HomeMy WebLinkAbout3409 Buntwing Ln - Special Inspections/Engineering - 09/26/2012KEM Homes, Inc.
7352 Greenridge Road, Unit A-6
Windsor, Colorado 80550
Attn: Ms. Cindy O'Neill (cindy@kemhomes.com
Re: Construction Observation and Testing
3409 Buntwing Lane
Fort Collins, Colorado
EEC Project No. 11-01-222
Ms. O'Neill:
On February 29 and March 1, 2012, a representative of Earth Engineering Company, Inc.
(EEC) provided construction observation and testing for the referenced project. The
construction observation and testing was completed on a part -rime, on -call basis and
included field density testing of fill placed to develop subgrade and foundation bearing
for the referenced. residence.. The results of the construction observation and testing
completed during the referenced period are included with this report.
On the referenced dates, an EEC representative completed field density testing on newly
placed structural fill materials in the area of the referenced residence. The field density
testing was conducted at random locations and elevations within the structural fill and
was performed in general accordance with ASTM Specification D-2922. Results of a
previously completed laboratory- standard Proctor test were used to calculate the percent
compaction achieved in the field. Since the fill soils used consisted of imported Class-7
granular structural fill materials, we recommended those materials be placed in loose lifts
not to exceed 9 inches in thickness and compacted to be at least 95% of the material's
maximum dry density as determined in accordance with ASTM designation D-698, the
standard Proctor procedure. It was recommended the materials be adjusted to a workable
moisture content at the time of compaction.
P.O. BOX 271428 P.O. Box 49322
FORT COLLINS. COLORADO 80527- 1 428 COLORADO SPRINGS. COLORADO 80949.9322
4970) 224.1 522 (FAX) 663.0282 (7191 442-6813 IFAX) 447-9635
£'d 9£ti6£990L6 I 'uoilonalsuoo s9wOH W3N e9Z:60 ZL 9Z deS
Earth Engineering Company, Inc.
EEC Project No. 11-01-222
September 20, 2012
Page 2
The final field density test results are shown on the attached summary sheet and met the
project requirements for compaction and, as such, could be used for support of the
foundation footings using the design net allowable total load soil bearing pressure of
1,500 psf
We appreciate the opportunity to be of service to you on this project. If you have any
questions regarding this report, or if we can be of further assistance to you in any other
way, please do not hesitate to contact us.
Very truly yours,
Earth Engineering Company, Inc.
Michael J. Coley, P.E.
Principal Engineer
MJC!dla
9-d 9£46£990L6 I 'uoilonilsuoO sawoH N3N e9Z:60 Zt 9Z deS
EARTH ENGINEERING COMPANY, INC.
SUMMARY OF FIELD DENSITY TESTS
Project Name: 3409 Buntwing Lane
Location: Fort Collins, Colorado
Proctor Designation
pass 7
Meximurn Dry Density;pol
127.0
Optimum Mdslure Content (%)
6.'
Recp6ed Moisture Vadance
WA
Required Percent Compaction
95%
D-698
ProjeetNo' 11-01-222
Date: March 2012
_
Fleld Test
Results
w oy
Compliance
Project Specs
vith
z
U
1
2
m
2729
2/29
TS
!
2
APP roximate Test Location / Notes
Overex Badr811- Basement. N W Corner
Overex Badddil1-BasemeM NE Comer
Overex Baddil •Basement SE Garner
Ovgrex BacklB -Basement, SW Come*
6+erez Badc81-Basement, NW Comer
Overex Backfill- Basement, NE Comer
O.erex eackfa- Saeement,. SE Comer
Overex Back9g- Basement. SW Comer
O+erex Back811- Basement NW Comer
Overex �I- Basement, WE Comer
Ove�mc BacxNl • Basement, SE Comer
Overex Backfi1- Basement, Sw Comer
Basement Ovefe¢avatlan: 30'W d. East edge& 26 S d North Edge
Basement Overexcave8cn: 20"7v of East edge 8, 20' S of North Edge
Basement pvuvexcavaton: IV W 0' East edge a 20, S d North Edge
Garage Overexcavelon: 3' N d South Edge& 15' W d East Edge
Geroge Gverexcavafior: 8' N d SarTh Edge& 2O West of E Edge
Garage Overexcavatlon: 8' N of South Edge& 8' W of East Edge
Garage OverexcavaUon: 8' N of South Edge& 2SW of East Edge
Garage Ovarexcavadon:8' N of South Edge& 15, %V of East Edge
Garage Ovenexcavation:8 N of Souh Edge& 3' W of East Edge
Basement overexcavatl= 17 E of West edge & IV N of South Edge
Basement Cverexcavallon: l0 E d West edge & 15' S of North Edge
Basemerd Overexcevation: 20' S cf Norh edge & 16 W of East Edce
Basement Overexcavatlon: 15' E of West edge 8 20' N of South Edge
Basement Overexcavalon: 20' E of West edge & 20' N d5cum Edge
Basement Overeuavallon:a- Nof South edge&2U'E of West Edge
-2.7%
•2.3%
-2.5%
-2.5%
-3.0%
-1.9%
-2.5%
-2.5%
32% 1
-25%
-2.9%
-2.4%
3.11e
-2.8%
-2.1 % -
-1.3%
-1.9%
-1.9%
-1.d%
-1.9%
.2.5 %
-22x
-2.5%
-2.0%
.2.0%
-20%
100%
9TA
96%
95%
100%
99%
98%
98%
100%
97W.
96%
98%
101%
99%
99%
9T%
99%
iDt%
701 %
97%
lot%
97%
97%
101%
101%
133%
98%
'»Camp.
IPau/
pall)
Pass
Pass
Pass
Pass
Pass
Pass
51
55
pan
Pass
Pass
Pass
Pass
Pan
Pau
PISS
Pass
Pass
pass
Pav^19
Pass
Pau
Pau
Pass
Paps
Pass
Pass
Pass
Pau
E1ev-/lu7t
Ne-
5.Cr
5.0
5.0'
5-C'
AZ
-40
-4Z
•4A'
3.0'
-3.0'
3.0
3.0'
-2A'
-20'
-2A'
-0Z
-3A
3.0'
-2.0'
-t 0'
SG
•1.0'
-1.0'
.1.0'
SG
SG
SG
Material
(Proctor)
Gass 7
Class 7
Class 7
Gass7
Cas97
Clasa7
Gass7
tlau7
tlass7
Class 7
C188s 7
Class7
Class
Gass 7
Clan 7Z4J0%127A
Cass
Class 7
pass 7-2.D°6
Cass 7
Class 7
Class 7
Clan 7
Class 7
Ckss 7
Class 7
Class 7
Class
cent D7�>(Pasa!
lure D 71
43,30%127.1
3.7% 1232
35%. 124.7
32% 124.2
3.0% � 126.8
3.1% 125.1
3.1%. 1229
3.5% 1Z4A
2.8% 1272
3.5% 123.4
3.1 % 125.0
3.6% '•24.1
2.9% 128.4
4.6Y. 122.9
4.1% 128.0
3.5% 123.2
3.8% 123.7
3.5°.5 128.7
4.0% 128.7
4.0% 130.4
4,0% 124.7
Moisture
(Pass
NrA
WA
WA
WA
WA
NIA
WA
MIA
NIA
NIA
WA
NIA
WA
WA
/A
N!A
WA
NIA
NIA
NIA.
WA
NIA
MIA
WA
WA
WA
WA
3
4
5
2/2B
y29
7129
3
<
5
6
2l29
2/29
6
7
a
7
8
2/29
9
10
2/i9
2/29
9
10
11
71
2129
12
13
14
15
18
17
2/i9
31
31
3'1
3�"1
3'1
12
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
18
311
3/1
3'1
3'1
3'1
3r1
V1
371
3/1
3N
20
21
22
23
24
25
26
27
L'd 9£b6£990L6 I 'uoipnj1suo0 SGWOH W3N eLZ:60 U 9Z deS
LUMMIAS
5 C-155�C=C-ITL_�5
HTRU pTUAAL EN�INEERG
March 27, 2012
Kern Homes
7352 Greenridge Road, A-6
Windsor, Colorado 80550
Re: Footings & Foundation Wall Steel
304 Buntwing
Fort Collins, Colorado
Project No. 211178
Gentlemen:
On March 6, 9, 26 & 27, 2012, a representative of Weeks & Associates observed
footings and foundation wall steel at the referenced site. Observations indicate the
footing sizes and foundation steel reinforcement are in substantial accordance with the
engineered electrode had been �placeon d rIn accordance witfor the project h y Weeks & Associates. In addition, the
h the recommendations by NEC.
If we can be of further assistance please contact us.
Sincerely,
Wee s & Associates; Inc,
ay
G• Weeks;,P.E.....••''
tructural Engineer
IL'd 9£46£990L6 I 'uo1lonjtsuo0 sewoH W3N e8Z:60 Zi, 9Z deS
September 20, 2012
KEM Homes, Inc.
7352 Greenridge Road, Unit A-6
Windsor, Colorado 80550
Attu: Ms. Cindy O'Neill (cindy&kemhomes.com)
Re: Foundation Drain and Damp Proofing Observation
3409 Buntwing Lane
Fort Collins; Colorado
EEC Project No. 11-01-222
Ms. O'Neill:
EARTH ENGINEERING
COMPANY, INc.
As requested, Earth Engineering Company, Inc. (EEC) personnel have completed the
construction observation services you requested for the referenced project. Those services
included observations of the foundation drain placement and damp proofing at the
referenced address. The results of those observations are included with this report.
On March 20, 2012, EEC personnel observed the foundation drain for the referenced
project. The foundation drain consisted of 4-inch flexible perforated pipe enclosed in a
filter sock and bedded in `pea' gravel around the below grade exterior perimeter of the
structure and was sloped to drain to a sump pit in the basement. The damp proofing
consisted of a grey spray -on coating that appeared to cover all exterior below grade living
areas of the basement walls.
We appreciate the opportunity to be of service to you on this project. If you have any
questions regarding this report, or if we can be of further service to you in any way,
please do not hesitate to contact us.
Very truly yours,
Earth Engineering Company, Inc.
Principal Engineer