HomeMy WebLinkAbout512 Sycamore St - Correspondence - 07/27/2000DESIGNED STRUCTURES, INC. CIVIL ENGINEERING & DESIGN 4012 CLEVELAND AVE UNITS #6 P.O. BOX 303 WELLINGTON, CO 80549 PH: (970)-568-0212 FAX: (970)-568-9390 Email: designed@)earthlink.net July 27, 2000 FT. COLLINS BLDG. DEPT. 281 N. COLLAGE FT. COLLINS, COLORADO RE: TRUSS INSPECTION @ 512 SYCAMORE To Whom It May Concern: Our office has performed an "on -site" inspection of the existing roof substructure at the referenced address. Our inspection was limited to the area located on the west portion of the roof, which had previous fire damage. Based on our observation the rafters located directly above the brick chimney is in need of remediation. Our office recommends that the existing 2x4 roof rafters be left in place as well as installation of new 2x4 members alongside all of the roof rafters in the west roof section. The new 2X4 member shall be nailed @ 16" o.c. with 16d nails into the existing rafters and extend full length. We would furthermore recommend that a 2x6 collar ties be installed approximated 18° to 24" form the ridge board. We also noted that some of the roof sheathing is in need of repair. The sheathing areas in need of repair should be support with a new layer of 7/16" OSB board, cut to fit between the rafters and support with 2x2 or the new 2x4 members. The following is a sketch showing the west roof area and the rafter members. 5_12 SYCAMOAC / (Z:J,6 IRUAAl A)ZEA J _ �poo RFcs-Al-Xisc, a w 3 Please call if we can be of further assistance. Steven R. Stapp, P.E. DESIGNED STRUCTURES, INC. RAFt6RS 710 BE RE AA,,eC0 0014 43