HomeMy WebLinkAbout1721 Choice Center Dr - Correspondence/Building Code - 04/16/2013SSOE Group 3504 7th Avenue South V Birminghom, Al 35222 205.323.2373 T 205.322.2731 F ..ssoe.com April 16, 2013 Ms. Bronte Lake RE: The Commons Design Collective, Inc. Buildings 1 and 2 601 East Pratt Street Ft. Collins, Colorado Suite 300 Baltimore, Maryland 21202 Project Numbers Building 1: 012-00854-00 Building 2: 012-00858-00 Dear Bronte: This is to confirm that we approve the use of aluminum conductors for installation in Buildings 1 and 2 of The Commons in Fort Collins, Colorado subject to the following conditions: 1. Use of aluminum conductors is approved for feeders rated at 100 amps and larger as defined in specification section 260519, 3.1, A. 2. Aluminum conductors are not allowed for feeders or circuits rated less than 100 amps. 3. Conductor insulation shall comply with 260519, 3.2, B, C and D. 4. Aluminum conductors shall be sized for the overcurrent protection device at 75 degree C per NEC Table 310.16. If you have any questions please call me at 205-323-2373 extension 337 or e-mail me at woarkerCrDssoe.com. Sincerely, SSOE 55r� 6 O. Wade Parker Project Manager Copies to: Eric Farrington, Catamount Construction File: T10yEaI�OptV•OnALEtiF 3011BN4RNIF /IWCtl�UC101�D0IX making clients successful by soving them time, trouble, and money I 0009909