Loading...
HomeMy WebLinkAbout5103 Star Dust Ln - Disclosures/Mechanical - 04/18/2013City of Fort Collins S FO �7 Residential Mechanical Systems Performance Report This form is a record of testing targets and results, with Pass/Fail outcomes. For information on measurement tools and testing techniques, see the'Residamial New Construction Mechanical Systems Testing Guide.'The guide and this form maybe periodicalty updated; cheek the Building Services web site for the cunem version. This form must be completed and signed by an ^Approved Agency; and submitted to Building Services as a requirement for receiving a C.O. Color key Bath exhaust Pass Airflow measurement method 'tdti(ryYam rse Temperature of air through - F - Indicated flow to Volumetric flow multiplier measurement tool y + � ... , (@ SOOT, air temperature Measured Exhaust Airflow Operation Minimum Design Ind cated Exhaust Pickup Location Intermtltent or Airflow Airflow Flow Volumetric Flow Pass .Fall Continuous Requirement (CFM (CFM) (CFM 5,000') (CFM SOOT) 5000) Kitchen exhaust Oven fuel �,,,^Electnc Exhaust airflow [� WA.-- Kitchen hood does not vent outside OperaOon 'intemlfttant.__ Cemtnoq.gs Minimum exhaust airflow requirement ¢+ i� `- ;'CFM5000' airflow Airflow measurement method L�^"- ggaive•tlow txtod -..�± G; h}'QaHpBi(l3 sir Temperature of air through " F Indicated flow to Volumetric flow multiplie measurement tool--�G 5000', air temperature�.C"� Aicated flow h' - SP'S)t ` CFM Volumetric fbvr '? ';, CFM SOOT Pass11 Fail Wing rotes (fan speed masking, ,, flow out of range - .) - MecMni Srsw m Pwfonnarca TestM Subn*W Fm other than sub -structural floor exhaust n exhaust airflow requirement CFM 5000' Indicated to Measured Airflow Design Airflow Measurement Measurement Location. Volumetric Flow Indicated Flow Volumetric Flow PasslFell (CFN 5000') Method Air Temperature (F) Multiplier (CFM) (CFM 5000 ) .. � i Total exhaust airflow �7fA CFI Y Total supply airflow' k0ad systems In which supply airflow is circulated by the air handler fan, fan speed for measurement wg ` ,:>' ia(F, .:.4: , "eve "Ar,' tlancadairflow In balanced systems Average of measured supp a-_";_ Target flow 9 and exhaust Ilo`� r } .. rIa CFM 5000' (average./- ` CFM 5000' ,1 '� Pass Fail Substructural floor exhaust WA — rw sub -structural goon exhaust system Design airflow CFM 5000' Measured airflow Airflow measurement method �— ��imhr�ge .:,._ OaY 1ketllpb'!41sodf'I,tettpbatharsg Temperature of air through - Indicated Dow to Volumetric flow muINPI1e measurement tool -' or r "F _ d 5000, air Indicated flow s';.. , , r CFM Volumetric flow �•: " . CFM 5000' Pass Fail - Temperature of air through G] WA — no ductwork or no dug 1 measurement tool outside corxlfliorxtd space ', F House conditioned Moor area sl Indicated flow to Volumetric flow perat let Volumetric air temperatur Maximum Allowed Duct Leakage Measured Duct Leakage Test Parameter and Conditions Normalized Leakage (CFM25 / 100 st) Absolute Leakage (CFM25) Indicated Flow (CFM25) Volumetric Flow (CFM25 5000) Measurement Timing Air Handler Pw/Fall Total leakage Rough -in Excluded 4 Q: S Total leakage Rough -in Included 6 # - Total leakage Complete Included 12 Leakage to outdoors Complete Included 8 WON" Sntemr Para =. Tasbq SL&rgt l F. V20/2060e 2016 r- 1 Filter type 11 BrandEXi-� Static pressures (OPTIONAL) Cooling coil installed _ Y _ N Mode: _ Heating _Cooling Continuous Fan Fan speed tap Humidifier bypass _ Open _Closed - All registers open P.- AP filter = Type/style Thickness Inches / P=- t Z P-+ MERV (optional AP AC coil = P = + , —?6 I AP Total ESP = �- Cooling: Measured air flow through indoor coil using flow grid j. WA - no AC system instaliec Design cooling airflow L` 'i ` �u....-CFM 5000' Target airflow limits (design +/- 13Y) fE ( CFM 5000' Measured airflow Cooling fan speed tap ,17 .. _ �1 ,. 7-77-1 Temperature of air through ; w r' measurement tool ,� ' -(F NSOP� Pa - TFSOP. :,' # Pa Measured aiMow, no adjustments or correction CFM Volumetric flow : `f .CFM 5000' .,.Pass Flow grid plate size Indicated flow to @ 5000', a flow multiplier @5000'air temperature Flow Resistance Correction Facto' J Adjusted (indicated) airflow ; / / / if CFM mm Fail Heating: Gas manifold pressure OEM manifold pressure IW�specification, C Target manifold aprressure limits (spec +/- 5Y.) Measured manifold pressure 3/ IWC -. Pass Heating: Temperature rise ® OEM temperature rise limits F Measured temperature rise Return au F Temp rise F Supply air 4F Pass + Fail 0 IWC Fail Caution: Temp rise within 10 F of top of range McCi "Syst Px� Tesft&&V Fro vM120609 3ore (This section under development, not yet being enforced) Register air flows MEW ® All registers are cut through finish materials and moving air.., Pass Fail (Remainder of section under development, not yet being enforced) Pressure balance Pressure diflerence limit, room -to -core 'w }ib ' gkti: Pa Room Measured pressure pass Fail drop (Pa) Wclunical Systems Pedwmance Testkg Subminal Form V20120608 406 , W WA - no natural draft combustion appliances Worst -ewe depressurization testing House setup pplianees Z pressure BPI depressurization limit Pa wrt outside Measured net CAZ depressurization Pa wrt outside OK (less negative) I Caution (more negative) illage BPI maximum limit seconds Measured spillage duration seconds Pass . duration not exceeding limit sft pressure BPI limit Pa wrt CAZ Measured Pa wrt CAZ Pass - pressure more negative than limit I concentration in undiluted flue gas BPI maximum limit ppm Measured CO ppm Pass . CO level not exceeding limit Caution . CO level 25 to 100 ppm F Mechanical Systems Pedormar Twtup eubmbrat Fam VM120608 S016 System controls operating per design Intent ew System Pass Fall Local exhaust Whole -house ventilation Substructural floor exhaust It1-eating Cooling. Approved Agency (technician performing inspection and testing documented on this form) Nam (Ord) Title .r Company -- Signature and Date d—, HVAC contractor (Fort Collins license holder) ® Name (print) Tine Company Signature and Date MeceM" Systems Performance Teeing SrNnmal Form V2o 12W88 6of6