HomeMy WebLinkAbout925 W Lake St - Special Inspections/Field Verification - 07/18/2013Islamic Center of Fort Collins
Permit # B1111384
Building Department Required Docs
Table of Contents {jam
1) Welding and Bolting Inspections
ections
J�
2) Balance Report
j3)-Elevator-lnspection (TO -COME- TT RELA )
Please call me with any Questions,
Matt Brown
Brinkman Construction
970-219-0048
PROJECT: ISLAMIC CENTER OF FORT COLLINS
AIR TERMINAL
TEST REPORT
SYSTEM: EVAP-1
NOTES:
PAGE: 09
PROJECT: ISLAMIC CENTER OF FORT COLLINS
AIR TERMINAL
TEST REPORT
SYSTEM: EVAP-2
NOTES:
PAGE: 10
FAN TEST
REPORT
PROJECT: ISLAMIC CENTER OF FORT COLLINS
FAN NUMBER
EF-1
EF-2
UNIT DATA
UNIT DATA
UNIT DATA
MANUFACTURER
PENNBARRY
PENNBARRY
MODEL
Z1215TDA
Z121 STDA
SERIAL
H12SZ77966
H12SZ77967
DESIGN CFM
400 CFM @ 0.375" ESP
400 CFM @ 0.375" ESP
MOTOR DATA
MOTOR DATA
MOTOR DATA
MANUFACTURER
FASCO
FASCO
MOTOR HP
RPM
1/5
1050
1/5
1050
PHASE
TYPE
1
1-126131
1
U26B1
S.F.
FRAME
1
N/G
1
N/G
VOLTS
AMPS
115
3.5
115
3.5
DRIVE DATA
DRIVE DATA
DRIVE DATA
MOTOR DRIVE
BORE
DIRECT DRIVE
DIRECT DRIVE
FAN DRIVE
BORE
NO. BELTS
SIZE
DRIVE CHANGE
ROTATION
STARTER DATA
STARTER DATA
STARTER DATA
MFG.
MODEL
NONE
NONE
SIZE
RANGE
SET AT (AMPS)
REQ THERM
THERMAL PROTEC11ON
TEST DATA
TEST DATA
TEST DATA
CFM
VOLTS
895
118
555
118
RPM
AMPS I
DIRECT DRIVE
3.1
DIRECT DRIVE 12.4
NOTES:
-0.14" v
NAC -0.10" rJ +0.30"
PAGE: 11
FAN TEST
REPORT
PROJECT: ISLAMIC CENTER OF FORT COLLINS
FAN NUMBER
EF-3
EF-4
UNIT DATA
UNIT DATA
UNIT DATA
MANUFACTURER
PENNBARRY
PENNBARRY
MODEL
ZJ1
ZJ1
SERIAL
H12SZ779841
H12SZ779601
DESIGN CFM
90 CFM @ 0.375" ESP
50 CFM @ 0.375" ESP
MOTOR DATA
MOTOR DATA
MOTOR DATA
MANUFACTURER
FASCO
FASCO
MOTOR HP
RPM
N/G
1550
N/G
1550
PHASE
TYPE
1
U63SB1
1
U635131
S.F.
FRAME
1
N/G
1
N/G
VOLTS
AMPS
115
1.4
115
1.4
DRIVE DATA
DRIVE DATA
DRIVE DATA
MOTOR DRIVE
BORE
DIRECT DRIVE
DIRECT DRIVE
FAN DRIVE
BORE
NO. BELTS
SIZE
DRIVE CHANGE
ROTATION
STARTER DATA
STARTER DATA
STARTER DATA
MFG.
MODEL
NONE
NONE
SIZE
RANGE
SET AT (AMPS)
REQ THERM
THERMAL PROTECTION
TEST DATA
TEST DATA
TEST DATA
CFM
VOLTS
130
117
165
119
RPM
AMPS
DIRECT DRIVE
1.4
DIRECT DRIVE
1.4
NOTES:
PAGE: 12
FAN TEST
REPORT
PROJECT: ISLAMIC CENTER OF FORT COLLINS
FAN NUMBER
EF-5
EF-6
UNIT DATA
UNIT DATA
UNIT DATA
MANUFACTURER
PENNBARRY
PENNBARRY
MODEL
Z10S
Z1Z1 S
SERIAL
H12SZ77972
H12ZS77968
DESIGN CFM
250 CFM @ 0.25" ESP
709 CFM @ 0.375" ESP
MOTOR DATA
MOTOR DATA
MOTOR DATA
MANUFACTURER
FASCO
FASCO
MOTOR HP
RPM
N/G
1050/1550
1/5
1050
PHASE
TYPE
1
1-1905131
1
U26B1
S.F.
FRAME
1
N/G
1
N/G
VOLTS
AMPS
115
2.5/3.6
115
13.5
DRIVE DATA
DRIVE DATA
DRIVE DATA
MOTOR DRIVE
BORE
DIRECT DRIVE
DIRECT DRIVE
FAN DRIVE
BORE
NO. BELTS
SIZE
DRIVE CHANGE
ROTATION
STARTER DATA
STARTER DATA
STARTER DATA
MFG.
MODEL
NONE
NONE
SIZE
RANGE
SET AT (AMPS)
REQ THERM
THERMAL PROTECTION
TEST DATA
TEST DATA
TEST DATA
CFM
VOLTS
340
119
710
118
RPM
AMPS
LOW SPEED
1.2
DIRECT DRIVE 13.0
NOTES:
ATMOS (*;7 +0.04" ATMOS v +0.03"
PAGE: 13
FAN TEST
REPORT
PROJECT: ISLAMIC CENTER OF FORT COLLINS
FAN NUMBER
SF-1
UNIT DATA
UNIT DATA
UNIT DATA
MANUFACTURER
PENNBARRY
MODEL
Z121 STDA
SERIAL
H12SZ77969
DESIGN CFM
709 CFM @ 0.50" ESP
MOTOR DATA
MOTOR DATA
MOTOR DATA
MANUFACTURER
FASCO
MOTOR HP
RPM
1/5
1050
PHASE
TYPE
1
U26131
S.F.
FRAME
1
N/G
VOLTS
AMPS
115
3.5
DRIVE DATA
DRIVE DATA
DRIVE DATA
MOTOR DRIVE
BORE
DIRECT DRIVE
FAN DRIVE
BORE
NO. BELTS
SIZE
DRIVE CHANGE
ROTATION
STARTER DATA
STARTER DATA
STARTER DATA
MFG.
MODEL
NONE
SIZF
RANGE
SET AT (AMPS)
REQ THERM
THERMAL PROTECTION
TEST DATA
TEST DATA
TEST DATA
CFM
VOLTS
780
117
RPM
AMPS
LOW SPEED
2.7
-0.22" v
ATMOS
NOTES:
PAGE: 14
FAN TEST
REPORT
PROJECT: ISLAMIC CENTER OF FORT COLLINS
FAN NUMBER
HRV-1 SUPPLY
HRV-1 RETURN
UNIT DATA
UNIT DATA
UNIT DATA
MANUFACTURER
SEMCO
SEMCO
MODEL
FV3000S-4RT4AB
FV3000S-4RT4AB
SERIAL
59056/M067294-01
59056/M067294-01
DESIGN CFM
2,800 CFM @ 1.50" ESP
3,074 CFM @ 0.50" ESP
MOTOR DATA
MOTOR DATA
MOTOR DATA
MANUFACTURER
WEG
WEG
MOTOR HP
RPM
3
1760
3
1760
PHASE
TYPE
3
N/G
3
N/G
S.F.
FRAME
1.15
182T
1.15
182T
VOLTS
AMPS
208-230/460
8.98-8.12/4.06
208-230/460
8.98-8.12/4.06
DRIVE DATA
DRIVE DATA
DRIVE DATA
MOTOR DRIVE
BORE
AK46
1 1/8"
AK46
1 1/8"
FAN DRIVE
BORE
AK44
3/4"
AK44
314"
NO. BELTS
SI2E
ONE
A58
ONE
A58
DRIVE CHANGE
ROTATION
AK54
CORRECT
N/A
CORRECT
STARTER DATA
STARTER DATA
STARTER DATA
MFG.
MODEL
ABB
MS116
ABB
MS116
SIZE
RANGE
Al2-30-10
6.3-10
Al2-30-10
6.3-10
SET AT (AMPS)
REO THERM
9.0
9.0
THERMAL PROTECTION
YES
YES
TEST DATA
TEST DATA
TEST DATA
CFM
VOLTS
2760
205/204/204
3129
205/204/204
RPM
AMPS
1580
7.4/7.5/7.2
1740
9.6/9.7/9.2
E)o-1HEATAUST ATMOS -0.78" -1.44" rJ ATMOS
E)CHANG
SUPPLY -0.67" FILTER -1.08" rJ +0.03" HEAT +0.14"
NOTES: *1 UNIT HAD TO BE JUMPERED TO BALANCE, NOT RUNNING AT TIME OF TEST
PAGE: 15
PROJECT: ISLAMIC CENTER OF FORT COLLINS
AIR TERMINAL
TEST REPORT
SYSTEM: EXHAUST & HRV
mm
��,'=
�M
•
mmmmmmm
®
Wm_-
mwmm
mw
-.
NOTES: *1 NO MANUAL DAMPERS INSTALLED
*2 DIRECT DRIVE SINGLE SPEED UNIT
PAGE: 16
BALANCE REPORT
PROJECT:
ISLAMIC CENTER OF
FORT COLLINS
925 WEST LAKE STREET
FORT COLLINS, CO
PREPARED FOR:
AMER/CAN PLUMBING
REPORT ISSUE DATE: 4310
JULY 18, 2013 4I I I�
AR/ PROJECT NO.:
13302
PREPARED BY:
` 747 Sheridan Unit 88
r��3t :ram
.,.. Lakewood, Colorado 80214
Phone: (303) 232-5145
Fax: (303) 232-1238
e-mail: airright@aoLcom
http://www. air-righ tinc. com
TEST, ADJUST, AND BALANCE REPORT
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND
WAS OBTAINED IN COMPLIANCE WITH NEBB PROCEDURAL STANDARDS. ANY VARIANCES FROM THE
DESIGN REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS REPORT IS CERTIFIED TO BE
ACCURATE AND COMPLETE, TO THE EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED
THROUGHOUT THIS SURVEY.
THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NEBB
'PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS -
AND THE PROJECT SPECIFICATIONS.
,CERTIFIED BY.- r DATE: JULY 18, 2013
THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NEBB
-PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS -
AND THE PROJECT SPECIFICATIONS.
CERTIFIED BY.
DATE.
AIR -RIGHT WARRANTS THAT THE AIR AND HYDRONIC SYSTEM EVALUATED DURING THIS SURVEY
IS OPERATING AT THE SPECIFIED LEVELS AS SHOWN WITHIN THIS REPORT, AT AND ONLY AT THIS TIME.
AIR -RIGHT MAKES NO OTHER WARRANTIES, STATED OR IMPLIED, CONCERNING THE CONTINUED
PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS EQUIPMENT PAST THIS TIME.
ARI TECHNICIAN(S):
ARI NEBB TAB SUPERVISOR: TIMOTHY A. TOPPING REG. NO. 2589 CERTIFICATION EXPIRATION: 03131114
(,nMoTHY A.TOPPING
E B B 2589TIONi2se9 3cp aatns /
747 SHERIDAN BLVD UNIT 8B, LAKEWOOD, COLORADO 80214, PHONE:(303) 232 S14S FAX:(303) 232-1238
$rTABLE OF CONTENTS
DOCUMENT PAGE
COVER PAGE .
1
TAB CERTIFICATION
2
TABLE OF CONTENTS.
3
AIR APPARATUS TEST REPORT RTU-1
4
AIR APPARATUS TEST REPORT RTU-2
5
FAN TEST REPORT EVAP-1 & EVAP-2.
6
AIR TERMIAL TEST REPORT SUPPLY.
7-10
FAN TEST REPORT EF-1 & EF-2
11
FAN TEST REPORT EF-3 & EF-4
12
FAN TEST REPORT EF-5 & EF-6
13
FAN TEST REPORT SF-1
14
FAN TEST REPORT HRV-1
15
AIR TERMINAL TEST REPORT.
16
DRAWING
17-18
PROJECT: ISLAMIC CENTER OF FORT COLLINS
AIR HANDLER UNIT DATA
MANUFACTURER
TRANE
MODEL
YSC092F3RDA01DOBlA
SERIAL
123810101 L
FAN TYPE
FC
DESIGN CFM
3,375 CFM @ 1.60" ESP
MIN OSA
910 CFM
STARTER DATA
MANUFACTURER
FACTORY PACKAGE
MODEL
SIZE/THERMAL NO.
RANGE
SET AT (AMPS)
REQ.THERMAL
RATING (AMPS)
AIRFLOW DATA
SUPPLY CFM
2,942
OSA CFM
923
RETURN CFM
2,019
FILTER
-0.18" -0.37"
COIL
NOTES: *1 UNIT AT MAX AMPS
AIR APPARATUS
TEST REPORT
UNIT: RTU-1
MOTOR NAMEPLATE DATA
MANUFACTURER
MARATHON
HP
R.P.M.
1
1725
PHASE
FRAME
3
56
S.F.
TYPE
11.15
N/G
VOLTS
AMPS
200-230/460
3.6-3.5/1.7
THERMALLY PROTECTED
DRIVE DATA
MOTOR DRIVE
1VL34
MOTOR BORE
5/8"
FAN DRIVE
AK59
FAN BORE
1"
NO. BELTS & SIZE
ONE A)G5
ROTATION
CORRECT
DRIVE CHANGE
WA
TEST DATA
INITIAL
FINAL
FAN R.P.M.
835
VOLTAGE
205/205/205
AMPERAGE
3.6/3.6/3.6
�j +0.36"
PAGE: 04
m
PROJECT: ISLAMIC CENTER OF FORT COLLINS
AIR HANDLER UNIT DATA
MANUFACTURER
TRANE
MODEL
YSCO92F3RHA01DOB1A
SERIAL
123810117L
FAN TYPE
FC
DESIGN CFM
3,375 CFM @ 1.60" ESP
MIN OSA
870 CFM
STARTER DATA
MANUFACTURER
FACTORY PACKAGE
MODEL
SI2FJTHERMAL NO.
RANGE
SET AT (AMPS)
.REQ. THERMAL
RATING (AMPS)
AIRFLOW DATA
SUPPLY CFM
3,485
OSA CFM
877
RETURN CFM
2,608
FILTER
-0.16" -0.38"
COIL
NOTES:
AIR APPARATUS
TEST REPORT
UNIT: RTU-2
MOTOR NAMEPLATE DATA
MANUFACTURER
MARATHON
HP
R.P.M.
1
1725
PHASE
FRAME
3
56
S.F.
TYPE
1.15
N/G
VOLTS
AMPS
200-230/460
3.6-3.5/1.7
THERMALLY PROTECTED
DRIVE DATA
MOTOR DRIVE
1VL34
MOTOR BORE
5/8"
FAN DRIVE
AK59
FAN BORE
1"
NO. BELTS & SIZE
ONE AXG5
ROTATION
CORRECT
DRIVE CHANGE
N/A
TEST DATA
INITIAL
FINAL
FAN R.P.M.
835
VOLTAGE
205/205/205
AMPERAGE
3.7/3.7/3.8
+0.40"
PAGE: 05
FAN TEST
REPORT
PROJECT: ISLAMIC CENTER OF FORT COLLINS
FAN NUMBER
EVAP-1
EVAP_2
UNIT DATA
UNIT DATA
UNIT DATA
MANUFACTURER
CHAMPION COOLER
CHAMPION COOLER
MODEL
15012W
15012W
SERIAL
XG7140002
XG7140001
DESIGN CFM
13,000 CFM @ 0.50" ESP
13,000 CFM @ 0.50" ESP
MOTOR DATA
MOTOR DATA
MOTOR DATA
MANUFACTURER
BALDOR
BALDOR
MOTOR HP
RPM
7.5/1.9
1725/850
7.5/1.9
1725/850
PHASE
TYPE
3
N/G
3
N/G
S.F.
FRAME
1.15
215T
1.15
215T
VOLTS
AMPS
208/230
20/7.5
208/230
20/7.5
DRIVE DATA
DRIVE DATA
DRIVE DATA
MOTOR DRIVE
BORE
2VP42
1 WIT'
2VP42
1 3/8"
FAN DRIVE
BORE
2BK190
SK1 3/16"
2BK190
SKI 3/16"
NO. BELTS
SIZE
TWO
B103
TWO
B103
DRIVE CHANGE
ROTATION
16.0X2BSK
CORRECT
16.0X2BSK
CORRECT
STARTER DATA
STARTER DATA
STARTER DATA
MFG.
MODEL
SQUARE D
8536SC031-130
SQUARE D
8536SC03H30
SIZE
RANGE
1
9-27
1
9-27
SET AT (AMPS)
REQ THERM
20
20
THERMAL PROTECTION
YES
YES
TEST DATA
TEST DATA
TEST DATA
CFM
VOLTS
13,120
205/205/205
13,040
205/205/205
RPM
AMPS
530
14.0/14.1/13.8
530
14.4/14.4/13.8
-0.15" v
+0.03"
NOTES:
-0.15" * +0.03"
PAGE: 06
PROJECT: ISLAMIC CENTER OF FORT COLLINS
AIR TERMINAL
TEST REPORT
SYSTEM: RTU-1
NOTES: *1 UNIT AT MAX AMPS
PAGE: 07
PROJECT: ISLAMIC CENTER OF FORT COLLINS
AIR TERMINAL
TEST REPORT
SYSTEM: RTU-2
SYSTEM
TERMINAL
DESIGN
INITIAL
FINAL
NOTES
NO
TYPE
SIZE
AK
VEL
CFM
VEL
CFM
VEL
CFM
1
CD
24"X24"
100
110
2
CD
24"X24"
100
95
3
CD
24"X24"
150
150
4
CD
24"X24"
250
240
5
CD
24"X24"
150
150
6
CD
24"X24"
150
155
7
CD
24"X24"
150
155
8
CD
24"X24"
150
165
9
CD
24")Q4"
250
245
10
CD
24"X24"
200
200
11
CD
24"X24"
150
165
12
CD
24"X24"
150
150
13
CD
24"X24"
150
140
14
CD
24"X24"
150
150
151
CD
24"X24"
200
210
16
CD
24"X24"
200
215
17
CD
24"X24"
200
210
18
CD
24"X24"
175
210
191
CD
24"X24"
100
105
20
CD
24"X24"
125
135
21
CD
24"X24"
125
130
TOTAL
3375
3485
NOTES:
PAGE: 08