Loading...
HomeMy WebLinkAbout400 S Meldrum St - Correspondence/Backflow - 11/08/1995Services Water & Wastewater City of Fort Collins Cross -Connection Control Required November 8, 1995 Permit Application # 25166 400 South Meldrum St.- Remodel for Lucile's Restaurant A backflow prevention assembly is required on the service connection at this address. This must be an approved Reduced Pressure Backflow Assembly installed horizontally and accessible for testing. This assembly is designed to discharge water under a backpressure situation when the second check is fouled. It is also capable of a full discharge if the first check is fouled. Because of the possibility of this occurring the assembly must be installed in a location where there is adequate drainage for the size of the service. Call for a test and inspection when assembly is installed. All backflow preventer installations must provide adequate clearances on all sides of the backflow preventer. If ther9151810 estions concerning these backflow preventers please contact this office. John Nelson Cross -Connection Control Administrator 303-221-6677 P.O. Box 580 - Fort Collins, CO 80')22-0580 - (303) 221-6681