HomeMy WebLinkAbout5937 Greenridge Cir - Special Inspections/Engineering - 05/23/1994May 23, 1994
Project No: 1363-02-94
Jack Jennings
Clawhammer Consolidated
1029 Laporte Avenue
Ft. Collins, Colorado 80521
Re: Lot 23, Greenridge at Southridge Greens P.U.D.
9"7 Greenridge Circle; Ft. C0111=9 Colorado
Dear Mr. Jennings,
Shear Engineering Corporation has conducted observations at the above referenced address
throughout construction of the remodel improvements. As actual existing improvements were
exposed and confirmed, field design and construction modifications were made. All of these
changes were in association with basement improvements. A summary of the actual changes and
final installations are as follows. The attached plans note these changes for more understandable
reference.
1 The existing basement beam where the post was removed consisted of 2 - 1 3/4" x 11 7/8"
micro lams. One additional 1 3/4" x11 7/8" micro lam was added to this beam because of
the removal of the post.
2 A new footing pad was installed at the bottom of the basement stairs. Because there was a
substantial amount of gravel under the slab, direction was made to provide the new footing
pad on natural soils below the gravels. A 10" x 18" x 36" footing pad was provided.
3 The footing pad noted on the Post and Pad detail Q family room / bedroom was installed.
Because there was a substantial amount of gravel under the slab, direction was made to
provide the new footing pad on natural soils below the gravels. An 10"x24"x24" footing pad
was provided. The bottom of the footing pad is 30" below the finished top of slab grade.
Because of substantial settlement of a portion of the basement concrete slab in the extreme
northwest corner of the house, this portion of the basement slab was removed and will be
replaced.
There was concern that the foundation wall may also have settled because of the extensive
settlement noted in the basement slab. Shear Engineering made several elevation level shots and
determined that there was negligible difference in the shots made at the rear (north and west)
foundation walls and that settlement of the foundation wall is not a concern.
If you have any questions, please call at
0 20262
Brian W. Shear, P.E��
Shear Engineering Corporation
BWS / jmb
cc: City of Fort Collins Building Department