AIR LEAKAGE REPORT
Date: November 02, 2012
Building Name: PhilGreen Const
Owner's Name: PhilGreen Construction, Inc.
Property: 4820 Prairie Vista Dr
Address: Fort Collins, CO80526
Builder's Name: PhilGreen Construction, Inc.
Weather Site: Ft Collins, CO
File Name: 4820 Prairie Vista Dr-PhilGreen-REM13.blg
Whole House Infiltration
Duct Leakage
Ventilation
Rating No.: 26451
Rating Org.:
EnergyLogic, Inc.
Phone No.:
1.800.315.0459
Rater's Name:
Justin Heldenbrand
Rater's No.:
1088900
Rating Type: Confirmed
Rating Date: 11/1/12
Blower door test
Heating
Cooling
NaturalACH:
0.11
0.09
ACH @ 50 Pascals:
2.41
2.41
CFM @ 25 Pascals:
698
698
CFM @ 50 Pascals:
1096
1096
Eff. Leakage Area: [sq.in]
60.2
60.2
Specific Leakage Area:
0.000141
0.00014
ELAM 00 sf shell: [sq.in]
0.951
0.95
Leakage to Outside Units
Main
CFM @ 25 Pascals:
1
CFM25 / CFMfan:
0.0008
CFM25 / CFA:
0.0003
CFM per Std 152:
N/A
CFM per Std 152 / CFA:
N/A
CFM @ 50 Pascals:
2
Eff. Leakage Area: [sq.in]
0.09
Thermal Efficiency:
N/A
Total Duct Leakage Units
CFM251CFA
Total Duct Leakage:
0.0003
Mechanical:
Exhaust Only
Sensible Recovery Eff. (%):
0.0
Total Recovery Eff. (%):
0.0
Rate (cfm):
62
Hours/Day:
24.0
Fan Watts:
15.0
Cooling Ventilation:
No Ventilation
ASHRAE 62.2 - 2010 Ventilation Requirements
For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable IndoorAir Quality in
Low -Rise Residential Buildings, a minimum of59 cfm of mechanical ventilation must be provided continuously,
24 hours per day. Altematively, an intermittently operating mechanical ventilation system may be used if the
ventilation rate is adjusted accordingly. For example, a 118 cfm mechanical ventilation system would need to
operate 12 hours per day, as long as the system operates to provide required average ventilation once each
hour.
REM/Rate - Residential Energy Analysis and Rating Software v13.0
This information does not constitute any warranty of energy cost or savings.
01985-2012 Architectural Energy Corporation, Boulder, Colorado.
(DnergyLogic
a �> is9naen F
'�rpti analysis. Insight. answers.
P
COMPONENT LOAD SUMMARY
Date: November 02, 2012 Rating No.: 26451
Building Name:
PhilGreen Const
Rating Org.:
EnergyLogic, Inc.
Owner's Name:
PhilGreen Construction, Inc.
Phone No.:
1.800.315.0459
Property:
4820 Prairie Vista Dr
Rater's Name:
Justin Heldenbrand
Address:
Fort Collins, CO 80526
Rater's No.:
1088900
Builder's Name:
PhilGreen Construction, Inc.
Weather Site:
Ft Collins, CO
Rating Type:
Confirmed
File Name:
4820 Prairie Vista Dr-PhilGreen-REM13.blg
Rating Date:
11/1/12
PhilGreen Coast
HEATING SEASON (MMBtulyr)
Ceilings/Roofs
4.3
Rim/Band Joists
1.1
Above Grade Walls
13.4
Foundation Walls
12.8
Doors
1.7
Windows/Skylights
8.2
Frame Floors
0.2
Crawl Space/Unht Bsmt
0.0
Slab Floors
4.0
Infiltration
2.8
Mechanical Ventilation
9.5
Ducts
0.0
Active Solar
0.0
Sunspace
0.0
Internal Gains
-16.2
Total
41.7
REMIRate -Residential Energy Analysis and Rating Software v13.0
This information does not constitute any warranty of energy cost or savings.
01985-2012 Architectural Energy Corporation, Boulder, Colorado.
COMPONENT LOAD SUMMARY
PhilGreen Const. Page 2
PhilGreen Const.
COOLING SEASON (MMBtutyr)
Ceilings/Roofs
0.2
RimBand Joists
-0.2
Above Grade Walls
-1.0
Foundation Walls
-2.0
Doors
-0.2
Windows/Skylights
2.2
Frame Floors
-0.0
Crawl Space/Unht Bsmt
0.0
Slab Floors
-1.8
Infiltration
-0.2
Mechanical Ventilation
-1.2
Ducts
0.0
Active Solar
0.0
Sunspace
0.0
Internal Gains
11.0
Whole House Ventilation
0.0
Total
6.9
REMIRate - Residential Energy Anatysis and Rating Software v13.0
This information does not constitute any warranty of energy cost or savings.