Loading...
HomeMy WebLinkAbout3540 John F Kennedy Pkwy - Correspondence/Backflow - 04/07/1998City of Fort Collins April 7, 1998 Water Utilities Stormwater • Water • Wastewater Cross -Connection Control Required Permit Application # 37168 3540 JFK Parkway, New "Paragon Office Building" A backflow prevention assembly is required on the water service. This must be an approved Reduced Pressure Backflow Assembly installed horizontally and accessible for testing. This assembly is designed to discharge water under a backpressure situation when the second check is fouled. It is also capable of a full discharge if the first check is fouled. Because of the possibility of this occurring the assembly must be installed in a location where there is adequate drainage for the size of the service. If there is a lawn irrigation system, an approved backflow preventer is required. A separate permit is required for a lawn irrigation system. Call for an inspection when assemblies are installed and tested. All backflow preventer installations must provide adequate clearances on all sides of the backflow preventer. If there are any questions concerning these backflow preventers please contact this office. John Nelson Cross -Connection Control Administrator 970-221-6677 P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6681