Loading...
HomeMy WebLinkAbout2833 W Lake St - Violations/Building Code - 12/22/2005fort collies neighborhood & building services City of Fort Collins Y81 N. College AVG., P.O. Box 580• Fort Collins CO 80522-0580• Voice: 970 2216760 FAX 970 224 6134 Rental Housing Inspection Report Violation Notice December 22, 2005 Mary Zenzen 36682 Pauline Place Windsor, Colorado 80550 Reference: 2833 West Lake Street Fort Collins, Colorado 80521 Dear Ms. Zenzen, The Larimer County assessor's office lists you as the owner of the above referenced address. This letter shall serve as notice that an inspection of this address was recently performed, the purpose of which was to verify compliance with the Non -Owner Occupied Housing Standard, Fort Collins City Code Chapter 5 Article VI Division 2 (Rental Housing Code) as adopted by the City. The inspection identified that the basement has been converted and is being used a separate dwelling unit. This letter shall serve as notice that the basement is in violation of current zoning and building codes and shall not be considered nor rented as a separate dwelling unit. Zoning has never allowed this address to be a duplex and is zoned as a single family dwelling only. Because of the zoning for this address no permit could have or can be issued to create a legal duplex. The duplex use is illegal and not allowed and shall cease within 30 days of receipt of this notice. Failure to comply with the order to cease will result in a summons to appear in municipal court where fines of up to $1,000/day can be assessed. Additionally, as a single family rental property the following items were identified in the basement as needing repair: 1. The sewage ejector system is not protected by approved check valve. A check valve must be installed by a City licensed plumbing contractor with a report of such installation filed with this office. The ejector system has recently backed up and the surrounding floor must be professionally cleaned to assure that all contaminants have been removed. Provide a receipt for clean up by a professional cleaning company. 2. The inspector found: open bulb fixtures installed in the closet, mis-wired electrical outlets, paint embedded outlets, no smoke detectors, sewage ejector pump improperly wired, and some switches not working. Provide a report from a City licensed electrical contractor that the electrical system for the entire house has been checked repaired and is in good working order. 3. Provide a report from a City licensed mechanical contractor that the furnace and water heater have been serviced within the past 6 months and are in good working order. All repair documents shall be submitted to this office within 30 days of this inspection report. Michael W. Gebo Codes & Inspections Administrator