HomeMy WebLinkAbout2613 Stanford Rd - Special Inspections/Engineering - 02/26/2009 (2)WELD / BOLT INSPECTION REPORT SUMMARY Client Name: VILLAGE ON STANFORD, LLLP. Inspection Date: 02/26/2009 Project: 2613 STANFORD ROAD, FT COLLINS, CO Project Number: FC04399.000 Report Number: 1 TYPE OF INSPECTION / APPLICABLE CODE O Visual Weld AWS D1.1-02 Table 6.1 ❑ Magnetic Particle Weld AWS D1.1-02 Sect. 6.10 ❑ Liquid Dye Penetrant Weld AWS D1.1-02 Sect. 6.10 Location and Description of Work: WELDS Field Rep: JACK PAPPERT ❑ Ultrasonic Weld 0 Decking AWS D1.1-02 Sect. 6.13 AWS D1.3-02 Sect. 4.5 ❑ High Strength Bolt RISC Spec. for Structural Joints Using ASTM A 325 or A490 Bolts, Sect. 8 & 9. ❑ Anchor Bolts Project Specifications We made site visits on 2/25/09 and 2/26/09 to inspect the welding of the beam to beam, column to beam, column to pier sleeve, 29-gauge decking to purlins, and 29-gauge decking to beam connections for the carport structure at the Village of Stanford. We also inspected the #12 Tek Screw connections of the purlins to beam flanges and the #10 Tek Screw w/neoprene washer connections of the decking to purlins and beams. AWS D1.1, 6011 electrodes, 3/16" fillet welds in the H, V, and O positions. We inspected approximately 575 inches of welds and accepted 100%, of which approximately 2% had been rewelded. Plans were prepared by Carport Structures Corporation, Project No. 09-1323 (Village of Stanford), dated 1/19/09, page S-1. Our office will be contacted when additional inspection is requested. BOLTS l3 ��"gQt�c�btfadgbaa,! At the time of our inspection, the items observed met the quality standards sited above unless noted below. ❑ Discrepancies were observed, please see the attached Outstanding Discrepancies list. Specific information is presented on the following inspection reports. 351 Linden Street I Suite 140 1 Fort Collins, CO 80524 1 Phone: 970-206-9455 1 Fax: 970-206-9441