HomeMy WebLinkAbout320 Kalkaska Ct - Disclosures/Mechanical - 09/14/2012City'of Fort Collins
Residential Mechanical Systems Performance Testing Submittal Form Ci`„Prs4�
This form is a record of testing targets and results, with PassfFail outcomes. For information on measurement tools and testing techniques, see the "Residential New
Constructbn Mechanical Systems Testing Guide." The guide and this form may be periodically updated; check the Building Services web site for the current version.
This form must be completed and signed by an 'Approved Agency,' and submitted to Building Services as a requirement for receiving a C.O.
Color key
Measured value to
Target or limit
compare with target
Pass
Fail
Caution
Other date
Testing date(s)
tth exhaust
Airflow measurement meth ow box _ Flow collar
P sstve flow hood Pilot tube traverse
Temperature of air throug Indicated flow to Volumetric flow muMpli r
measurement too 69 F ® 5000', air temperature1.098
Measured Exhaust Airflow,
Operation Minimum
Exhaust Pickup Location Intermittent or Airflow Indflo led Volumetric Flow PassFail
Continuous Req .i ." (CFM) (CFM 5,000�
masterBath
LIX640it _ Contin
50 cfm
159
164.782
U.L Bath
Lyntermit —Conlin
150 cfm
161
167_
—pl
Pwdr
-Lmtermfl _ Conlin
50 cfm
161
167
01
Intermit Contin
Intermit Conlin
Intermit Collin
Intermit Conlin
Intermit Contin
Kitchen exhaust
Oven fuel
1 '
(\�)
fie, y�^rExhaust
Lust
airflow
Minimum
rflow requiremen1CFM 5000'
Operatio
—Intermittent
—Continuous
red airflow
Airflow measurement method — Flow box _ Flow collar
Passive flow hood Pilot tube traverse
Temperature of air through F Indicated flow to Volumetric flow multiplier
measurement tool 0 5000', air temperature
Indicated flow FM Volumetric f1owCFM 5000' - a Pass [-13] Fail
Testing notes (fan speed, masking
flow out of range,...
Mechanical Systems Performance Testing Submittal FormV26120321 1 of 6
(sterns other than sub -structural floor exhaust
1Minimum
exhaust airflow requirement
46
FM 5000'
Indicated to
Measured Airflow
Volumetric
Design AfrOow;WMeasurement
Measurement Location +
Flow
Indicated Flow Volumetric
(CFM 5000')Method
Air Temperature (F)
Multiplier
(CFM) Flow
Pass/Fail
(CFM 5000')
boxTotal
exhaust airflow
— assve flow hood
_ Flow collar
Pftot tube traverse
pwdr
1.098
61
67
_ Flow collar
Total
- Pitot tube traverse
�_
�4LLL1
supplyairflow
_ Flow box
_�i'i
Passive Flow hood
systems in which supply airflow is circulatedtblhe air handler fan, fan speed for measuremen _ Heat Cooling Continuous fan
danced airflow in balanced systems
Average of measured supp Target flow ran
and exhaust fl CFM 5000' (average +/-15%) to CFM 5000
❑ Pass [ .Fail
Sub -structural floor exhaust
Design airflow
Measured airflow
CFM 5000'
Airflow measurement meth — Flow tax — Flow collar
_ Passive flow hood — Pitot tube traverse
Temperature of air through F Indicated flow to Volumetric flow multiplier Q
measurement tool a 5000', air temperature �j�I
Indicated flow CFM Volumetric flow CFM 5000'Lai Pass [ u ,Fail
Temperature of air throug 69 F
measurement too
House conditioned floor area 1542 =sf
Test Parameter and Conditions
Measurement
d leakage
d leakage
it leakage
to
Air Handier
Indicated flow to Volumetric Flow multiplier
0 5000', air temperature 1.098
Maximum Allowed Duct Leakage
Normalized Leakage Absolute
Leakage
(CFM25 / 100 at) (CFM25)
4
6
12
a 1128
Measured Duct Leakage
Indicated Flow Volumetric
Flow
48 153
3R
319
WIN
Mechanical Systems Performance Testing Submitlakfo V20120321 2 of 6
Filter type
1-1 Bran koch Type/sty, Dis sable Thickne 1" inches MERV(optional)�
Static pressures (OPTIONAL)
n cz , \ e axe -�
Mode: _ Heating
Cooling
Continuous Fan
\
P = + s
111
Fan speed tap
Humidifier bypass _ Open _Closed
registers open
AP AC coil =
rr
'
—Zone dampers open
■
P=
.8P fitter =
51\
aP Total ESP
P=_ 0
Cooling: Measured air flow throu h indoor coil usirg flow grid
Design cooling airfio 816 CFM soon' Target airflow limit (design +/- 15%) 694 to 938 1 CFM 5000'
Measured airflow
Cooling fan speed tap Med-High
Temperature of air throug
measurement too %0 F
HSOP 23.4 pa TFSOP 22.5 Pa
Measured airflow, no adjustments or correction ��CFM
Volumetric flo 830 CFMSOWC/ � S0—,Pass
Flow grid plate s 14 20
Indicated Row to Volumetric flow multipl r
0 5000', air temperature 1.098
Flow Resistance Correction Facto DG700
Adjusted (indicated) ahfio 756 FM
Fail
Heating: Gas manifold pressure
OEM manifold on, ssu
specification,specificaIWC Target manifold pressure limits (spec +/- 5%) IWC
Measured manifold pressu 3•4 IWC �1 `ri�Pass ul Fail
Heating: Temperature rise
OEM temperature rise limi XVb to F
Measured temperature rise
Return air •75 F Supply air 1115 F
Temp rise 4Q F pass a Fail ❑
Caution: Temp rise within
10 F of top of range
Mechanical Systems Perfomwnce Testing SuAmiUAfo V211120321 3 of 6
(This section under development, not yet being enforced)
Supply air flows (This section underdevelopment, not yet being enforced)
balance
difference limit, room -to -core -3 to +3 Pa
Room
Measured pressure
drop (Pa)
Pass
Fail
Master Bedroom
+2.3
bdrm over Garage
+0.5
—�
Bedroom 3
+0.6
study
+0.8
o�
Mechanical Systems Performanos Testing Submtltatfo V20120321 4 of 6
Outdoor temperature
Worst -case depressurization testing `
House setup
e of bath tans on
Vented range hood on
Clothes dryer on
Air handler on
r fans on
appliances
Applianc
Typ
Locadoi
Z pressure
BPI depressurization limit Pa wrt outside
Measured net CAZ depressur¢ationPa wrt outside
OK (less negative) I Caution (more negative)
BPI maximum limit
seconds
Measured spillage duration
seconds
Pass = duration not exceeding limit
ft pressure
BPI limit
Pa wrt CAZ
Measured
Pa wrt CAZ
Pass = pressure more negative than limit
concentration In undiluted flue gas
BPI maximum limit
ppm
Measured CO
ppm
Pass = CO level not exceeding limit
Caution = CO level 25 to 100 ppm
These doors are Closed:
_ Draft -hood
Induced -draft
_ Draft -hood
Induce"raft
_ Draft -hood
Induced -draft
❑ OK FMj Caution L K Mon ❑ K ILI Caution
100
100
100
❑ ass
i ail
ElPass
it
❑ ss
rl-0 aii
J0, ution
1911
Caution
I0& ution
Mechanicd Systems Performance Testing SubmineWo V20120321 5 of 6
System controls operating per design intent
SVAtPM
Pass
Fall
Localexhaust
Whole -house ventilation
7�F-
❑',
Sub -structural floor exhaust❑_
❑
Heating
❑
Cooling_
❑..
Approved Agency (technician performing inspection ad testing documented on this form
1Name (print) Paul Higman
Title Energy Rater
I
ICompany Thermal Concepts/ Allied
signature and Dam 09/14/20
HVAC contractor
Name (print)
Irene
I�f any
signature and Dam
Thomas
Northern Colorado
09/1
Mechanical Systems Performarce Testing Submittafo V20120321 6 of 6