August 3, 2012
River Rock Commons
520 North Sherwood
Fort Collins, Colorado 80521
Attention: Don Flick
Building Maintenance Committee
Subject: Structural Engineering Consultation
Deck Guardrail Post Replacement
River Rock Commons, 520 N. Sherwood
CTLIT Project Number: FC05954.000-501 L1
Dear Mr. Flick,
Per your request, we made a site visit to the site referenced above on Wednesday, August 1, 2012.
The purpose of our visit was to observe existing conditions of a deteriorated deck guardrail post and
recommend an appropriate structural repair.
Observations
The second story deck consists of 2x10 joists at 16" o.c. supported by a (2) 2x12 rim beam. The rim
beam is supported by 8" dia. log columns. The existing columns are continuous from the grade up
through the deck and extend 4'-0" above the joists. The columns also serve as posts for the
guardrail system. During our site visit, we observed the column in question at its guard rail
connection above the deck surface. We understand that it is your intent to remove and replace the
damaged section of column.
Discussion/Recommendations
We recommend removing the top portion of the column, beginning at about 2 inches above the
bottom of the rim beam, and replacing it with a new 8 inch diameter log post. The bottom of the post
should be squared to 4"x4", minimum. Two Simpson DTT2Z-SDS2.5 connectors should be installed
onto the existing 2x10 joist per the attached details to support the new rail post. The exposed end of
the existing column should be protected with sealant and ice/water shield.
Limitations
Our scope of services in this project is limited to the post referenced above. This report is based
upon our site observations, a review of the documents provided (if any), and our experience with
projects of this type. Unseen defects may exist which could affect the performance of the
structure. We believe this investigation was conducted with the level of skill and care used by
structural engineers practicing in this area at this time. No warranty, express or implied, is made.
Thank you for sel 0 TTHOMPSON for your engineering 41Vhen we can be of
additional servi O�plege./ec r� t the undersigned. O RF.G�
v:
very truly yo r� O -�� •� TH 'ST�9
CTLITHOM SQL, IN,G465 X : Reviewed By:
35177
Rae Doner, P 'r� ,OAIAI. G Wayne Thomp ��
Project Engineer Project Manager F'
SS/ONA� F�
351 Linden Street I Suite 140 1 Fort Collins, Colorado 80524
Telephone:970-206-9455 Fax:970-206-9441
INSTALL NEW SOLID BLOCKING
SO THAT BOLTS ARE
CENTERED IN POST, 48" LONG,
ATTACH WITH (20) 16d NAILS
EXISTING 2x10 DECK JOIST
NEW 2x10 BLOCKING, 45" LONG,
ATTACH WITH (20) Ibd NAILS
"A' NEW 8" DIA. POST, NOTCH TO MIN.
4x4 SQUARE BELOW DECKING
�— NOTCH POST TO ACCOMMODATE DECKING
B I I I BY / /— EXISTING (2) 2x12 RIM BEAM BEYOND
n
EXISTING DECKING
EXISTING 2x10 JOISTS 19 16" O.G.
(2) 51MP50N DTT2Z-SDS2.5 DECK POST
CONNECTORS, INSTALL PER MFR.
EXISTING 8" DIA. POST, CUT OFF TOP OF
P05T AND APPLY SEALANT AND ICE 4
WATER SHIELD TO EXPOSED END
ELEVATION VIEW
NEW 8" DIA. POST, NOTCH
TO MIN. 4x4 SQUARE BELOW
DECKING EXISTING 2x12 RIM
NEW SOLID BLOCKING, EXISTING l2) 2x12 RIM BEAM
48 LONG, ATTACH W/ 2 SQUARE
(20) lbd NAILS WASHERS 2" SQUARE
EXISTING � WASHER ,5QUA, NOTCH
TO MIN. 4x44 SQUARE
DECKING BELOW DECKING
EXISTING 2xl0 o o o ° o
DECK OIST
-
° o
I �
o O o o O
48" MIN
z REMOVE EXISTING
(2) SIMPSON DTT2Z-SD525
BLOCKING
DECK POST CONNECTORS,
v
INSTALL PER MFR.
(2) SIMPSON DTT2Z-SDS2.5
DECK POST CONNECTORS,
EXISTING (2) 2x12 RIM BEAM
INSTALL PER MFR.
REMOVE EXISTING RIM J015T FOR
NEW SOLID BLOCKING
ALL -THREAD INSTALLATION,
NOTCH TO HIDE BOLTS
EXISTING 2x10 DECK JOIST
EXISTING 8" DIA. POST, CUT OFF
SECTION B-B
TOP OF POST AND APPLY
SEALANT AND ICE 4 WATER SECTION A -A
(PLAN VIEW)
SHIELD TO EXPOSED END
River Rock Commons
520 N. Sherwood
Fort Collins
EFSTRUCTURAL
ENGINEERS
CTL 1 THOMPSON INCORPORATED I P:970-206-9455
351 Linden Street, Suite 140 F:970-206-9441
Fort Collins, CO 80524 www.ctIthornpsor.corn
DRAWN. SHEET
RMD
PROJECT f 1
FC05954.000
DATE. OF
08/03/12
SCALE, 1
1 /4,=l,-0"
• •
ii'Mot d Rh III
i N c o Q a o a a r c o
September 6, 2012
River Rock Commons
520 North Sherwood
Fort Collins, Colorado 80521
Attention: Paul Hegland
Building Maintenance Committee
Subject: Structural Engineering Consultation
Deck Guardrail Post Replacement
River Rock Commons, 520 N. Sherwood
CTLIT Project Number: FC05954.000-501 L2
Dear Mr. Hegland,
We previously made a site visit to the location referenced above to observe existing conditions of a
deteriorated deck guardrail post. Following the site visit, we presented you a letter and repair design
for the post (letter dated August 3, 2012). Since then, you have reviewed additional posts and two
have been identified as deteriorated. This letter is in regards to an alternative repair design for the
two additional deck rail posts at the subject location. You have requested that the alternative repair
not involve removing any portion of the existing log column.
Discussion/Recommendations
We recommend installing two Simpson MSTI straps at each deteriorated post. The straps should
be installed on the front and back sides of each post (on the outside away from the deck, and on the
inside facing the deck). Each strap should be attached with (13) SD#9x2-1/2" long screws on the
portion above the deck surface and (13) Simpson SD#9x2-1/2" long screws on the portion below (a
total of 52 screws per deck post). It is the contractor's responsibility to probe the wood and
determine where competent wood is located and where the deteriorated section at the deck is
located. The straps should be long enough so that the deteriorated area is bridged and that the
screws can be installed into fully competent material. As an alternate, thicker steel may be utilized
with the same number of screws.
Limitations
Our scope of services in this project is limited to the two additional deteriorated posts referenced
above. This report is based upon our site observations, a review of the documents provided (if
any), and our experience with projects of this type. Unseen defects may exist which could affect
the performance of the structure. We believe this investigation was conducted with the level of
skill and care used by structural engineers practicing in this area at this time. No warranty,
express or implied, is made.
Thank you for
additional servi
Very truly
CTLITHO
Rae Doner,
Project Eng
CTLITHOMPSON for your engineering needs. When we can be of
fggtact the undersigned.
46465
qi&/[?,
OO RFG� `
e • 'TH S%
Reviewed By:
y•
Wayne Thomooff;PE
Project Manag&Q0X •.,
35177
//Z