HomeMy WebLinkAbout7214 Crooked Arrow Ln - Disclosures/Air Sealing - 04/04/2013BUILDING LEAKAGE TEST Date of Test: 4i412013 Technician: Doug Groff Test File: Shadow Creek Blower Door Customer: Shadow Creek Homes Building Address: 7214 Crooked Arrow Lane 7600 E. Orchard Road Fort Collins, CO 80525 Greenwood Village, Colorado 80111 Phone Test Results 1. Airflow at 50 Pascals (50 Pa = 0.2 w.c.) 2. Leakage Areas: 3. Minneapolis Leakage Ratio 4. Building Leakage Curve: 5. Test Settings: 1049 CFM (+i- 0.3 %) 2.27 ACH 0.33 CFM per f12 floor area 92.7 in2 (+/- 4.1 %) Canadian EgLA @ 10 Pa 45.1 in2 (+/- 6.3 %) LBL ELA @ 4 Pa 0.15 CFM50 per f12 surface area Flow Coefficient (C) = 56.6 ( +/- 9.8 %) Exponent (n) = 0.746 ( +/- 0-025 ) Correlation Coefficient = 0.99837 Test Standard: = CGSB Test Mode: = Depressurization Equipment = Model 3 Minneapolis Blower Door Infiltration Estimates 1_ Estimated Average Annual Infiltration Rate: 40.1 CFM 0.09 ACH 2. Estimated Design Infiltration Rate: Winter: 57.1 CFM 0.12ACH Summer: 34.0 CFM 0.07 ACH 3. Recommended Whole Building Mechanical 53.8 CFM Ventilation Rate: (based on ASHRAE 62.2) Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: IoF-3 L-d BUILDING LEAKAGE TEST Page 2 Date of Test: 4/4/2013 Test File: Shadow Creek Blower Door Building Conditions Inside Temperature: 66 deg F Heating Fuel: Gas Outside Temperature_ 6n deg F Heating Fuel Cost # of Stories 1.0 Heating Efficiency: Heating Degree Days: 6020 Wind Shield: M Cooling Fuel Cost: 9 of Occupants Cooling SEER: Cooling Degree Days: 287 4 of Bedrooms: 2.0 Volume: 27665 ft3 Ventilation Weather Factor: 0.87 Surface Area: 6783 ft2 Energy Climate Factor: 17.0 Floor Area: 3134 ft2 Design Winter Wind Speed: 9.0 mph Design Winter Temp Diff: 69 deg F Design Summer Wind Speed: 7.0 mph Design Summer Temp Diff: 16 deg F Comments G [.3,,�,,�- e- � C< �11�5 C% 1 Y, 5 1 a SO Pol. ZO 3 Z•d BUILDING LEAKAGE TEST Page 3 Date of Test: 4/4/2013 Test File: Shadow Creek Blower Door Data Points: Data Entered Manually INominat Temperature Buildng Fan Pressure Nominal Adjusted Fan Baseline Pressure (Pa) (Pa) Flow Flow % Error Configuration Std Dev (Pa) -3.8 Na +1- 0.00 -65.0 427.0 1220 1213 -0.6 Ring B -60.0 382-3 1155 1148 0.3 Ring B -55.0 333-9 1080 1074 0.6 Ring B -50.0 2B5.9 1000 994 0.5 Ring B -45.0 233.7 905 900 -0.9 Ring B 3 or-5 £-d Air Leakage BURGESS Property Organization HERS Nfl Shadow Creek Burgess Inc. Confirmed 7214 Crooked Arrow Lane 303-300-4527 414/13 Fort Collins, CO 80525 Robert Hutchinson Rater ID:7479033 CONSTRUCTION CONSULTANTS Weather:0enver, CO Builder INC. Plan # 1625 Shadow Creek Homes SINCE 1980 7214 Crooked Arrow Lane.btg Whole House Infiltration Blower Door Test Heating I Cooling Natural ACH 0.10 0.08 ACH @ 50 Pascats 2.17 2.17 CFM @ 25 Pascals 637; 637 CFM @ 50 Pascals 10001 1000 Eff. Leakage Area (sq.in) 54.91 54.9 Specific Leakage Area 0.000121 0.00012 EL.A/100 sf shell (sq.in) 0.81 ! 0.131 Duct Leakage Leakage to Outside Units Hvac CFM @ 25 Pascals 0. CFM25 / CFMfan 0.0000, CFM25 / CFA 0.0000 CFM per Std 152 N/A CFM per Std 152 / CFA j NIA CFM @ 50 Pascals i 0 Eff. Leakage Area (sq.in) 0.00 Thermal Efficiency N/A Total Dud Leakage Units ! CFM25/CFA Total Duct Leakage 0.0380 Ventilation Mechanical Exhaust Only Sensible Recovery Eff. (%) 0.0 Total Recovery Eff. (%) 0.0 Rate (cfm) 54 Hours/Day 24.0 Fan Watts 11.3 Cooling Ventilation Natural Ventilation ASHRAE 62.2 - 2010 Ventilation Requirements For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable Indoor Air Quality in Low -Rise Residential Buildings, a minimum of 54 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively, an intermittently operating mechanical ventilation system may be used if the ventilation rate is adjusted accordingly. For example, a 108 cfm mechanical ventilation system would need to operate 12 hours per day, as long as the system operates to provide required average ventilation once each hour. REM/Rate - Residential Energy Analysis and Rating Software v14.2 This information does not constitute any warranty of energy cost or savings. a 1985-2013 Architectural Energy Corporation, Boulder, Colorado. g•d BURGESS COLORADO DIVISION SHADOW CREEK HOMES, LLC 11 HERS THERMAL BYPASS FINAL INSPECTION 13j ADDRESS: 7214 Crooked Arrow Ln. DATE: 4/42013 CITY: Ft. Collins POM CONSTRUCTION COMMUNITY: Water Leaf - Ft. Collins JOB#: 1625 Plan CONSULT_AJWS BUILDER: Shadow Creek Homes, LLC INSPECTION ID#: 767379 INC. SINCE 1986 BCCI REP: Doug Graff303-59"267 STATUS: Passed ITEMS NOT COMPLETED: 0 REPAIR SUMMARY: ADDITIONAL 0 THERMAL BYPASS,0 FINAL Inspection Notes: 1 HOME CONFIRMED, STICKERS PRINTED 2 @:1000 CFM $ott-f155,C7� NIC Items: /-d CONSTRUCTION CONSULTANTS INC. SINCE 1996 COLORADO DIVISION SHADOW CREEK HOMES, LLC HERS FINAL INSPECTION ADDRESS: 7214 Crooked Arrow Ln. CITY: Ft. Collins COMMUNITY: Water Leaf - Ft. Collins BUILDER: Shadow Creek Homes, LLC BCCI REP: Doug Groff 303-598-8267 ITEMS NOT COMPLETED: 0 REPAIR SUMMARY: ENERGY 0 Inspection Notes: 1 Blower Door Test Passed @: 1000 CFM 2 Signed TBC checklist not required 3 home confirmed, stickers printed WC Items DATE: 4/4/2013 PO#: JOB#: 1625 Plan INSPECTION ID#: 767378 STATUS: Passed g•d