subsurface soil conditions, or architectural features of the
building. Thank you for the opportunity to serve you, feel free to call if you have any questions.
•
Sincerely,
Advanced Engineering, LLC
Jason E. Baker, P.E.
'p0 RE.
EG�S
,► 33739
�S/nnin�•EN�\�
146 Barberry Place, Loveland, Colorado 80537 Telephone 970-278-1909 Fax 970-278-1910 .