G LEAKAGE TEST
Date of Test: 3/21 /2013
Test File: DR Horton Blower door
Customer: DR Horton
7600 E Orchard Rd #350-S
Greenwood Village, Colorado 80111
Phone
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Areas:
3. Minneapolis Leakage Ratio:
4. Building Leakage Curve:
5. Test Settings:
Technician: Doug Groff
Building Address: 857 Campfire Drive
Fort Collins, Colorado 80524
1162CFM (+/-0.1%)
2.37 ACH
0.32 CFM per ft2 floor area
266.6 in2 (+/ 1.3 %) Canadian EgLA @ 10 Pa
223.3 in2 (+/ 2.0 %) LBL ELA @ 4 Pa
0.17 CFM50 per ft2 surface area
Flow Coefficient (C) = 636.5 ( +/- 3.0 %)
Exponent (n) = 0.154 ( +/- 0.008 )
Correlation Coefficient = 0.99644
Test Standard: = CGSB
Test Mode: = Depressurization
Equipment = Model 3 Minneapolis Blower Door
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 181.1 CFM
0.37 ACH
2. Estimated Design Infiltration Rate: Winter: 282.8 CFM
0.58 ACH
Summer: 168.3 CFM
0.34 ACH
3. Recommended Whole Building Mechanical 12.4 CFM
Ventilation Rate: (based on ASHRAE 62.2)
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2
Date of Test: 3/21/2013 Test File: DR Horton Blower door
Building Conditions
Inside Temperature:
72 deg F
Heating Fuel:
Gas
Outside Temperature:
52 deg F
Heating Fuel Cost:
# of Stories
1.0
Heating Efficiency:
Heating Degree Days:
6020
Wind Shield:
M
Cooling Fuel Cost:
# of Occupants
Cooling SEER:
Cooling Degree Days:
287
# of Bedrooms:
3.0
Volume:
29382 ft3
Ventilation Weather Factor:
0.87
Surface Area:
6819 ft2
Energy Climate Factor:
17.0
Floor Area:
3648 ft2
Design Winter Wind Speed:
9.0 mph
Design Winter Temp Diff:
69 deg F
Design Summer Wind Speed:
7.0 mph
Design Summer Temp Diff:
16 deg F
Comments Garage WRT House: 45.5 Pa @ 50 Pa
BUILDING LEAKAGE TEST Page 3
Date of Test: 3/21 /2013 Test File: DR Horton Blower door
Data Points: Data Entered Manually
Nominal Temperature
Building Fan Pressure Nominal Adjusted Fan Baseline
Pressure (Pa) (Pa) Flow Flow % Error Configuration Std Dev (Pa)
1.9
n/a
+/- 0.00
-65.0
46.8
1240
1216
0.1
Ring A
-60.0
45.7
1225
1202
0.1
Ring A
-55.0
44.1
1205
1182
-0.3
Ring A
-50.0
43.0
1190
1167
-0.1
Ring A
-45.0
41.9
1175
1153
0.2
Ring A
BURGESS COLORADO DIVISION
DR HORTON - COLORADO
HERS FINAL INSPECTION
BADDRESS: 857 Campfire Dr DATE:
CITY: Fort Collins PO#:
CONSTRUCTION COMMUNITY: Trail Head - Ft. Collins JOB#:
CONSULTANTS BUILDER: DR Horton - Colorado INSPECTION ID#:
SINCE . BCCI REP: Doug Groff 303-598-8267 STATUS:
ITEMS NOT COMPLETED: 0
REPAIR SUMMARY:
ENERGY 0
Inspection Notes:
1 Blower Door Test Passed @: 1190 CFM
2 HOME CONFIRMED, stickers printed
N/C Items:
3/21/2013
211823 ON
1886 Plan
705102
Passed
BURGESS
C
CONSTRUCTION
CONSULTANTS
INC.
SINCE 1986
COLORADO DIVISION
DR HORTON - COLORADO
HERS THERMAL BYPASS FINAL INSPECTION
ADDRESS:
857 Campfire Dr
CITY:
Fort Collins
COMMUNITY:
Trail Head - Ft. Collins
BUILDER:
DR Horton - Colorado
BCCI REP:
Doug Groff 303-598-8267
ITEMS NOT COMPLETED: 0
REPAIR SUMMARY:
ADDITIONAL
Inspection Notes:
No notes entered.
N/C Items:
0 THERMAL BYPASS,0
FINAL
DATE:'
3/21/2013
POM
JOBM
1886 Plan
INSPECTION ID#:
705101
STATUS:
Passed
Air Leakage
Property
Organization
DR Horton
Burgess Inc.
857 Campfire Drive
303-300-4527
Fort Collins, CO 80524
Robert Hutchinson
Weather: Denver, CO
Builder
Trail Head 1886
DR Horton
857 Campfire Drive.blg
Whole House Infiltration
HERS
Projected Rating
10/5/2012
Rating No: Worst Case
Scenario
RaterID:7479033
Blower Door Test
Heating I Cooling
CONSTRUCTION
CONSULTANTS
INC.
Natural ACH
ACH @ 50 Pascals
0.11
2.43
0.09
2.43
CFM @ 25 Pascals
758
758
CFM @ 50 Pascals
1190
1190
Eff. Leakage Area (sq.in)
65.3
65.3
Specific Leakage Area
0.00012
0.00012
ELA/100 sf shell (sq.in)
0.%
0.96
Duct Leakage Leakage to Outside Units
Hvac
CFM @ 25 Pascals
0
CFM25 / CFMfan
0.0000
CFM25 / CFA
0.0000
CFM per Std 152
N/A
CFM per Std 152 / CFA
N/A
CFM @ 50 Pascals
0
Eff. Leakage Area (sq.in)
0.00
Thermal Efficiency
N/A
Total Duct Leakage Units
CFM25/CFA
Total Duct Leakage
0.0241
Ventilation
Mechanical
Sensible Recovery Eff. (%)
Total Recovery Eff. (%)
Rate (cfm)
Hours/Day
Fan Watts
Cooling Ventilation
Exhaust Only
0.0
0.0
66
24.0
11.3
Natural Ventilation
ASHRAE 62.2 - 2010 Ventilation Requirements
SINCE 1986
For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable Indoor Air Quality in Low -Rise Residential
Buildings, a minimum of 66 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively, an
intermittently operating mechanical ventilation system may be used if the ventilation rate is adjusted accordingly. For example, a
133 cfm mechanical ventilation system would need to operate 12 hours per day, as long as the system operates to provide required
average ventilation once each hour.
REM/Rate - Residential Energy Analysis and Rating Software v14.2
This information does not constitute any warranty of energy cost or savings.
O 1985-2013 Architectural Energy Corporation, Boulder, Colorado.