HomeMy WebLinkAbout4045 Stoney Creek Dr - Disclosures/Air Sealing - 05/30/2013[3l209 o(Z9 BUILDING LEAKAGE TEST Date of Test: 5-30-13 Customer: Spanjer Const Test Results 1. Airflow at 50 Pascals: (50 Pa = 0.2 w.c.) 2. Leakage Areas: 3. Building Leakage Curve: Test File: spanjer 4045 Stoneycreek BD Technician: Paul Higman Project Number: Building Address: 4045 Stoneycreek FC, CO 80525 998 CFM50 (+/- 0.9 %) 2.44 ACH50 0.3600 CFM50/ft2 floor area 100.3 in2 ( +/- 3.9 %) Canadian EgLA @ 10 Pa 52.6 in2 (+/- 6.3 %) LBL ELA @ 4 Pa Flow Coefficient (C) = 73.5 ( +/- 9.9 %) Exponent (n) = 0.667 ( +/- 0.026 ) Correlation Coefficient = 0.99463 4. Test Settings: Test Standard: CGSB Test Mode: Depressurization Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 52.1 CFM 0.13ACH 2. Estimated Design Infiltration Rate: Winter: 88.8 CFM 0.22 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Summer: 49.8 CFM 0.12 ACH ..k BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 5-30-13 Test File: spanjer 4045 Stoneycreek BD Building Information Location Climate Information Volume 24588 Surface Area Floor Area 2772 Height 16 # of Bedrooms 5 # of Occupants Year of Construction 2013 Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6020 Cooling Degree Days 287 Design Winter Wind Speed 9.0 mph Design Summer Wind Speed 7.0 mph Design Winter Temp Diff 69 deg F Design Summer Temp Diff 16 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 5-30-13 Test File: spanjer 4045 Stoneycreek BD Depressurization Test: Environmental Data Indoor Temperature (OF) Outdoor Temperature (OF) 67.0 77.0 Data Points - Data Entered Manually Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration -0.7 n/a n/a -60.0 -59.0 36.6 1100 1110 -0.4 Ring A -54.3 -53.3 30.4 1004 1013 -2.7 Ring A -50.1 -49.1 30.2 1001 1010 2.4 Ring A -45.5 -44.5 26.3 936 945 2.2 Ring A -40.0 -39.0 198.2 834 842 -0.5 Ring B -36.2 -35.3 166.9 766 773 -2.2 Ring B -30.1 -29.2 142.8 709 716 2.8 Ring B -25.1 -24.2 105.8 611 617 0.4 Ring B -20.5 -19.6 73.7 511 516 -3.3 Ring B -1.2 n/a n/a Deviations from Standard CGSB - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 5-30-13 Test File: spanjer 4045 Stoneycreek BD Comments House WRT Garage =-49.8pa